Document 4JrqmyB42VX4DELavy8pVo0gp

558 CHAPTER 21 1958 Guide personal preferences of the purchaser, the designer- should make certain that the heat output at the water temperature available is equivalent to the calculated heat loss from the space. The heating units within each separately controlled circuit should be of similar types, for example; either all cast-iron or all fin-tube convector type units. Fan units should not be included in a controlled direct radiation zone. The radiation should be located at points of maximumheat loss ,or along outside walls, unless this is impracticable. Determination of Water Flow Rate The rate of water flow in a system is determined by the heat carrying capacity of the water. This capacity is the product of the rate of flow, the specific heat, and the temperature drop of the water as it passes through the heating units. The equation generally used to describe this relationship is: where H = Wc(h - U) (1) H = heat carrying capacity, Btu per hour. W = mass flow or weight of water, pounds per hour, c = specific heat of water. <i = temperature of water entering heating unit. <, = temperature of water leaving heating unit. The equation may be rewritten as follows for the purpose of convenience in use with Fig. 2. H = Gwc(li -- ti) (2) where G = rate of water flow, gallons per minute. to = rate of water flow per gallon per minute, pounds per hour. The value of to should be obtained from Fig. 2 for the temperature at which the rate of flow is determined, and the value of c should be determined at the average temperature. For example: If water enters a heating unit at 210 F and leaves at 190 F, and a water flow of 1 gpm is measured at 190 F, the heat carrying capacity, found by substituting values from Fig. 2 in Equation 2, is H = (1) (484) (1.005) (210-190) = 9728.4 Btu per hr or 9.73 Mbh At 60 F the mass flow rate is 500 lb per hr at 1 gpm and the specific heat is very close to 1 Btu per lb, F deg. Accordingly, at a 20 deg temperature drop, 1 gpm will release 10 Mbh. This value, 10 Mbh per gpm of water at a 20 deg temperature drop, is extensively used throughout the hot water heating industry in the calcula tion of data for low temperature systems. It is considered well within the limits of accuracy of heating system design. If 1 gpm will release 10 Mbh at a 20 deg drop, it will release 15 Mbh at a 30 deg drop, and 20 Mbh at a 40 deg drop. Most low temperature systems installed today are designed on the basis of a 20 deg temperature drop. The temperature drop selected in the de sign of a system is used to determine the water flow necessary to supply tbs heat required under conditions of maximum heat loss with supply water temperature at a maximum value. If the supply water temperature is in- Hot Water Heating Systems 559. creased'at any time, the capacity of a. heating unit and the temperature! drop of water through the unit is increased accordingly. When the supplywater temperature is modulated according to outside temperature, the tern-' perature drop of the water in the system is considerably less than the. design value during the greater part of the heating season. The use of a design-temperature drop greater than120 deg should be con-! sidered where large quantities-of required ventilation air are heated with' extended surface coils, where the required pumping capacity is high, where pumping costs are a critical item, and where extended systems make a sav ing by the reduction in pipe size possible. Factors considered in selection of a proper temperature drop for a system are: (1) the effect of the design average water temperature and water ve locity on the capacity and cost of the heating units, (2) the size and cost of the piping, and (3) the initial and operating cost of the pump. Design Water Temperature The design supply water temperature is the maximum temperature of the water supplied to the system for the purpose of developing the selected rated capacity of the heating units. The design average water temperature of a hot water heating system is the design supply water temperature less the design temperature drop. Capacities of heating units are generally determined on the basis of the de sign average water temperature for cast-iron radiation and for baseboard or finned pipe radiation. Where a greater degree of precision is required to establish the capacity of heating units, for example, for contract and com petitive bidding work, it may be desirable to determine heating unit capac ities on the basis of design supply water temperature and temperature drop through the unit. This is particularly true where the secondary heating surface in the heating element of the unit is a large percentage of the total heating surface, as in convectors. Design supply water temperatures for Ration systems vary from 180 to 250 F, a common temperature being Factors considered in the selection of a design supply water temperature are the effect on the capacity of the heating unit, the effect on occupants who may be near the unit, and the greater possibility of boiling as the pres sure varies. Pipe Sizing Methods I?16 theoretical basis of calculations of head loss due to friction of fluids m Pipe is the Darcy or Fanning equation, discussed in some detail in Chap ter 4, Fluid Flow. s'zes ter hot water heating systems are determined most conveni- y from charts such as Figs. 3 to 6 and Table 1 showing pressure loss in ation to rate of flow and size of pipe. Allowance for fittings is generally wrv'uf k m e'b?w equivalents which is the number of 90-deg elbows that tTvahulk ,,9 ave e'-'qiuuiivaileniat fmrioction loss at thne same rate ofi fnlow. FJig. 7t anda then6 ^ ai? usetel in determining the numiber of ellbbeow equivalents which Figs 7 converted to equivalent length of pipe 1by means of Table 3. velonpH k ` an^ tables 1 to 3 are based chliieefly on enmpirical equations de- Univer i Giesecke in cooperative rreesearch with the Society at the n,n,,^, "*7 rj Texas aaunud mthee EEnngginineeeerriningg EExxppeerrimimeenntt SSttaattioionn ooff tthhee AAggrir-i^ural and Mechanical College of Texas}-" e friction loss used in sizing pipe for a system depends upon the type