Document 4axD5bmd0QODZ3g3wEbjrLJkR
Diameter of Branch Pipe
F ig. 5. M a in and B ranch Pipes for' Equal F riction per F oot of L ength
(20 to 100 Per Cent Capacity)
American Society of Heating and Ventilating Engineers Guide, 1934 262
Chapter 19--Air Duct Design
Example S. Suppose a 60-in. main pipe is to be used, and it is desired to know the size of branch pipe required to carry 50 per cent of the total air in the main. Find 50 per cent at the left of the chart, move right to the 60-in. diagonal line and note directly above at the top of the chart that the.branch pipe will be 46.5 in. in diameter.
Where rectangular ducts are used it is frequently desirable to know the equivalent diameter of round pipe to carry the same capacity and have the same friction per foot of length. Table 1 gives directly the circular equivalent of rectangular ducts for equal friction and capacity. To obtain the size of rectangular ducts for different capacities, but of the same friction per foot of length, first obtain the equivalent round pipe for equal friction. Thus, if a branch of sufficient size to carry 30 per cent of a 12 x 36-in. pipe is desired, it is found from Table 1 that the main is equivalent to a 22.2 in. diameter round pipe. From Fig. 5, 30 per cent of this is a pipe 14.3 in. in diameter, and referring again to Table 1, the rectangular equivalent branch is a 12 x 14-in., 10 x 17^-in., or any other desirable combination.
Multiplying or dividing the length of each side of a pipe by a constant is the same as multiplying or dividing the equivalent round size by the same constant. Thus, if the circular equivalent of an 80 x 24 in. duct is required, it will be just twice that of a 40 x 12 in. duct, or 2 X 23.3 = 46.6 in.
DUCTS FOR PUBLIC BUILDINGS
A main duct with branches is generally used to convey tempered air for ventilation purposes only. In place of individual ducts, a compara tively large main duct supplies air by branches to the room or rooms. The velocities vary according to the nature of the installation and the degree of quietness required. At the start of the run a velocity as high as 2000 fpm may be used, but this is considered the maximum for public building work, and is reduced to from 400 to 800 fpm in the risers. This duct system may be designed so that the loss of pressure in the branches is equalized in a manner similar to that previously described.
Example of Equal Friction Method
Examples. Fig. 6 shows a typical layout of an air distribution system which is
applicable for ventilation of hotel dining rooms, offices, etc.
The volume of air in cubic feet per minute for the room is determined on the basis of
the number of air changes per hour required. In the example shown, the room ventilated is a hotel dining room 135ftx85ftxi5ft. A7^-minute air change (8 air changes per hour) is assumed for proper ventilation, giving 22,935 cfm as the air required.
22 935
The clear area of the fresh air inlet is based on a velocity of 1000 fpm or
=
22.94 sq ft. If the air washer is provided with automatic humidity control, the tempering coil should raise the temperature of the entering air to 32 F. The washer with its auto matic control will then raise the temperature from 32 F to 42 F. If the washer is not provided with automatic humidity control. the tempering coil must raise the temperature of the entering air to at least 55 F to allow for some temperature drop in the washer due to evaporation. The reheating coil is selected to raise the temperature of the air from that leaving the air washer to 70 F. The air washer should have a maximum velocity of 500 fpm through the clear area, which, in this case, is 46 sq ft. For more detailed infor mation on tempering coil and air washer control, see Chapters 23 and 14.
Since the plan shows a moderately short run of main .duct with no risers near the fan outlet, a fan should be selected which will have the required capacity of 22,935 cfm with a maximum velocity through the fan outlet of 1400 fpm. The outlet area, therefore, should be 16H sq ft.
263