Document 3ewXGxVGp4Mqanyow42VaJ4x
616
Chapter 33
1945 Guide
APPLICATION OF CONTROLLING DEVICES TO A TYPICAL SYSTEM
7 Fig. 1 shows the location of controlling devices for a year 'round air conditioning
system such as shown in Chapter 20, Fig. 3. A control diagram for pneumatic control , equipment is shown in Fig. 2 for convenience in explaining the function and sequence of
operation of the controj in Fig. 1, but obviously the individual-controls may also be of self-contained or electrically operated type provided they obtain the same control of valves and dampers.
The auxiliary controlling devices indicated may all be mounted together on an instru ment board which may also contain a framed copy of the control diagram and the
description of the automatic control cycle. Air gages, identified by suitable inscription plates, may be installed in the branch connections to and from the auxiliary devices on the instrument board to indicate the functioning of the various devices.
A description of the automatic control cycle follows:
When the fan motor is stopped, solenoid air valve E-l, actuated from the fan motor circuit, is de-energized and exhausts its branch to close minimum outdoor damper D-l, reposition three-way air valve V-a to close heating coil valve V-l, and remove main air
from remote bulb indicator dew-point thermostat T-l, thereby closing maximum out door damper D-2 and opening return air damper D-3.
When the fan motor is started, E-l fills its branch, thereby opening minimum outdoor damper D-l, repositions V-a to permit T-3 and T-4 to control`V-1 and supplies main air to T-l to permit same to operate D-2 and D-3.
r During the summer cooling season, manual indexing switch S-l is positioned to fill its
Branch, whereby it supplies main air to dew-point thermostat T-2, positions three-way
air valves V-e and V-f to permit T-3 to control face damper D-4 and by-pass damper D-5,
positions three-way air valve V-b to close heating coil valve V-l, positions three-way air
valveV-c to remove the control of maximum outdoor damper D-2 and return air damper
D-3 from dew-point thermostat T-l and. place these dampers under the control of dew
point thermostat T-2.
When S-l is positioned as noted, remote bulb dew-point thermostat T-2 functions on a rising temperature to first gradually open maximum outdoor damper D-2 while simultaneously closing return air damper D-3 and on a further slight temperature
rise, gradually positions chilled water valve V-2 to pass chilled water to the dehumidifier.
The reverse operating sequence occurs on a falling dew-point temperature. Should the outdoor wet-bulb temperature rise above the desired indoor wet-bulb temperature, positive acting outdoor wet-bulb thermostat T-5, positions three-way air valve V-d to remove dampers D-2 and D-3 from the control of T-2, thereby closing outdoor damper D-2 and opening return air damper D-3.
On a rising return air temperature T-3 functions to open face damper D-4, while simultaneously closing by-pass damper D-5 as required to maintain the desired return air temperature. The reverse operation occurs on a falling return ait temperature.
During all seasons except the summer cooling season, manual switch S-l is positioned
to exhaust its branch, thereby making dew-point thermostat T-2 inoperative and posi tions chilled water valve V-2 for continuous recirculation, positions three-way valve V-b to permit heating coil valve V-l to be operated as required, positions three-way valve
V-c to permit T-l to control D-2 and D-3, positions three-way valve V-e to permit T-3 to operate through low limit discharge thermostat T-4 to control heater valve V-l and
positions three-way valve V-f to open normally closed face damper D-4 and close normally open by-pass damper D-5.
i When switch S-l is positioned as noted, remote bulb dew-point thermostat T-l functions on `a rising temperature to gradually open maximum outdoor damper D-2,: while simultaneously closing return air damper D-3 as required to maintain the desired
dew-point temperature. ' The reverse operation occurs on a falling dew-point tempera
ture. When the outdoor wet-bulb temperature rises above the desired dew-point temperature, the dew-point temperature will rise accordingly until such time as the
system is indexed for summer cooling and chilled water is made available to drop the* dew-point temperature.
Return air thermostat T-3 functions on a rising temperature to pass air through low
limit discharge thermostat T-4 to gradually close heating coil valve V-l. Should the discharge temperature fall below the operating point of T-4, this thermostat will release
air from its branch to gradually open V-l as required to maintain the desired low limit discharge temperature regardless of the operation of T-3.
__________ CHAPTER 34-------------
instruments dan ieit ^yFJetLods
Temperature Measurement, Pressure Measurement, Afeasure* ment of Air Movement, Air Change Measurements, Measuremerit ofRelative Humidity, Dust Determination, Heat Transfer Through Building Materials, Measurement of Heat Exchange for Comfort Conditions, Combustion Analysis, Smoke Density
Measurements, Carbon Monoxide.Measurements
THIS chapter presents a description of many test instruments used for heating, ventilating and air conditioning tests and presents a discussion of their use.
TEMPERATURE MEASUREMENT
Changes in the intensity of heat may be determined by several methods* such as measuring the change in volume of a liquid, the change in internal pressure of a confined gas, the current set up between dissimilar metals joined in a circuit, or the change in resistance of an electrical circuit.
Thermometers
.. .
The most common method used is the change in volume of a liquid such as mercury or alcohol enclosed in glass. Mercurial thermometers may be used for measuring temperatures from --40 F to approximately 1000 F. The lower limit is set by the freezing point of mercury. Since the boiling point of mercury is only about 675 F, the space above the mercury in thermometers designed for higher temperatures must be filled with an inert gas under pressure. Alcohol thermometers may be used for temperatures from --94 F to+248 F.
The more accurate thermometers are individually calibrated and have
divisions etched on the stem. The two most common reference points
are the freezing and boiling points of water. On. the Fahrenheit scale,
which is most commonly used in engineering work, there are 180 divisions
between these points. On the Centigrade scale which is used by.chemists
and physicists, there are 100 divisions in this range'. The temperature
in degrees Fahrenheit equals % of the temperature in degrees .Centi
grade, plus 32.
-
For permanent installations, glass thermometers are often protected by metal jackets and equipped with metal scales. Due to the heat
capacity and heat conductance of the jacket, it is more difficult to obtain the true temperature at a point with these than with the exposed etched
stem type. The latter is usually preferred for test purposes. . Where used to measure.temperatures in a duct, it may be inserted through a cork, or rubber plug. Care must be: taken to locate the bulb at the point where the temperature is desired. and in many cases-several must be used to
get a correct average. .
The probable error in etched stem thermometers is plus or- minus one
scale division, which makes calibration after manufacture necessary for
most test work. Mercury thermometers are usually calibrated for com
plete stem immersion.
When incompletely immersed, a stem correction should be made for the
*For a comprehensive treatment of temperature measurement the reader is referred to Temperature, Its Measurement and Control in Science and Industry, a symposium sponsored by the American Institute of Physics and published by Reinhold Publishing Corp.