Document 44epvgRj6r5XmpBE13vJaeZJR

500 CHAPTER 34 1959 automatically controlled, their sequence of control is similar to that described for horizontal rotary-cup burners. 3. Qas Burners. Some of the more common primary con trols for gas burners are as follows. a. Domestic gas burners of the atmospheric type require a primary control, to insure safe starting and operating con ditions, which will (1) prevent opening of the gas . valve unless the pilot is operating properly, and (2) stop the flow of gas through the burner if safe ignition conditions do not prevail. at all times. b. Commercial and industrial gas burners of the atmos pheric type require a primary control whose function is similar to that for domestic sizes of these burners except in the rate of response to a" pilot flame failure. The pilot flame burns constantly' and, in general, the primary control systwn will (1) ensure operation only when ignition of the main burner will be safe; (2) start and stop the main burner when required to do so by either the operating controller or a limit control; and (3) dose the safety shut-off valve in the gas supply line to the burner upon a flame failure or an electrical power failure. c. Commercial and industrial gas burners of the power type equipped with electric ignition require a primary control whose most important operations include: (1) starting the burner motor upon a call for beat by the oper ating control; (2) providing a prepurge period before ac tivating the gas-electric ignition; (3) proving the presence of proper ignition before allowing gas to flow to the main burner or shutting off the electric ignitor; (4) closing the safety shut-off valve in the event of a flame failure (it is usually required that the flow of gas be stopped within four seconds following a flame failure); (5) stopping'the burner when either'an operating controller or a limit control re quires it; and (6) locking out on a flame failure shut-down (the programming control then must be manually reset prior to a restart). REFERENCES 'Domestic Burners for Pennsylvania Anthracite (Under feed Type) (U. 8. Department of Commerce, National Bureau of Standards Commercial Standard No. CS48-40). * Industry standards, recommended practices, technical in formation (Stoker Manufacturers Association Manual, Stoker Manufacturers Association). 'Code for determination of rated capacities of anthracite underfeed stokers, adopted June l, 1944, and Code for deter mination of rated capacities of bituminous underfeed stokers, adopted May 3, 1944 (Stoker Manufacturers Association Man ual, Stoker Manufacturers Association). 'Automatic Mechanical Draft OH Burners Designed for Domestic Installations (U. S. Department of Commerce, Na tional Bureau of Standards Commercial Standard No. CS7542). Fhie Connected Oil Burning Space Heaters Equipped with Vaporizing Pot Type Burners (U. 8. Department of Com merce, jVaJtona/ Bureau of Standards Commercial Standard No. CS101-43). Warm-Air Furnaces Equipped with Vaporizing Pot-Type Oil Burners (U. S. Department of Commerce, Na tional Bureau of Standards Commercial Standard No. GSI0446). Oil-Burning Floor Furnaces Equipped with Vaporizing Pot-Type Burners (U. S. Department of Commerce, National Bureau of Standards Commercial Standard No. CSl 13-44). BIBLIOGRAPHY A. J. Johnson: Performance expectancy of domestic under feed stokers for anthracite {AIMS Transactions, Vol 119 1936). R. A. Sherman, E. R. Kaiser, and H. R. Limbacher: The Re lation of the Size of Bituminous Coals to Their Performance on Small Underfeed Stokers--Burning Tests on Four Typical Coals (Bituminous Coal Research,-Inc., Technical Report No. 1--Part n, July 1937). J. A. Moyer: Oil Fuels and Burners (McGraw-Hill Book Co., New York). H. P. Tapp: Handbook of Oil Burning (American Oil Burner Association, superseded by OHI). F. H. Faust and G. T. Kaufman (eds.): Handbook of Oil Burning (Oil Heat Institute of America). C. H. Burkh&rdt: Domestic Oil Burners, Installation and Servicing (McGraw-Hill Book Co., New York). A. H. Senner: A Study of the Oil Burner as Applied to Do mestic Heating (U: S. Department of Agriculture Technical ' Bulletin 109). R. J. Bender: Program in domestic oil heating (Mechanical Engineering, October 1942). L. E. Seeley and E. J. Tavanlar: ASHVE Rkssabch Report No. 907--Study of performance characteristics of oil burners and low pressure heating boilers (ASHVE Teaksections, VoL 37, 1931, p. 617). L. E. Seeley and J. H. Powers: ASHVE Research Repost No. 925--A study of intermittent operation of oil burners (ASHVE Transactions, Vol. 38, 1932, p. 317). L. E. Seeley, J. H. Powers, and E. J. Tavanlar: Air supply and its effect on performance of oil burners and heating boilers (ASHVE Transactions, Vol. 39, 1933, p. 75). L. E. Seeley and E. J. Tavanlar: Study of fuel burning rates and power requirements of oil burners in relation to excess air (ASHVE Transactions, Vol. 40,1934, p. 319). D. W. Nelson: Oil burning in residences (ASHVE Trans actions, Vol. 41, 1935,p. 355). . . R. C. Cross and W. R. Lyman: A study of oil-fired heating boilers (Heating and Ventilating, October 1931). Gaseous Fuels (American Gas Association). . Comfort Healing (American Gas Amociation). American Standard Approval Requirements for. Central House Hearing Gas Appliances (American Standards Associa tion, ASA Z21.13). Steam and Hot Water Boilers (Vol. I, Z21.13.1-1956 with ad denda Z21.13.1a-1957). Gravity and Forced Air Central Furnaces (Vol. H, Z21J321956 with addenda Z21.132a-1957). Gravity and Fan Type Floor. Furnaces (Vol. HI, Z21.13.3-1956 with addenda Z2I.133S-1957). ' Gravity and Fan Type Vented Recessed Heaters (Vol. IV, Z21.13.4-1955 with addenda Z21.13.4a-1956 and Z21.13.4b- 1957). American Standard Requirements for Installation of Do mestic Gas Conversion Burners (American Standards Associa tion, Z21S-1948). American- Standard Requirements for Installation of Gas Equipment tn Large Boilers (American Standards Association, Z21S3-1950). American Standard for Installation of Gas Piping and Gas Appliances in Buildings (American Standards Association, Z2130-1954). American Standard Approval Requirements for Gas Unit Heaters (ASA Z2U6-1957). American Standard Approval Requirements for Gas-Fired Duct Furnaces (ASA Z21.34-1955, with addenda Z2134a-1956 and addenda Z21J34b-1957). American Standard Approval Requirements for Gas-Fired Room Heaters (ASA Z21.11-1956, with addenda Z21.11a-1957). A.GA. Industrial Gas School Lectures (American Gas As sociation, 1951). J. D. Keller: Radiant gas burners (A.GA. Sales Conference, American Gas Association, 1949). W. Trinks: Industrial Furnaces (Vol. 1 and 2, John Wiley & Sons, New York, 1944). R. C. Cros: A method for determining fuel burning rates in heating boilers fired by automatic devices (Heating and Venti lating, January 1932).' R. A. Sherman and R. C. Cross: Heat losses and efficiencies of fuels in residential heating (ASHVE Transactions,' VoL 43, 1937, p. 185). CHAPTER 35 HEATING BOILERS, FURNACES, SPACE HEATERS BOH.FR5: Construction, Types, Design Considerations, Rating and Testing Codes, Efficiency, Rating, Selection, Space Limitations, Connections and Fittings, Erection, Operation and Maintenance. FURNACES: Types, Materials and Construction, Ratings, Testing and Rating Codes, Efficiency, Design Considerations, Humidification Equipment. SPACE HEATERS: Types: Solid Fuel, Oil, Gas,- Materials and Construction, Testing and Rating, Design Considerations, Installation N presenting the subject of Boilers, Furnaces, and Space I Heaters this chapter is divided into three parts; the first deling with boilers, the second treating warm air furnaces, and the third covering space, heaters. HEATING BOILERS Steam and hot water boilers for low-pressure heating are built of steel or cast iron in a wide variety of types and razes, many of which are illustrated in the Catalog Data Section. The nationally recognized code governing the construction of low-pressure steel and cast-iron heating boilers is the ASME Boiler Construction Code for Low Pressure Heating Boilers. Some states and municipalities have their own codes which apply locally, but these are usually patterned after the ASME Code. The maximum allowable working pressures are limited by the ASMS Code for Low Pressure Heating Boilers to 15 psi for steam and 160 psi for hot water heating boilers, with a maximum temperature limitation of 250.F. Hot water boilers are generally designed for a working pressure of 30 pei'knd may be supplied for higher working pressures, for either heat ing purposes or for. hot water supply, only when designed, tested, and stamped for the higher pressure. TYPES OF HEATING BOILERS Heating boilers are classified in a number of different ways, such as: ' . -. . 1. According to materials of construction. These are steel and cast iron. Very few nonferrous boilers are made. ' 2. According to the fuels for which the boilers are designed. These are coal, hand-fired or stoker-fired; oil; gas; or wood. Some boilers are designed specifically for one fuel, but many boilers are designed for more than one fuel. 3. According to the specific purpose or application for which the boiler is used, such as space heating or domestic hot water supply. 4. According to the design or construction of the boiler such as sectional, round, fire-tube, water-tube, magazine-feed, Scotch, etc. Cast-Iron Boilers Cast-iron boilers are generally classified as: 1. Square or rectangular boilers with vertical sections and rec tangular grates, commonly known as sectional boilers. 2. Round boilers with horizontal pancake sections and circu lar grates. Cast-iron boilers are usually shipped in sections, and as sembled at the place of installation. However, some small boilers are shipped factory assembled. In the majority of boilers the sections are assembled with push nipples and tie rods but external headers and screw nipples are also used successfully. Many sectional boilers are provided with large push nipples at top to permit the circulation of water be tween adjacent sections, at both the water line and bottom of the boiler, which is necessary to enable the use of ah in direct water heater with the boiler for summer-winter hot water supply. Round and sectional boilers may be increased in size by the addition of sections and corresponding plate work. Small sectional type boilers are available with wet-base construction, wherein the ashpit or combustion chamber sides and bottom are surrounded by extensions of .the water legs of the boiler sections, and thus ho separate base.is required. This type of construction permits the boiler to be set directly on a wood or composition floor without danger of fire. The wet-base nlan provides some additional heating surface. Capacities of cast-iron boilers range generally from capaci ties required for residences up to about 12,000 sq* ft of steam radiation but boilers are made with capacities up to approximately 32,000 sq ft EDR (steam). Steel Boilers . Steel boilers may be of the fire-tube type, in which the gases of combustion pass through the tubes and the boiler water circulates around them, or of the water-tube type, in which the gases circulate around the tubes'and the water passes through them. Either the fire-tube or water-tube type may be designed with integral water-jacketed furnaces, or ar ranged for refractory lined brick or refractory lined jacketed furnaces. Those with integral water-jacketed furnaces are called portable firebox boilers, and are the most commonly used type. They are usually shipped in one piece, ready for piping connections. Refractory furnaces are usually installed, in refractory lined furnace boilers after they are set in place. Capacities of steel boilers range from those required for small residences up to about 50,000 sq ft EDR (steam). Boilers for Special Applications One of these is known as the magazine-feed boiler devel oped for the burning of small sizes of anthracite and coke, and has a large fuel carrying capacity, which results in longer firing periods than would be the case with the standard types burning coal of buckwheat size. Special attention must be given to proper chimney sizes and connections in order to in sure adequate draft. Boilers for hot water supply are classified as direct, if the water heated passes through the boiler, and as indirect, if