Document 4Jk9rLMDY3N9DawBeY7J2D4xx
586;
CHAPTER 27
1950 Guide:
Insulation can materially prolong the time required, for the water, to give up its heat, and if the velocity of the water flowing in the pipe is main tained at a sufficiently high rate, freezing may be prevented.
Table 9 may be used for making estimates of the thickness of insu-. lation necessary to take care of still water in pipes at various water and surrounding air temperature conditions. Because of the damage and service interruptions which may result from frozen water in pipes, it is essential that an efficient insulation be utilized. This table is based on the use of a material haying a conductivity of 0.30. The initial water tem perature is assumed to be 10 deg above, and the surrounding air temperature 50 deg below the freezing point of water (temperature difference, 60 F).
. The last column of Table 9 gives the, minimum quantity of water at initial temperature of 42 F which should be; supplied every hour for each linear foot of pipe, in order to prevent the temperature of the water from
Table 9. Data fob Estimating Requirements to Prevent Feeezinq of Watbb in Pipes with SubboundIno Aib at --18 F
being lowered to the freezing point. The weights given in this column should be multiplied by the total length of the exposed pipe line expressed in- feet. As an additional factor of safety, and in order to provide against temporary reductions in flow occasioned, by reduced pressure, it is ad visable to double the rates of flow listed in thk table. It must be empha: sized that the flow rates and periods of time designated apply only for the'
conditions stated. To estimate for other service conditions, the following method of procedure may be used.
If water enters the pipe at 52 F instead of 42 F, the time required to
cool it to the freezing point will be prolonged to twice that given in the
table, or the rate of flow of water may be reduced so that the quantity
required will be one-half that shown in the last column of Table 9.
However, if the water enters the pipe at 34 F, it will be cooled to 32 F in
one-fifth of. the time given in the table. It will then be necessary ,to
increase the rate of flow so that five, times the specified quantity of water
will have, to be supplied in order to prevent freezing.
- If the minimum air temperature is --38 F (temperature difference 80 E) instead.of --18 F, the time required to cool the water to the freezing point
Pipe Insulation
587
will be 60/80 of the time given in the table, or the necessary quantity of water to be supplied will be 80/60 of that given.
In making calculations to arrive at the values given in Table 9, the loss of heat stored in the insulation, the effect of a varying temperature 'difference due to the cooling of pipe and water, and the resistance of i the, outer surface of the insulation to the transfer of heat to the air, have all been neglected. When these factors enter into the computations it is necessary to enlarge the factor of safety. Also as stated, the time shown in the table is that required to lower the water to the freezing point: A longer period would be required to freeze the water, but the danger point . is reached when freezing starts. The flow of water will stop and the entire line will be in danger as soon as the water freezes across the section of the pipe at any point.
When water must remain stationary longer than the times designated in Table 9, the only safe way to insure against freezing is to install a steam or hot wateir line, or to place an electric resistance heater along the ,
Table 10. Thickness, of Pipe Insulation Obdinabily Used Indoors4
Steam Pressure Psig
or Condition
0 to 25 25 to 100 100 to 200 Low Superheat Medium Superheat High Superheat
Steam Temperature Fahrenheit Degrees
212 to 267 267 to 338 338 to 388 388 to 500 500 to 600 600 to 700
Thickness op Insulation
Pipes Larger Than 4 In.
1 in.
IH m-
2 in. 2K in.
3 in. 3Hla.
Pipes 2 In. to
4 In.
1 In.
1H in. *2 in.
2K 3 in.
Pipes K In. to IK In.
1 in.
1 in. IK in.
2 In. 2 in.
side of the exposed water line. The heating system and the water line are ; then insulated so: that the heat losses from the heating system are not excessive, and the heating effect is concentrated against the water pipe where it is needed. For this form of protection 2 in. of an 'efficient insu lation may be applied.
ECONOMICAL THICKNESS OF PIPE INSULATION
The thicknesses of insulation which ordinarily are used for various temperature conditions are given in Table 10. Where a thorough analysis of economic thickness is desired, this may be accomplished through the use of the chart, Fig. 6.
The dotted line on the chart illustrates its use in solving a typical example. In using the chart, start with the scale at the left bottom margin representing the'given number of hours of 'operation, per year; then proceed vertically to the line-representing the given value of heat; : thence , horizontally to the right, to the line representing the given tern-' perature difference; thence, vertically to the line representing the con.ductivity of the given material; thence horizontally to the left, to the line representing the given discount on that material; thence vertically to the curve representing the required per- cent return on*:the investment; thence horizontally to the right, to the curve representing the given pipe