CHAPTER 26
1949 Guide
trap for handling both the condensation and;the air, provided the air, finally can be eliminated at some other point in the return system., '
For high pressure, systems the same kind of traps,may be used as with .vacuum systems, except that they must be constructed for the pressure, used. . If the air is to be eliminated at the return header of-the unit, a high pressure air valve.can be used; otherwise the air.may be passed with the condensate through the high-pressure return trap, and then eliminated at some other point in the system. .
Fig. 8 represents the connections to a hot water heating system: . The air vent is not required if the main is above the heater and air can be eliminated through the piping system.
UnitUeaters, Unit Ventilators; Unit Humidifiers
555
not less than 5 lb should be maintained on the heating element, or a corre sponding differential in.pressure between the supply and retums should be maintained by means of a vacuum.'
UNIT VENTILATORS
A unit ventilator is essentially a unit heater equipped -with dampers for introducing outdoor and recirculating air in varying quantities, and arranged with a system of control that permits the heating effect ,to be varied with the fans operating continuously. Either steam or forced .hot water may be employed as the heating medium, although steam is the more common. Unit ventilators are intended primarily for use in schools, meet ing rooms, offices or other applications where the density of occupancy indicates the need for ventilation. In normal operationj the discharge air temperature from a unit ventilator is varied in accordance with the room
BOILER CAPACITY FOR STEAM UNIT HEATERS
The capacity of the boiler should be based on the rated capacity of the
unit heiters at1 the lowest entering air temperature and highest fan speed
that will occur, plus an allowance for -pipeline losses. -It is^unwise-to
install a single unit-heater, as the sole load on any boiler,, particularly if'
the unit heater motor is started and stopped by thermostatic'control.; The
wideband sudden fluctuations of load that occur under.,such-.conditions
would require closer attention to the boiler .than is usually:possible in a
small installation.- Where oil or gas is used to fire the boiler, it is possible
by,means of a; pressurestat to control the boiler, in response, to. this rapid
fluctuation., in most cases, and particularly where the boiler is coal-fired,
it is advisable, to use two or-more smaller unit.heaters instead of`one large
unit-. .
...
j H, C r
Steam pressures below 5 lb can be used with safety for recirculating unit'
heaters when their heating surfaces are designed for. those pressures, and
when proper , provision is. made for returning the .condensate. . If . uiiits
admit air that maybe at a temperature below freezing, a steam pressure of
!'Piq,;9. Typical Unit' VENTiLATbiis Showing Two op Many Abbangements `
; ; ; rv. '
of Dampebs and Heating Coils
'' ."
' .i
demands.. -Where a heating effect .is required, the air delivered is above room temperature. Where the. heat, generated within the; room by occupants, sun; etc., is sufficient to cause overheating, then the air delivery tem perature must be below that of the rooms. It is customary to equip unit ventilators with control devices that prevent the delivery of air at a tem perature that will cause cold drafts. Uriit; ventilators may be of the radia tor or damper controlled, type constructed on the blow-through or draw-through principle as illustrated in Fig. 9, ,,
Ratings of Unit Ventilators
Unit ventilators of the steam type are customarily cataloged with two ratings, one the input and the other the output capacity. The first is the heat input to the unit which is determined by measuring the temperature and quantity of condensate and the pressure and quality of,.the .steam. The second is the heat output of the imit which is determined by measuring