Document 3ez4o5ND0No010BDKXyQDgGYJ
To:
FGJ, JliC, DRB
From:
J. C. Ledvina
Date:
July 24, 1990
Subject: VCM NESHAPs Revisions
Attached is a copy of the recently promulgated revisions to the VCM
NESHAPs. These revisions are the result of a lawsuit over certain
provisions of the 9/30/86 changes to the standard.
Vista was a
party to this suit.
The revisions are generally favorable for us although the benefit
is relatively minor.
The definition of "exhaust gas" has been
clarified to exclude leaks from being considered an "exhaust gas".
Vent headers receiving "exhaust gases" are considered subject to
the standard even if they contain less than 10'/. VCM.
Relief valve discharges routed to a control device will not be
considered exceedances of 61.65(a) if the control device reduces
emissions as specified in the standard.
Flares are allowed as
control devices.
Previously, some companies were subjected to
enforcement action for RVDs routed to control devices.
The standard for leaks from pumps has been revised so that a drip
from a double mechanical seal is not a "leak" subject to the
standard. Mechanical seal drips detected during the weekly pump
inspection do not need to be repaired if there is no detectable
(above background) VOC emissions coming from the dripping seal .
VDC determination is done with a portable analyzer.
Leaks from
double mechanical seals found at times other than during the weekly
inspection do not need to be immediately repaired if the frequency
cf leaks is consistent with design considerations or past operating
experience. This language was added to address concerns that even
new seals leak a little. To qualify for this, each plant must have
a written criterion against which they exclude repairs. Since this
is new, you need to write a criterion.
If the leak is still
occurring at the time of the weekly inspection, the drip needs to
be checked with a portable analyzer to see if VOCs are present.
If they are, the leak must be repaired.
The definition of "EDC purification1' has been changed to exclude
in termedia te storage tanks. Crude EDC tanks no longer need to be
routed to a control device.
This isn' t much help for us since
Louisiana hasn t changed LESHAP and we already spent the money to control these tanks.
The definition of "3-hour period" was changed to avoid a situation
where a one hour exceedance of a control device standard can cause three violations.
Since Oklahoma and Mississippi incorporate national standardsVJA'.0001165130
A
reference, these changes are effective immediately in those states, Louisiana needs to modify LESHAPs before the changes are effective for LCVCM.
Give me a call if you have questions or would like to discuss.
y
/jjDG Led v in
cc :
q/\
RAC, HDG, RMS, WLM, DLC, THH
VAB.0001165131