Document 4JK1LMxnEy2GG7v4rwgDBYxbQ
294
CHAPTER 15
1948 Guide
.Section
Party wall............................ ;..... Door............................................
Net Area Sq Ft
1065s 35
u
Btu/(Hr) (Sq Ft) (FDec)
0.26 : 0.59
(/p *i)
F Deg
2.8 14
Total. .......
<z
Btu Per Hr .
.775 290
1065
Calculated from gross wall.area less door area.
Heat Cain Through Glass Areas.
In computing the load for 3:00 p. m., only the south windows and doors will be exposed to direct sunlight. Table 15 and Equation 12 will give the total heat gain from the glass areas. The window reveals will slightly shade the south windows; the fraction of window area receiving direct radiation is obtained from Equation 13 by substituting values as follows:
n = s/1 = 4/60; rs = 4/36; (J -- 45.5 deg, tan (5 = 1.02. T = 16 deg, tan y = 0.287.
Gi = 1 -- ^ X 1.02 - ^ X 0.287 + ^ X ^ X 1.02 X 0.287 = 0.902.
The south doors will be considered entirely sunlit. The outdoor air temperature is 94 F at 3:00 p. m. From Table 20 the inside Venetian blind factor is taken as 0.75. Referring to Table 15 the instantaneous heat gain due to solar and sky radiation for' 40 deg n. latitude for south exposure at 3:00 p.m. is read as 42 Btu per sq ft. These figures are tabulated below. 60 X 0.902 X .75 X 42 = 1705 Btu per hr. The normal
transmission 60 X 1.04 (94 -- 80) = 874. The sum of these heat gains is totaled in last column. The remaining doors and windows are calculated in a similar manner.
Location
Abba
Sq Ft
South windows......
doors.- ............... North windows.....
60 35
18 35 30
Fraction Sunlit
0.902 1.00
Inside Venetian
Blind Shading Factor
0.75
Solar Heat Gain
Radiation Heat Gain*
Btu/Sq Ft
Btu/Hr
42. 1705. 42. 1470. 15. 27.
270.
15. 450.
Normal Heat
Transfer
Btu/Hr
874. 510.
510. 437.
Total___
Total Heat Gain
Btu/Hr
2579. 1980.
780. 887.
6226.
See Equation 12 and the note under caption of Table 15. bDoors are H glass. Calculate sky radiation for glass portion and normal transmission for entire door assuming U -- 1.04 for wood portion as well as glass.
In some jobs it would be proper to increase (or decrease) the instantaneous radiation heat gain by a load-lag factor. The reason for not doing so in this case is that the solar gain is of a low magnitude and reference to the table indicates that 0.8 of the-previous hour would not affect the results materially.
Heat Gain From Ventilation and Infiltration.
Since the necessary ventilation rate of 1275 cfm is greater than one air change per hour, it will be satisfactory for determining the ventilation component of the heat gain.
Window infiltration will be taken as negligible since the windows do not open and the ventilation rate is almost 2 changes per hour which is sufficient to prevent normal expected infiltration through closed windows with storm sash. .
Door infiltration requires some judgment. Assume that for each person passing through the double doors, the infiltration will be 100 cu ft of outdoor air, see Table 21. Assume that the outside doors will be used at the rate of 10 persons per hour, and the inside doors at the rate of 30 persons per hour. Total infiltration will then be 40 X 100 =4000 cfh or 67 cfm.
The design rate of entry of outside air is then
Q = 1275 + 67 = 1342 cfm.
Cooling Load
295
The sensible, latent and total loads are determined from Equations 15, 16 and 17, respectively at 3:00 p. m. (Table 10) to = 94, t\ -- 80, W0 = 0.0169, W\ = 0.0098.
qs = 1342 X 1.08 (94 - 80) = 21,700 Btuh.
<Ze = 1342 X 4840 (0.0169 - 0.0098) = 46,100 Btuh. gt = Ss + ge = 21,700 + 46,100 = 67,800 Btuh.
Heat Gain from Sources Within the Conditioned Space.
For the occupants, use the data of Table 22 for moderately active office work. Sensible heat = 85 X 200 = 17,000 Btu per hr. Latent heat = 85 X 250 = 21,250 Btu per hr.
Total = 38,250 Btu per hr.
For the lighting, use Equation 18 with a use factor of unity, and a special allowance factor of 1.20 for the fluorescents and of unity for the tungsten globes:
gel = (12,000 X 1.20 + 4000) X 3.41 = 62,700 Btu per hr.
For the fan motor; use Equation 19 with a load factor of unity and do not introduce the motor efficiency because of the motor being external to the space.
gem = 7.5 x 2544 = 19,100 Btu per hr. .
Moisture Permeation, Miscellaneous Allowance, and the Load-Lag Estimate.
Moisture permeation will be negligible, since this is a comfort job with a good building construction.
There would be some heat gain in the ductwork, but this would not be great because of the short run involved. Practical judgment on this job would suggest that no adjust ment for load lag need be made to the load as computed. While it is true that inside radiation forms an important part of the total heat gain, it is advisable to be conservative in recognizing the effect of the large, flat, hot roof on the comfort sensations of the occu pants. Radiation from the relatively low. ceiling, augmented by heat absorption from the lighting fixtures, would produce a sensation of warmth in excess of the nominal effective temperature (see Chapter 12) established by the wet-bulb and dry-bulb tem peratures. Hence, it is not desirable to take advantage of every small decrease possible in the peak design load, especially since the peak occurs in mid-afternoon when every thing would be rather well warmed.
Total Loads and Required Air Quantity Through Conditioning Equipment.
The total loads are summarized below.
Load Component
Party wall and inside door..................................... Ventilation and infiltration....................................
Sensible, Btu Per Hour
116,720 ' 1,065 6,226
21.700 17,000 62.700 19,100
244,511
Latent, Btu Per Hour .
46,100 21,250
'
67,350 311,861
Compute the specific enthalpy of the water removed from Equation 22.
gw =
X 1076 = 3900 Btu per lb.
From the Mollier diagram, determine that the apparatus dewpoint is 47.9 F. (Refer to Chapters 3 and 43.)
In computing the effective air quantity, assume a coil efficiency of 85 per cent. Then,
Qra
--
244,500 1.08 (80 - 47.9)
X 0.85
=
8300 cfm.
(Refer to Chapter 25 for coil selection and efficiency.)