Document 3RyQ85zkgzMxQG2gK4jMrwZx
342
CHAPTER 17
1948 Guide
_ The correct fuel burning rate can be determined directly from the several charts for oil or gas burning installations, as these customarily
operate on a strictly intermittent basis. These fuel burning: devices usually introduce the fuel at a single fixed rate during- the on periods and this rate should be sufficient to carry the gross load. In the case of coal
stokers, which are usually capable of variable rates of firing, it is desirable to operate at as low a rate as weather conditions will permit, but the maxi
mum firing rate of the stoker should be sufficient to carry the gross load. This rate may be determined by the same method as used foj oil or gas.
REFERENCES
' 1--Domestic Bumers for Pennsylvania Anthracite (Underfeed Type), National Bureau of Standards, Commercial Standard No. CS48-40).
(U.
S.
Departments '
Commerce,
2--Stoker Manufacturers Association Manual: Industry Standards. Recommended Practices. Tec Information. Published by Stoker Manufacturers Association, 307 N. Michigan Ave., Chicago 1, 111.
meal
3"Code for Determination of Rated Capacities of Anthracite Underfeed Stokers, adopted June-1. 1944, and a Code for Determination of Rated Capacities of Bituminous Underfeed Stokers? adopted May 3, 1944. See Stoker Manufacturers Association Manual.
*--Automatic Mechanical Draft Oil Burners Designed for "Domestic Installations (17. S. Department of Commerce, National Bureau ofStandards, Commercial Standard No. CS76-42). Flue Connected Oil Burning Space Heaters Equipped with Vaporizing Pot Type Burners'(7. S. Department cf Commerce, National Bureau of Standards, Commercial Standard No. CS101-43). Warm-Air FurnacesEquipped with Vaporizing Pot-Type Oil Burners (7.5. Department of Commerce, National Bureau of Standards, Commercial Standard No. CS(E) 104-43).
5"Gas Floor Furnaces, Gravity Circulating Type (7. S. Department of Commerce, National.Bureau of Standards, Commercial Standard No. CS99-42).
BIBLIOGRAPHY
Performance Expectancy of Domestic Underfeed Stokers for Anthracite, by Alien J. Johnson (Transactions,. A.I.M.E., Coal Division, Vol. 119, 1936).
The Relation of the Size of Bituminous Coals to Their Performance on Small Under
feed Stokers--Burning Tests on Four Typical Coals, by R. A. Sherman, E. R. Kaiser and
H. R. Limbacher, Technical Report No. 1, Bituminous Coal Research, Inc. (July, 1937)
Part 11.
'
Oil Fuels and Burners, by James A. Moyer (McGraw-Hill). Handbook of Oil Burning, by Harry F. Tapp.
A Study of the Oil Burner as Applied to Domestic Heating, by Arthur H. Senner (Technical Bulletin 109, XJ. S. Department of Agriculture).
Progress in Domestic Oil Heating, by Rene J. Bender (Mechanical Engineering, October, 1942).
A.S.H.V.E. Research Report No. 907--Study of Performance Characteristics of Oil Burners and Low Pressure Heating Boilers, by L. E. Seeley and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol. 37, 1931, p. 517).
A.S.H.V.E. Research Report No. 925--A Study of Intermittent Operation of Oil Burners, by L. E. Seeley and J. H. Powers (A.S.H.V.E. Transactions, Vol. 38, 1932, p. 317).
-Air Supply and Its Effect on Performance of Oil Burners and Heating Boilers, by L. E. Seeley, J. H. Powers and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol; 39,1933, P- 75).
' Study of Fuel Burning Rates and Power Requirements of Oil Burners in Relation to Excess Air, by L. E. Seeley and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol. 40, 1934, p. 319).
.Oil Burning in Residences, by D. W. Nelson (A.S.H.V.E. Transactions, Vol. 41, 1935, p. 355).
A Study of Oil-Fired Heating Boilers, by R. C. Cross and W. R. Lyman (Heating and Ventilating, October, 1931).
Combustion, American Gas Association.
Comfort Heating, American Gas Association.
Approval Requirements of Central House Heating Gas Appliances, American Standards Association.
A Method for Determining Fuel Burning Rates in Heating Boilers Fired by Auto matic Devices, by R. C. Cross (Heating and Ventilating, January, 1932).
Heat Losses and Efficiencies of Fuels in Residential Heating, by R. A. Sherman and R. C. Cross (A.S.HiV.E. Transactions; Vol. 43, 1937, p. 185).
Chapter 18
HEATING BOILERS AND FURNACES
BOILERS: Construction, Types, Design Considerations, Testing ; and Rating . Codes, Efficiency, Rating, Selection, Space Limitations, Connections and;
Fittings, Erection, Operation and Maintenance. FURNACES: Types, Materials and Construction,* Ratings, Testing and Rating Codes, Efficiency, Design Considerations,.Humidification Equipment
IN presenting the subject of Boilers and Furnaces this chapter is divided into two parts; the first dealing with boilers and the-second
treating warm air furnaces.
.-
HEATING BOILERS
Steam and hot water boilers for low pressure heating are built in a wide variety of types and sizes, many of which are illustrated in the Catalog Data Section. They are made of steel or cast-iron.-
CONSTRUCTION
The only code governing the construction of low-pressure heating steel and cast-iron boilers that has gained recognition on a national basis is the ASME Boiler Construction Code for Low Pressure Heating Boilers. Some states and municipalities have their own codes which apply locally but these are usually patterned after the ASME Code.
The maximum allowable working pressures are limited by the ASME Code to 15 psi' for steam and 30 psi for hot water heating boilers. Hot water boilers may be used for higher -working pressures, for heating purposes, or for hot water supply when designed and tested for the
higher pressure.
TYPES OF HEATING BOILERS
Heating boilers are classified in a number of different, ways, s'uch as:
(a) According to materials of construction. These are steel and cast-iron; Very few-
non-ferrous boilers are made.
i. - :
(4) According to the fuels for which the boilers are designed. These are coal, hand fired or stoker fired; oil; gas; or wood. Some boilers are designed specifically for'one.fuel but many, boilers are designed for more than one fuel.
(c) According to the specific purpose or application for which the boiler is used, such as space heating or domestic hot water supply.
(d) According to the design or construction of the boiler such as, sectional, round,
fire-tube, water-tube, magazine feed, Scotch, etc.
.
Cast-Iron Boilers ,
Cast-iron boilers are generally classified as:
(a) Square or rectangular boilers with vertical sections and rectangular: grates
commonly known as sectional boilers.
;
.
(4) Round boilers with horizontal pancake sections and circular grates.
Cast-iron boilers are usually shipped in sections and assembled at the
place of installation. In the majority of boilers the sections are assembled
with push nipples and tie rods. Many sectional boilers are provided with
' 343
-- -
: