478
CHAPTER 19
1957 Guide
Fig. 2. Recommended Type of High Sidewall Installation on Warm Wai.i.*
* Horizontal vanes, in back or front, to give downward deflections not to exceed from 15 to 22 deg.
used where a branch is taken off a main trunk. Squeeze dampers are used for adjusting the volume of air flow and resistance through a given duct. A damper with positive locking device should be provided for each mam or duct branch. Labels placed on ducts should indicate the room being served. Damper positions should be marked to indicate proper summer and winter settings, dnd to reveal tampering.
Ducts The ducts may be either round or rectangular in cross section. The
centerline radii of elbows should preferably be not less than one and one-
Warm Air Heating Systems
479
half times the pipe diameter for round pipes. The throat radius of a turn in a rectangular duct should be at least one-half the duct dimension in the plane of the turn. Warm air. ducts passing through cold spaces or located in exposed walls, should have 1 to 2. in. of insulation.
Special attention should be given to the problem of noise elimination. The metal duct connection to and from the fumace casing and fan housing should be broken by strips of fire resistant fabric. Motors and mountings must be carefully selected for quiet operation. Electrical conduit and water piping must not be fastened to, nor make contact with the fan housing. Installation of a fan directly under a return air grille is usually avoided.
SIMPLIFIED METHODS OF DESIGN
Simplified methods of design have been developed for several types of forced warm air heating systems. In general, the specific procedure chosen depends upon the type of system and the type of structure in which it is
Fig. 4. Perimeter Loop System with Feeder and Loop Ducts in Concrete Slab
to be used. In most cases, more than one type of system may be used in a specific structure. It is therefore necessary to first choose the system desired and then determine the applicable design procedure.
Perimeter-Loop Systems in Concrete Slab Construction
,, perimeter-loop system,5 shown in Fig. 4, conveys the warm air .^ugh embedded ducts to perimeter diffusers. The air is delivered from He furnace to feeder ducts which extend radially to the loop duel. The air ows through the loop duct to the diffusers. The ducts serve the dual R^Ppse of conveying the warm air and of warming the floor. Although ,e design of the concrete slab is not specifically the concern of the meQanical engineer, it is absolutely necessary that he understand the con-
erations involved lest improper construction be used with consequent onT,? e^ec^ 0Q *he performance of the heating system. For information
slab construction, as well as duct placement, duct insulation, etc., see ^anual 4 of the National Warm Air Healing and Air Conditioning Asso-
ln. A section of typically installed loop duct is shown in Fig. 5. Simplified design procedures5 are contained in Manual 4. One of these, ject to the following limitations: total heat loss 100,000 Btuh, maxi-