S' American Society of Heating and Ventilating
Engineers Guide, 1934
Chapter 26--Chimneys
draft is employed as an auxiliary to overcome the increased resistances or draft losses. Natural draft systems are used almost exclusively in the smaller size plants where the amount of gases generated is relatively small and it would be expensive to install and operate a mechanical draft system.
The principal advantages of natural draft systems may be summarized as follows: (1) simplicity, (2) reliability, (3) freedom from mechanical parts, (4) low cost of maintenance, (5) relatively long life, (6) relatively low depreciation, and (7) no power required to operate. The principal disadvantages are: (1) lack of flexibility, (2) irregularity, (3) affected by surroundings, and (4) affected by temperature changes.
Mechanical Draft
Artificial draft, or mechanical draft, as it is more commonly called, is a
difference in pressure produced either directly or indirectly by a forced
draft fan, an induced draft fan or a Venturi chimney as the pressure
transformer. The intensity of mechanical draft is dependent for the most
part upon the size of the fan and the speed at which it is operated. The
element of temperature does not enter into the creation of mechanical
draft and therefore its intensity, unlike natural draft, is independent of the
temperature of the gases and the atmosphere. Mechanical draft includes
the induced and Venturi types of draft systems in which the pressure
difference is the result of a suction and also the forced draft system in
which the pressure difference is the result of a blowing. Mechanical draft
systems tend to produce a vacuum or a plenum, according as the system
used in its production creates a pressure difference below, or above,
atmospheric pressure, respectively. A mechanical draft system may be
used either in conjunction with, or as an adjunct to, a natural draft
system.
CHARACTERISTICS OF NATURAL DRAFT CHIMNEYS
In order to analyze the performance of a natural draft chimney, it is advantageous to compare its general operating characteristics with those of a centrifugal pump and also a centrifugally-induced draft fan, there being a close similarity among the three. Figs. 1, 2 and 3 show the general operating characteristics of a typical centrifugally-induced draft fan, a typical centrifugal pump, and a typical natural draft chimney, respectively. The draft-capacity curve of the chimney corresponds to the head-capacity curve of the pump and also to the dynamic-head capacity of the fan; the efficiency curve of the chimney to the efficiency curves of the pump and fan; and the gas horsepower curve of the chimney to the brake horsepower curves of the pump and fan.
When the gases in the chimney are stationary, the draft created is termed the theoretical draft. When the gases are flowing, the theoretical intensity is diminished by the draft loss due to friction, the difference between the two being termed the available draft. The general equation for the available draft intensity of a natural draft chimney with a circular
section is as follows:
D, 2mm0
- fs) 0.00126 W^rc/X D^BoWc
(1)