CHAPTER 23
1957 Guide:
Table 9. Viscosity Effect on Centrifugal Pump Characteristics ,
Kinematic Viscosity
SSU*
Pump Head
0 to 30 50 100
200
1.00 1.00 0.98 0.96
300 400 500 - 600
0.95 0.93 0.92
0.91
700 800 900 1000
0.90
0.89 0.88 0.87
* SSU Saybolt Seconds-- Universal.
p00*
O
Correction Factors
Pump Capacity
1.00 1.00 1.00
0.97 0.96 0.96 0.95
0.94 0.94 0.93 0.92
Pump Efficiency
1.00 0.94 0.88 0.79
0.73 0.68 0.65 0.62
0.59 0.57 0.55 0.53
2. Keep pipe near surface--about 2 in. cover. 3. Use reinforcing steel designed for thermal stress if high structural loads are
expected (such as on highways).
Testing
After installation and before pouring concrete, all piping should be tested to about 100 psi. This pressure should be maintained until all welds and connections have been checked for leaks. If an oil is used as an anti freeze, the test should be performed with air or some gas (only 50 psi re quired with an air test) but not with water. The danger of using water is that the pipe may not be thoroughly dried when the oil is introduced. The water will tend to collect, and when the temperature falls below 32 F the collected water may freeze and cause damage.
Draining
Proper drainage is necessary for both the slab surface and the coil. The slab must be sloped so that the water from the melted snow can run off. Puddles are objectionable on sidewalks or drives. They cause splashing, and they retard heat flow from the embedded pipes: The pipes must be placed so that they may be drained. If the anti freeze becomes corrosive it must be drained. It is not good practice to rely entirely on blowing of air through the system.
Drifting Snow
It is quite likely that some drifting will occur on every system that is adjacent to a wall or vertical surface. The designer should try to antici pate this condition and add extra piping in these areas. If possible, coils should be added in the vertical surface. Another expedient is to carry the drainage to the area expected to be drifted. The drainage will tend to wash away some of the snow.
Design Example
Example 4 Design a snow-melting system for an area of 10,000 sq ft in Pittsburgh Pa. using a free area ratio of 0.5. Assume an air temperature of 10 F and a wind velocity of 10 mph. Use an oil antifreeze solution.
Panel Heating
633
Pipe Size
H l
m 2 2H 3 3K 4 5 6
Table 10. Correction Factors for Pipe Size (f or Laminar Flow, A'K. < 2000)
Inside Diameter
Inches
Feet
Di* Ft4
^ 5.84 X 10~` Di*
(See Figure 20)
0.622 0.824
1.049 1.380 1.610 2.067 2.469 3.068 3.548 4.026 5.047 6.065
0.0518 0.0687 0.0874
0.115 . 0.134 0.172
0.206 0.256 0.296 0.335 0.421 0.505
7.18 X 10- 2.23 X 10~5 5.84 X 10-` 1.75 X 10-< 3.26 X 10-< 8.75 X 10~* 1.81 X 10-
4.30 X 10-J 7.68 X 10-" 1.26 X 10-" 3.14 X 10"s 6.50 X 10-*
'8.13 2.62
1.00 0.334 0.179 0.0667 0.0322
0.0136 0.00760 0.00462 0.00186
0.000898
Solution : From Table 5 select a snowfall rate of 0.08. From Table 6 find the re
quired heat output of top of slab as qa = 168 forRa = 1, and g0 = 64 for ftA =0
Then for flA = 0.5 use g,, = 116 because 0.5(168-64) + 64 = 116. From Equation
12 tm = 0.5g,, + t, = (0.5 X 116) + 33 = 91 F.
.
Assume that back and edge losses are 40 percent. Then the total heat require ment on heat exchanger is
= 10,000 X 1.40 X 116 = 1,624,000 B.tuh. From Equation 25
G= 160tOmCm
1,624,000 160 X 60.5 X 0.431 " 390 gPm
(Interpolating from Table 7, wm = 60.5 and cm = 0.431 for fm = 91 F.)
Since a temperature drop of 20 deg was used, the fluid must enter the slab at 101 F and leave at 81 F.
Assume that the coil circuit of longest equivalent length is 300 ft and has a flow
in U fPJS and tile pipe is l in- IPS- From Table 1, Chapter 26, the I.D. = 1.049
m. - 0.0875 ft and the I. D. section area = 0.864 sq in. = 0.00600 sq ft, hence for
12 gpm, the flow is 0.0268 cu ft per sec and the velocity = 04 ^ .
0.00600
p'
,, Interpolating from Table 7, the kinematic viscosity is 4.92 X 10~* ft* per sec tan accurate interpolation requires the use of ASTM Standard Viscosity chart B.)
tHtence .th. e _Reyno,ld,s num,ber =-V--D-- = -4-.-4--7---X----0-.-0--8-7--5 = 7950 y 4.92 X 10"
0 nm7om.?igV4 of ChaPter 4, using a roughness factor of e = 0.00015, whence e/D = lz> tbe friction factor / is found to be 0.0355. Substituting in Equation 23
hi
=
/X
L D
X
V" -- eg
=
0.0355
x
300 0.0875
X
4.47* 64.3
37.9 ft of fluid = 15.9 psia.
m^L?umpmust deliver 39 8Pm against a 15.9 psia head. The heat exchanger
lure oirnn 1,624,000 Btuh with an inlet temperature of 81 F and an outlet tempera-
nV)injnin* TM ii!./~
(Actually at&nu walilouwwaanucwe DsUhUoUu1ldU bUeV m1 ade for temperature drop in the
between the slab and the heat exchanger.)
in Chnn+C*)aoS*0n
should be designed in accordance with the procedure outlined
pter 21, Hot Water Heating Systems. The amount of expansion should be