The ulUity usually selects protective equipment when it supplies power, except when the customer owns and operates the primary substation. Proper protec tion oi plant generators, particularly against short circuits, is always the power engineer's job.
Today's generators have protective devices that 11) cut down burning oi iron and insulation on an internal tault 12) prevent dangerous heating oi gen erator (rom any prolonged short circuit. Generator short-circuit devices (all into three classes. Dilioroniial relays compare currents in opposite ends
of generator phase windings, operate when current
going in doesn't match that coming out. Essentially independent oi load and fault-current magnitude, these relays are quite sensitive.
Overcurrent protectors operate when current ex
ceeds preset amours!. These include fuses, direct, ing trip coils and straight overcurrent relays, must trip fast on shorts but not act on permt*8Si overloads. With loses, instantaneous trips and r^ui*'
current magnitudo alone iixes when and how " device operates. Time-delay relays and trips mechanically adjustable operating speed.
V'o/tage-restrained relays measure current one voltage to determine when and how fast to operoti General agreement prevails that; (1) Induction over current.relays and air breakers with direct^ trips often fail to give selective short-circuit pro/
lection because of decrement of generator shortcircuit current. (2) Overcurrent relays with voltage restraint or equivalent con be Incorporated to permit coordination with feeder breakers.
Voltage and current relaying both ploy part in today's generator hall protection'
WWhhrre nneeuuttrraall,. oo(f tfoaww-.vvonlhtaTMge....g...s..n..a..r.a..lora (under 600 v) are to be grounded, current-limiting reactor, hold lino-faground fault* to *iie of 3-phase fault currents. General practice an highervoltage generators (2300 v and above) Is to ground the neutral through a resis tor. fn this case, ground current Is limited to a still lower value but not less than rating at target! cl in the circuit, lo in sure satisfactory relaying. This limitation minimises damage during short circuit yet maintains advantage ol a groundedneutral system.
Short-Circuit Protection. Ctn with ihe above grounding practice, there still re mains the problom ol gelling adequate short-circuit protection where current magnitude atone is depended on for operation. The reason: By the lime we want'the generator breaker to operate, there may no) be enough dillorence be tween fault current and pormfMfblo short-lime overload current to insure positive operation without running risk
ol false operation. And the breaker still must be tripped to break possible are al tho.fault point even though current mag nitude isn't excosslvo.
Years back, generators wete otton oporaiod without protection against ex terna) faults other than leader overcurrent rofaylhg and differential protection around the main bus. Desiring to avoid shutting down generators U al all possi ble, some utilities still follow this proclice (Power, April 105). pp 94. 95}. Station operators are expected to spot trouble and take stops to dear Ihe fault. This practice.was born ol the fact that no device was available that could trip the generator breaker on a sustained fault without running ihe risk ol unnecessary shutdowns because of what might be called ''normal" surges.
Hew Practice. This approach Is changing since ihe advent ol ihe overcurrent relay with voltage restraint. This relay can. In oiled, site up a given current and decide whother it is a permissible overload or a
H >mtOn
fault. Sensing ability of Ihe relay corns* from taking slock oi voltage at the tin* ovorcurrent Hows. When voltage J* nor- i mal or dose to U. overcurrent Is a normal '* surge. And voltage coil keep* relay hem operating. Bui as voltage goss lower, approaching sere for a solid Xphav* short, the curront coil trips the generator breaker-
some monulaclureTs recommend such protection for al) Industrial generators of 2300 v and above. Actually, tho scheme Is fun os desirable on lower voltages but cost often rules it out. Direct-Acting Tripe. Since we're speak ing of small machines, why can't directacting trip coila of (ow-voltage broaters be used for short-circuit protection, at toast at 600 v and befov? They ore used. But don't depend on ihem t kA* means oi generator protection. They're nol In ihe same league with overcurrent relays since they otlen can't dis tinguish between permissible overload and fault current.
Overhead grounding lines help bock up lightning arresters in primary substation.
If there's overcurrenl protection on Incoming lines and plant primary foedcr*. proleclion el transformer is main ilom al Ihe primary substation. Translormor winding* should bo guarded agalnsi: (I) surge voltage or lighining (2) overload.
Transformer-winding insulation can be stressed to voltages higher than normal ae a result ol lightning striking overhead lines or of surges from switching. Practical way to Until such peaks (not now) is with lightning arresters or spark-over gap* between line and ground. Surge current has a (ow-)mpedonc* path to ground when gap breaks down.
But arrostor must not break down oi norma) voltages. And transformer Insulation must stand up under voltage surge* permitted by the arrester. Today.'operating portion al arrests/* Is a ceramic material, able lo acl as on Insulator al one voltage and as a good conductor at a higher voltage.
The artester has limitations; it often can't handle a dWetl strike. Hence the overhead ground wire. Grounded overhead line it about the beet way to divert any dlrocl strikes.
TODAY'S EICCTtfCAl MACTICl
SOWER
carrying electricity to the job
* Which Systom? Modem lood-cenler idea is applied many ways, ^osi widely used system is (he simple radial, but others may fit roue needs belter. Trend is lo neutral grounding, higher voltage.
Distribution Components. Packaged unit substations ore ecoimical, flexible. Askaref and dry-type iranslormors gain ground, teck into new armored high-voltagecables, aluminum conduciors.
Circuit [nlorruplion. in today's ptanls. interrupting copacify ws ever more important. Air breakers now handle mosl jobs, w high-rupluring-capocily fuses offer interesting possibilities.