Document 3egboMzqe113ovNDRyaQonedn
--/
Monsanto
CjlEMlCALS-PlASTlCS
.... K4__
AN INDIRECT AROCLOR HEATER for UNIT CHEMICAL OPERATIONS
Monsonto Technicol Bulletin No. P-130
September, 1949
Monsanto Chemical Company
St. Louis (4), Missouri
>
1 zz
--, c? TO
Aroclor* 1248 (chlorinated biphenyl) is an ideal nonflammable liquid phase heat-transfer medium for temperatures up to 300C.
This bulletin describes the physical properties of Aroclor 1248 and illustrates the design and operation of heaters that have been used successfully by Monsanto plants during the past seven years. The units described are gas fired and the capacities are in the range of 200,000 to 400,000 B.t.u, per hour.
Other larger commercial installations using Aroclor 1248 have capac ities ranging up to 2,000,000 B.t.u. per hour.
Also small electrically heated stationary and portable units with capac ities around 40,000 B.t.u. per hour,using Aroclor 1248 as the heattransfer medium,are in service.
Several leading manufacturers of heating equipment are in position to build or offer Aroclor heating units to meet specific requirements.
Reg. U. 8. Pal. Office
aaiellng pal
i I*, to our bod knowledge, true and accurde, but all I ilnce the condition, of uie are beyond our control The connection with the tiae of three data Of euggeitione.
0408730
O Z2
Tl O TO
r
9
|
o_ CP c
S' 5'
f
D 8
Iff
t O
TOWOLDMON0034293 WATER_PCB-00018762
Reprinted from INDUSTRIAL AND ENGINEERING CHEMISTRY, Vol. 41, Page 1341, July 1940 Copyright 1949 by the American,Chemical Society and reprinted by permission of the copyright owner
Ail Indirect Aroclor Heater for
Unit Chemical Operations
MF.A11K MCAIUU.E', L. C. GARKETT, AND I'. G. BENIGNUS' Monsanto Chemical Comi>any, Anniston, Ala.
The characteristics of Aroclor 1248 indicate that it is an ideal liquii' phase he.at-cxclinngc medium for
Sprat Flammability. When a tube ruptures in a liquid heattransfer system under high pressure, a spray or mist forms.
temperatures up to 300s C. This article discusses its properties ami illustrates the design and operation of
The possible fire hazard under those conditions requires considera tions cot covered by the foregoing discussions relative to the ma
heaters that have been used successfully l>y Monsanto plants during the past seven years.
terial in the liquid form. In their comprehensive study of flammability of the higher boiling liquids and their mists, Sulli van, Wolfe, and Zisman (3) determined tho spray flammability
N CERTAIN manufacturing processes of the Monsanto limit of numerous materials in accordance with the percentage of
I Chemical Company, it was necessary to employ a noncom oxygen required for combustion. This value was then correlated bustible hoat-lranefor medium at pressures of 80 pounds per with the results of incendiary firing teste of the fluids conducted
square inch or loss ami temperatures up to 300 C. The following at the Naval Proving Ground, Dahlgren, Va, The oxygen re
general properties of a heat-exchange medium were required:
quirement for Aroclor 1248 combustion in the spray flammability
Freedom from fire hazards. Viscosities to permit pumping at room temperatures. Roiling point sufficiently above 300 C. to assure a liquid con dition at all times. Stability against boat, with enough safety' factor to accommo date accidental overheating. Controllable vaporization losses. Freedom from corrosive action against valves, piping, tank jackals, etc., made of cast iron and 6tecls, bronze, and stainless steel. Freedom from toxicity hazard.
Aroclor, chlorinated biphenyl (registered in U. S. Patent
limit studies was found to be 04%. Fluids requiring over 45 to 50% oxygen in the spray test failed to cause a fire in the incendiury test. These results establish the nonflammable and noncom bustible qualities of Aroclor 1248.
VISCOS1TV CONSIDERATIONS
Cold Fj.ow. For most inside installations centrifugal pumps will handle Aroclor at reduced rates without preheating. Experi ence confirms this. Outside installations have been started at 0 C. by heating the pump and feed line until circulation through
Office), was selected. The pertinent physical characteristics
relative to its use as a heat-transfer medium are given in Table I.
Table I. Physical Properties of Aroclor 1248
FREEDOM FROM FIRE HAZARDS
Fi.asii Point. Limitations of this test for the prediction of the fire hazard Of relatively nonvolatile organic fluids have been recognized by the American Society for Testing Materials com mittee (3, 4).
Fire Point is a more significant measurement. The Under writers' Laboratories (10) state that fire tests more truly reflect
Appearance Absolute density, g./ml.
Absolute viscosity, centipoises
Practically colorless mobile liquid
* C. < T.)
1.44 1.41 1.37 1.27 1.17
the (lack of) fire hazard of Aroclor.
SPONTANEOUS IGNITION TEMPERATURE. The COmbllStion-
muBting qualities of Aroclor 1248 are indicated by its high spon
taneous ignition temperature of 704 C. (1299 F.) determined by
Sullivan, Wolfe, and Zisman (P), using the convenient apparatus
described by Sortman, Beatty, and Heron (8).
Under conditions of industrial use the spontaneous ignition
temperature will be determined by factors including the nature
of the hot surface, the amount of liquid impinging on it, the
volume of enclosod space, and the ventilation.
An accidental failure in a heating system demonstrated the nonflammability of Aroclor 1248 and its freedom from tire hazard of fire propagation. An operator's failure to start the circulation of the heat-transfer medium when the gas heater was on resulted in excessive coil temperatures and caused the lower coil to soften and sag into the fire chamber. A weld ruptured and Aroclor 1248 pourca into the red-hot fire chamber in contact with the flame. Denso smoke arose from the heater but there was no external fire. After the gas flame was cut off, the smoking stopped.
Distillation range, A.B.T.M. D-20, 0 C. Flasli point, Cleveland open cup, A.B.T.M,
D B2-4&, 6 C. Fire point, Cleveland open cup, A.S.T.M.
D 92-45 Pour point, A.B.T.M. D*7, 0 C. Coefficient of expansion, ml./ml./* C. (25
65 C.) Specific volume, rnl./g.
Specific beat, cal./g./ C.
Vapor pressure, mm. Hg
0.06)3 0.0698 0.0800
193-100
0.600 0.700 0 728 0.767 0.860 0.WJ 0.KT 0.33# 0.33N
1 Present address, Monsanto Chemical Company, Organic Chemicals Division, Bt. Louie, Mo.
* J`resent address, Monsanto Chemical Company, Phosphate Division, Bl. Louie, Mo.
oboam
TOWOLDMON0034294 WATER_PCB-00018763
1342
INDUSTRIAL AND ENGINEERING CHEMISTRY
Vo!. 41, No. 7
Table II. Stability or Aroclor 1248 Heated tor 30 Hours Temgtnriure,
280 0.079 800 0.189 310 0.100
0.322 830 0.248
Table III.
Stability or Aroclor 1248 Continuously Heated at 280 and 330 C.
Hour*
Mj. of HCI per Ortn of Aroclor
2804 C
330* C.
0 079 0118 0109 0 194
0261
0 248 0.810 0.923 1.141
1.862
Table IV. Gas Analtsis or Aroclor 1248 Heated 4 Hours at 260 C. and 210 Pounds per Square Inch Pressure
Om %
Carbon dioxide Carbon monoxide Oxygen (derived from tir) Metbkne Hydrogen chloride Chlorine Acidity {% by weight HCI)
Prior to exposure After expo*ore
None None 20.2
the heater had beeu effected so that the system could operate normally.
BOILING POINT
Operating experience has shown that the boiling point of Aro clor 1248 (340 C. at 760 mm.) is enough above the 300 C. operating limit to prevent trouble from this cause. At the maxi mum operating temperature the vapor pressure is less than 0.5 atmosphere.
HEAT STABILITY
In order to establish a maximum practical operating tempera
ture, the stability of the material when heated to elevated tem
peratures in the presence of iron was noted. A slow stream of
nitrogen was passed over the hot Aroclor to sweep the decom
position products into a caustic trap. The amount of acidic
material was determined and calculated as hydrochloric acid.
The results given in Table II indicate the stability of Aroclor 1248
when individual samples were heated for 30
hours at the given `emperatures. The decom
position is very low at temperatures up to
j
3oo c.
*
The stability of Aroclor 1248 in contact with
L
iron continuously heated at 280 and 330 C. is
indicated by Table III. These test results indi
cate that Aroclor 1248 in con
tact with iron can be used
satisfactorily at temperatures
up to 800 C.
The National Board of Fire
Underwriters (/(?) reported that
"decomposition of the product
[Aroclor 1248} was not appreci
able at temperatures below
400 C., but became increas
ingly apparent at higher tem
peratures."
Their workers analysed the
decomposition products of Aroclor 1248 heated in the pres ence of hot iron at 459 C. and also heated in an iron cylinder
at 340 C. fitted with an internal gas burner bo that ths
gas flame impinged directly on the surface of the Aroclor.
Analysis of the gases produced under these conditions included
0.8% carbon monoxide, 0.17% oxygen (derived from the air).
0.99% hydrogen chloride, 2.1% combustible gas calculated as
methane, 0.002% chlorine, and no phosgene.
The same workers studied the stability of Aroclor when heated
for 4 hours in an iron pipe at 260 C. under an internal pressure
of 210 pounds per sauare inch', resulting from the introduction of
compressed air. Following this treatment and cooling, the cases
removed from the system were analysed. The acidity of the
Aroclor was determined prior to and after exposure to these con
ditions.
The results given in Table IV reflect an extremely small amount of decompoeition under conditions similar to those selected for the practical use of Aroclor 1248 as a heat-transfer medium.
In actual practice using the type of heating unit described below there has been no evidence of hydrochloric acid effect and do car bon deposits have been noted in the heater, pipes, or valves. The heaters have been operated successfully with combustion gases at approximately 600 C. in contact with the coils.
At one time, a spiral coil type of heater was built and through faulty design a burner tunnel was located 1.5 inches from the 2ineh steel pipe coil. The radiation from the white-hot refractory tunnel and the direct impingement of the flame on the pipe caused
the pipe to glow a dark rea for a space of about 2 inches. This unit was operated almost 3 months before a circulation stoppage occurred. When the line was opened lumps of carbon were found to have come loose and moved forward to lodge in the globe valves. The lumps measured about 1 X 2.5 cm. and one face was formed to fit tho pipe curvature. No hydrochloric acid effect was noted and the system was put back into operation after the burner location was changed.
controllable vaporization losses
The heating systems in which Aroclor 1248 is used are sealed except for the expansion tank, which has a loose cover or a vent pipe. Because this tank is separated from the stream by a sub stantial length of pipe, the temperature in the tank remains low.
In the light of the relatively low vapor pressure values for Aroclor 1248 (7), and as it is unlikely that the expansion tank will ever reach even the 1-mm. state (130 C.), there should not be a measurable loss of Aroclor from the system. Actual experience bears out this contention.
Other Losses. Although Aroclor darkens on use, its charac teristics remain the same and replacement has not boen found necessary after 7 years of continuous use. Accidental leaks or spills constitute the only observed losses.
PLAN AND PART SECTION Ti-E
Figure 1. Heater
0*087J<2
TOWOLDMON0034295 WATER_PCB-00018764
ulj 1949
INDUSTRIAL AND ENGINEERING CHEMISTRY
1343
Table V. Kebiptance or Structural Material to Aroclor
AlumlDum Corner MaiDealuru Nletel
Stiver Tio
K
Metals
Zinc Mild bled Phosphor bronte Red brass Buiinlcis itscl Yellow brass
26* C.
R RR R D RR R
125 C.
R W D D RR Re
RR. Excellent resistance, less tbau 1.0 X 10 "* cm. per day penetration or
0.00011 inch per year. R. Good resistance, penetration between 1,0 X 10** and 10 X 10** cm,
per day or between 0.00014 and 0.0014 inoli per year. D. Doubtful rMiatance, penetration between 10 X 10** cm. per day
and 100 X 10'1 cm. per day or between 0.0014 and 0.0J4 inch per year. e. hollowing letter indicating resistance, signifies material may be
better than indicated If totally immersed, as weight loss is believed to come fiom onjdatlon of part of test strip exposed to sir.
DESIGN AND CONSTRUCTION
Heating System. The heating Bystem required to utilize Aroclor 1248 as the exchange medium includes a heater (Figure 1), cooler, pump, and expansion tank (Figure 2), and control and safety circuits (Figure 3). -
FREEDOM FROM CORROSIVE ACTION
The resistance of various metals (7) at 25 and 125 C. is given in Table V.
Similar studies made at 325 C. (d) indicate that the penetra tion, in inches per year, for mild steel is 0.0028; for yellow brass, 0,00047; for copper, 0.00M5.
Many years of practical operating experience with Aroclor 1248 as a heat-transfer medium have shown that the material is prac tically noncorrosive to valves, piping, tank jackets, etc., made of cast iron and slock, bronze, and stainless sleel.
FREEDOM FROM TOXICITY HAZARD
Aroclor 1248 is a very stable, unreactive liquid. If the material is spilled on the skin, there are no noticeable ill effects; however, it is well to wash the skin with soap and water after contact.
A skin burn resulting from accidental contact with hot Aroclor should be treated in the norma) procedure used for hot oil burns. Aroclor adhering to the burned area need not be removed im mediately unless treatment of the burn demands it; in this case soap and water or repeated washings with a vegetable oil (linseed oil) should be used.
The vapors emitted by Aroclor 1248 healed to elevated tem peratures are Injurious to the liver on prolonged exposure and should uol be breathed. Drinker (5) indicated that 0.5 mg. of Aroclor 1248 per cubic meter of air is the maximum safe amount permissible in workrooms.
In commercial heat-transfer installations, the presumption is that the Aroclor is in u closed system free from leaks. Accord ingly, there should be no opportunity for workers to come in con tact with vapors from the hot heat-transfer medium.
Heater Design. The general requirements of the heater are compactness, ease of construction and service, and avoidance of direct flame impingement on the tubes,
Direct flame impingement is prevented by directing the gas
flame through an enclosed channel with half-thickness fire brick
protecting the tubes above until the high temperature of the
flame is reduced bv heat conducted through these bricks and
radiated to the two bottom coils. The size of the heater is reduced
to a minimum by using only 4.5 inches of insulating fire brick in
the hottest areas and 2 inches of Eagle Vo. 66 insulation on the cooler spots.
Two sizes of unils ate used: One has a maximum capacitv of
200,000 B.t.u. per hour, as shown in Figure 1. The larger has a
range of 200,000 to 400,000 B.t.u.
The small size consists of 90 feet of 1-inch standard weight Sled
pipe made into three coils of six pipes each and connected in
series. The huger size consists of 144 feet of 1.5-inch standard
weight steel pipe arranged in the same fashion. Results of testa on the small-size heater covering temperatures from 150 to
300 C. show temperature rises to 10 to 20 C. in the Aroclor
while circulating at a rate of 15 to 20 gallons per minute. The
outlet gas temperature is consistently within 75 C. of the outlet
Aroclor temperature. It is observed that the bottom two coils ab
sorb the major part of the heat. The small unit indicates 50 to
60% efficiencies for capacities up to 200,000 B.t.u. per hour when a
natural gas of 1000 B.t.u. per cubic foot is burned. A Surface
Combustion Company high pressure inspirator and tunnel burner set is used in this installation.
Over-all hoat-exehangt? coefficients (C) for the furnace are in
the range of 7 to 10 B.t.u per hour per square foot per degree
Fahrenheit. Over-all heat-excliangc coefficients for Aroclor 1248
to water in a double pipe heat-exchanger made from 1.25-inch
pipe with a 2-incli pipe jacket are in tin* 120 to 180 range.
Those figures
calculated from lest results on thPis
installation.
HFATER PIPING Figure 2. Cooler, Pump, and Expansion Tank
Cooler, A very useful adjunct to the system is a double pipe cooler on the outlet of the heater shown in Figure 2. By turning water into the jacket, the Aroclor can be cooled and the temperature of the system lowered. This is helpful when it is necessary bo cool a batch before removing it or when an exothermic reaction starts to get out of control.
Pump. The pump for circulating the Aroclor 1248 may be any one of a number of standard centrifugal units designed for hot liquid service.
0MJ8733
H
TOWOLDMON0034296 WATER_PCB-00018765
1344
INDUSTRIAL AND ENGINEERING CHEMISTRY
Vol. 41, No. 7
Pipe Construction
Casket* Bhut-off vbIvcb Control vnlvea Check valve* Pnlcty valve* ''lief valves (,'n*< And glaas
Table VI. Piping Detail
(Dimension* in tnehe*)
I through 0 '/< through /< 1 throug 8
V* through */ 1 through 2 2'/i through 9 '/* through V* 1 lhroi'gn2 2'/ through 0 'A through V* 1 through 2 2 through 6 1 '/ through 3 '/< *<[<
Schedule 80, A.8.T.M. AM or A106 Schedule 40. A.8.T.M. A53 or A100 Screwed Flanged Bena ia shop and
field where pos sible, Must be cleaned to remove scale Forged steel sorewed. Crane 300ci series Welded fittings. Crane 300c Series 30 (to match valves) Machine bolts A.S.A. B-18.2 with hex agonal nuts (or service below 500 K. Abovo use alloy steel. Crane triplrx A.S.T.M. A90 Crane 252h forged stee Crane 426 high tem perature thread eompon nd Soft iron ring fiat or corrugated Crane 3G00W. acrewed, gate Crane 3615W, flange, gate Crane 33XR. flange, gate Crane 3H40 XR, screwed, globe Crane 3GS3 XR, flange, globe Crane 151 XR, flange, globe Crane 3074 X, screwed Crane 3083 X, flanged Crane IS9 X, flanged Consolidated 1070 DW, screwed Consolidated 1012 W flanged Goetae 340D or
kinetallie D110 T~yyoo 100 PC'PH Marsh 0-100 It*/s<l- inch gage siphon with Crane 22211 bar stock valve, lergueon Series R20 Reflex type
The Dayton Dowd Type C pump is an example of the type required. It should be made of cast steel and have a watercooled stuffing box and water-cooled bearings. The stuffing box should have room for at least six rings of packing and a lantern ring. Durametallic No, D-110 or Garlock No. 234 may be used for packing the pump. An open impeller is desirable, as it will handle the cool, more viscous liquid on starting the system better than will a closed impeller. Enough horsepower for the most viscous conditions is required.
Piping System and Expansion Tank. The detail of the piping sy- iem for Aroclor 124$ used up to temperatures of 300 C. (572 F.) and 100 pounds per square inch pressure is given in Table VI, The valves and specialties given indicate the type re quired. All piping larger than 0.75 inch is flanged orwelded; ex perience has shown that hot Aroclor penetrates screwed joints of the larger sizes. Steel and cast steel are used throughout.
The system requires an expansion tank located at the highest level of the installation. The size of this tank is normally about 2b% of the capacity of the Aroclor system. Connections with valvos, made on either side of the pump, enable the operator to connect a flexible hose and to pump in or out as required,
For operation in locations where the Aroclor temperature may drop to where the attendant viscosities may make pumping im practical in the system as designed, it may be desirable to steamjaoket the Aroclor circulating lines to facilitate rapid startrup. Suitable safety provisions, such as safety pop-off valves, must be installed in the steam jacket system to prevent pressure ruptures which would develop if any condensate remained in a closed sys tem during high temperature operation.
In order to establish operating conditions and to check the operation of the heater itself, it is often desirable to measure the temperatures of the Aroclor in and out of the heater and cooler. Items 9, 10, and 11 (Figure 2) provide for this, They may be dial thermometers or mercury bulb thermometers of any commercially available type recommended for the service.
Table VII. Safety and Control Equipment
High preuure alarm Mercoid DA-31, open circuit on high pressure.
(detect* stoppage Actual settings depend on individual layout
of pipe)
2. Low preuure alarm Mercoid DA-31-3, open circuit on low pressure.
(detect* *toppagc of pump)
Actual settings depend on individual layout
Thermostat (detect* Fenwal 18002. Contact* open on temperature
hence obstruction
ol flow)
Float switch (detest* Mercoid Figure 40. 8.P. switch. Open at lew
leakage from sys level
tem)
Flattie failure system Combustion Control Corp. Fireye FF0. Flame
(cut* off gas if failure control for manual ignition go* burner
pilot flame goes systems
out)
0, Gas valve (cute off General Control Corp. K-10-2. Close* with
in cose preceding current oil
dovicea act)
7. Red light (alarm) Killark VA-I 60 W. or Benjimin 70lJ-V
8. Horn (sounds alarm) Edwards 312
Alarm relay
Type C-U04 1-NO, 1-NC watertight (/)
Stop horn relay
Type C-1104 1-NO, 1-NC, watertight (1)
Stop horn button
l-liA-4 (<)
Tliermomotor well 0-300 C. mercury bulb thermometer
(visual check of
neater perform-
Thermometer well 0 300' C. mercury bulb thermometer
(visual check of
heater perform
ance)
Thermometer well 0-360 C. mercury bulb thermometer
(visual check of
cooler perform
ance)
12. Solenoid valve
General Control K-10-2. Controls Aroclor
temperature to meet demands of system
For automatic temperature control a solenoid valve, item 12, is indicated in a by-pass arrangement with a manually operated needle valve. The nccale valve is adjusted to give almost enough heat to meet the requirements and the actual control ia carried on by the solenoid valve, which opens and closes os directed by a tempcraturc-control instrument connected to the equipment being
One unit was set up with temperature control using a Leeds <fc Northrop Model S all-electric control with droop corrector. Very close control over a wide range of heat demand resulted, when a throttling range adjustment of 4 was used on this control device.
Safety Circuit. Figure 3 shows a safety circuit which auto matically protects the system by closing off the gas supply in the event of faulty operating conditions. Provision is made for shutting off the warning horn while the system is being put back into operation after a safety shutdown.
A detailed list of the safety and control equipment is given in Table VII. The equipment named indicates the type required.
ACKNOWLEDGMENTS
The authors are grateful to A, M. Ellenburg of Monsanto's Re search Laboratory at Anniston, Ala., for furnishing many of the technical data about Aroclor 1248 and for assistance in preparing the manuscript.
LITERATURE CITED
(1) Allen Bradley Co., Milwaukee, Wis., Bull. 700. (2) /hid., Bull. 600. (3) Am. Soc. Testing Materials, Proc. Am. Soc. Tuting Material*,
34,63(1034). . (4) Am. Soc. Testing Materials. "Standards on Petroleum Prod
ucts and Lubricants," 1946. (5) Drinker, C. K.,J.lnd. Hyg. Toxicol., 21, 156 (1930), (6) Monsanto Chemical Co., Anniston, Ala., private communica
tion, April 13, 1944. (7) Monsanto Chemical Co., St. Louie, Mo., Moneanto Tech. Bull.
P-115 (August 1947). (8) Sortman, C., Beatty, H., and Heron, S-, Ind. Eno. Chiu . 33,
357(1941). (9) Sullivan, M. V., Wolfe. J. K.. and Zisman, W. A., Ibid., 39, 1607
(1047). (10) Underwriters' Laboratories, Chicago, HI., "Miscellaneous
Hazards," No. 2498,1934.
Received Auguit 27, 1048. Presented before the Meeting-in-Mlnisture, Alabama Section, Amsbican Cbiwical Socivrr, Deoember 8. 1945.
Pbixtbd in U. 8. A.
050873*
TOWOLDMON0034297 WATER_PCB-00018766
/
Monsanto
Chemicals-Plastics
________ ^./d
e
MONSANTO CHEMICAL COMPANY
ST. LOUIS
AKRON BIRMINGHAM BOSTON . CHARLOTTE CHICAGO
CINCINNATI CLEVELAND . DETROIT HOUSTON LOS ANGELES
NEW YORK PHILADELPHIA SAN FRANCISCO SEATTLE
MONSANTO (CANADA) LTD.
MONSANTO (AUSTRALIA) PTY LTD.
Montreal e Toronto Vancouver
Melbourne
MONSANTO CHEMICALS LTD. London
Representative! in the Principol Cities of the World
POB:KAO-MI>kfr--49
Printed in U.8.A.
0308735
TOWOLDMON0034298 WATER_PCB-00018767