Document 3QEO4dnjGm1mONVQw7GLzBjBa
KOPPERS COMPANY, INC. Freyn Department
-zi PLAINTIFFS
Is EXHIBIT BEA-36
Sp^ClFl Rations
pEBRu.
REVISED
*Rr i, i 956
DCMb
BR 3 1956
AlA INPORMATIOM HEREON IS THE PROPERTY OP KOPPERS COMPANY. INC. ENCINEERINO ANO CONSTRUCTION DIVISION AND IS CONPIDEMTIAL AND MUST HOT SC MADE PUSUC OR COPIED UNLESS AUTHORIZED RY IT AND IS SUUECT TO RETURN UPON DEMAND.
IR lOM-r-H
TABLE OF CONTENTS
SUBJECT
Contract No. 2036
SECTION
NO. OF PAGES
SCOPE OF WORK EXCAVATION AND FOUNDATIONS BUILDINGS MATERIAL HANDLING AND MISCELLANEOUS
EQUIPMENT COKE PREPARATION SINTERING MACHINE AND AUXILIARIES SINTER MACHINE FAN AND DUST COLLECTING
SYSTEM SINTER COOLER AND AUXILIARIES SINTER COOLER FANS AND BREECHING PIPING ELECTRICAL INSTRUMENTS MISCELLANEOUS PURCHASER'S WORK ALTERATIONS TO EXISTING PLANT
A B C
D .E
F
G H J. K L M N P R
2 2 8
13 2
6
5 3 1 3 31
2
3 3 3
ALL INFORMATION HEREON IS THE FROFERTT OF KOFFERS COMFANT. INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT BE MADE FUBUC OR COFIED UNLESS AUTHORIZED *T IT AND IS SUBJECT TO RETURN UFON OEMAND.
*11 1SM.1.B7
201 GENERAL:
. 1 These specifications define the work to be performed in engineering, fur nishing and constructing the No. 2 sintering plant, rated at 5290 net tons per day, at the Weirton, West Virginia plant of Weirton Steel Company.
. 2 The existing ore handling, crushing, and screening facilities of No. 1 sintering plant will be altered to supply ore for both sintering plants. The ore handling system for the sintering plant connects with the ore conveying system along the ore yard being furnished under Koppers Contract 2037.
. 3 The plant is based on screening and sintering the fines from Labrador, Hanna, and Weir ores, current blast furnace flue dust and filter cake. The minus 3/8 in. fines to be screened from the ores are assumed to be as follows:
Uncrushed Condition
Crushed to 2 in.
Labrador Hanna . Weir
70% 60% 40%
75% 70% 60%
.4 Equipment, other than conveyors, including the sintering machine, sinter ing fans, sinter cooler, drum pug mill, balling drum, screens, and auxi liaries will be based on a sintering rate of 3. 0 net tons product sinter per sq. ft. sintering machine grate area per day.
. 5 The conveyors and other material handling equipment will be based on a sintering rate of 3. 5 net tons product sinter per sq. ft. sintering machine grate area per day and upon 22 hour -per -day operation.
.6 202
It is understood that the Weirton Steel Company is referred to herein as the- PURCHASER; and Koppers Company, Inc., Freyn Department, as the CONTRACTOR.
SCOPE OF WORK:
. 1 CONTRACTOR will provide the engineering, equipment, materials, labor and supervision to perform the work and construct the sintering plant as defined by these specifications.
A-l
ALL INFORMATION HEREON IS THE PROPERTY OF KOPPERS COMPANY* INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT RE MADE PU1LIC OR COPIED UNLESS AUTHORIZED RY IT AND IS SURJECT TO RETURN UPON DEMAND.
K-ta 10M*7M
SECTION C BUILDINGS
ALL INFORMATION HEREON IS THE PROPERTY OF KOPPCRS COMPANY.' INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AMO MUST HOT ftt MADE PUSUC OR COPIED UNLESS AUTHORIZED IT IT AND IS SUtJCCT TO RETURN UPON OEMANO.
409
ELECTRICAL CONTROL HOUSE - SOUTH END: (continued)
. 7 One (1) unit heater will be provided.
. 8 The air filter equipment is described elsewhere in this specification.
410 .1
CAR HAUL HOUSE;
CONTRACTOR will design, furnish and erect one (1) car haul house sub stantially as shown on drawing 2036-3L165.
. 2 This building will be of structural steel construction, approximately 13 ft. 0 in. wide by 18 ft. 6 in. long center to center of columns. The building will be one (1) story and will house the car haul engine and controls.
. 3 The walls will be insulated steel panels. One (1) service door and lift beam will be provided. Two (2) personnel access doors will be provided.
. 4 Roof will be Koppers 4 ply built-up roofing applied over a steel deck.
. 5 Ground floor will be concrete paved.
411 .1
DUST COLLECTOR SUPPORT STRUCTURE:
CONTRACTOR will design, furnish and install one (1) uncovered heavy steel structure to support the dust collectors, suction system breeching, ducts, and electric control house. This structure will be approximately 66 ft. 10 in. long by 34 ft. 0 in. wide center to center of columns, and will be framed integrally with the main sintering building.
. 2 Structure will be substantially as shown on drawings 2036-7L45, rev. 2, and 2036-7L46, rev. 2, and will consist chiefly of heavy structural columns and beams. Stairways and walkways will be provided for access to dust collector panels.
. 3 Structure will provide support for the electric control room suspended over the roadway. Roadway clearance of 14 ft. 0 in. in elevation will be maintained.
C-8
ALL INFORMATION HEREON IS THE FROFERTY OF XOFFERS COMFANY. INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT SE MADE FUSUC OR COFIED UNLESS AUTHORIZED ST IT AND IS SUSJECT TO RETURN UFON DEMAND.
!
SECTION G SINTER MACHINE FAN AND DUST COLLECTING SYSTEM
AU. INFORMATION HEREON IS THE PROPERTY OF HOPPERS COMPANY. INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT IE MADE PUBLIC OR COPIED UNLESS AUTHORIZED SY IT AND IS SUBJECT TO RETURN UPON DEMAND.
801
COLLECTING MAINS:
. 1 CONTRACTOR will furnish and install two (2) unlined, tapered, rectangulai dust collecting mains to conduct waste gas from the sintering machine. The mains will be substantially as shown on drawings 2036-7L43, -7L44, and -7L46, and will be welded construction, fabricated from 5/16 in. steel plate. They will be designed for a maximum gas velocity of 2000 ft. per minute. Stiffeners will be provided to enable plates to withstand the ex ternal pressure. Mains will be supported with provision for expansion by cast steel rockers on steel beams.
. 2 One (1) expansion joint for each main will be provided at connection of main to breeching to dust collectors. Expansion joint will be for rectangu lar duct and will be a special bellows type made of stainless steel.
. 3 Continuous hoppers will be provided in the bottom of the mains. The hop pers will be fabricated from 5/16 in. steel plate, unlined and suitably stiffened. The hoppers will terminate in cast iron spouts that will dis charge from counterweighted flapper valves onto dust belts located under each main.
.4 .5
802
Access doors will be provided in each main at approximately 21 ft. 0 in. centers.
Twenty-eight (28) downcomer pipe assemblies will be provided. Each assembly will consist of pipe and elbow, butterfly damper and operating mechanism, and expansion joint. Pipe and elbow will be fabricated of 1/2 in. steel plate with flanges. Butterfly valves will be of cast iron and complete with control mechanisms operable from the building operating floor. Expansion joints will be special double bellows, stainless steel, with 42 in. O. D. steel pipe sleeves. Asbestos gaskets will be furnished as required.
DUST COLLECTORS:
. 1 CONTRACTOR will furnish.and install eight (8) American Ore Reclama tion centrifugal type dust collectors, rated at 64,000 c. f. m. each. Col lectors will be of welded steel construction, having a cylindrical shell 10 ft. 7 in. inside diameter and conical top and bottom sections. The bottom conical section will be provided with a 6 in. flange connection. The collectors will have side tangential inlets 2 ft. 5 in. wide by 6 ft. 8 in. long, and circular top outlets 4 ft. 11-1/2 in. diameter. The top outlet connection will extend inside the cylindrical shell.
G-l
AU. INFORMATION HEREON 13 THE PROPERTY OP (COPPERS COMPANY. INC. ENCINCERINO AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT DC MADE PUBLIC OR COPIED UNLESS AUTHORIZED SY IT AND IS SUBJECT TO RETURN UPON DEMAND.
s*ta
*
802
DUST COLLECTORS: (continued)
.2 The collector shell, top and bottom sections, will be fabricated of 5/16 in. steel plate. Shelf angles will be provided on the inside of collector for support of 4-1/2 in. thick lining. Lining will consist of carbo-frax brick at severe wear points and duro-brick in remainder of collector. Lining will be furnished and installed by CONTRACTOR. The tangential inlets will be provided with 3/8 in. abrasion-resistant steel wearing plates.
.3 Eight (8) Western Precipitation, type Rl, or equal, 6 in. dust valves will be provided. Valves will be equipped with 1/6 hp. drives and 12 in. dutchman to provide larger dust holding capacity. One (1) dust valve will be provided for each dust collector.
803
BREECHING:
. 1 CONTRACTOR will design, furnish and install breeching duct from collec tor mains to dust collectors. This breeching will be substantially as shown on drawings 2036-7L45 and -7L46.
. 2 Breeching will be fabricated from 5/16 in. steel plate suitably stiffened. A 2-1/2 in. thick carbo-frax brick lining will be provided in vertical riser where gas stream changes direction. Lining will be held in place by suit able steel retainers. A guiding vane, fabricated of steel plate, will be provided in the elbow at the connection to the collector main. Take-off outlets will be provided for connection to each dust collector. Outlets will be designed for 3600 FPM gas velocity.
. 3 The following expansion joints will be provided for each duct. One (1) rectangular, neoprene asbestos, insulated seal expansion joint will be pro vided in the vertical riser. Four (4) rectangular, neoprene asbestos, in sulated seal, expansion joints will be provided for connection to dust collectors.
.4 CONTRACTOR will design, furnish and install two (2) breeching ducts from the dust collectors to the main sintering fans. Each duct will con nect to four (4) dust collectors and to one (1) fan. Breeching will be sub stantially as shown on drawings 2036-7L45 and -7L46.
. 5 Breeching will be fabricated from 5/16 in. steel plate suitably stiffened, and will be designed for a gas velocity of 3000 FPM.
. 6 Three (3) slip sleeve packed expansion joints will be provided in each duct.
G-2
AU. INFORMATION HEREON IS THE PROPERTY OF HOPPERS COMPANY. INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT SE MADE PUBLIC OR COPIED UNLESS AUTHORIZED BY IT AND IS SUBJECT TO RETURN UPON DEMAND.
I-U I0M-7-RS
1101
GENERAL:
.1 1102
CONTRACTOR will furnish and inetallair, gas, steam, water, and indus trial drain piping for the sintering plant as hereafter described and generally as shown on flow diagrams 2036-7A16, -7A17, -7A18, and -7A53. All piping will be equipped with valves, fittings, drains, traps, and supports in accordance with CONTRACTOR'S standard specifications for the particular service.
COMPRESSED AIR PIPING:
. 1 CONTRACTOR will furnish the following above ground compressed air piping:
. 2 One (1) 3 in. line from PURCHASER'S supply to a point at the north end of
the sinter machine building with connection to the new compressor.
. 3 One (1)2 in. line from north end of sinter machine building to loading out bins for operation of quadrant gates.
.4 One (1) 2 in. line to run the length of the sinter machine building along the west wall at the ground floor.
. 5 One (1) 2 in. line to run the length of the sintering machine building along the east wall at the operating floor.
.6 One (1) 2 in. line to run the length of the sintering machine building along
the east wall at the machinery floor.
. 7 One (1)2 in. line to run the length of the sinter cooler to the mixer build ing.
.8 Connections will be provided from these headers to points requiring ser
vice.
1103
COKE OVEN GAS:
. 1 CONTRACTOR will furnish and install a coke oven gas line from PUR CHASER'S supply main to the ignition furnace, with shut-off valve and pressure indicator.
1104
STEAM PIPING:
. 1 CONTRACTOR will furnish and install the following above ground steam piping to supply unit heaters throughout the plant:
K-l
ALU INFORMATION HEREON 15 THE PROPERTY OP POPPERS COMPANY. INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT SC MADC PUSLIC OR COPIED UNLESS AUTHORIZED ST IT AND IS SUSJCCT TO RETURN UPON DEMAND.
t-t* IOM-7-R*
2
1104
STEAM PIPING: (continued)
. 2 One (1)4 in. steam header from PURCHASER'S source of supply to a pressure reducing station.
. 3 Steam headers from the pressure reducing station with connections to the areas requiring unit heaters.
.4 Connections from the headers to unit heaters in the north control center, south control center, substation, control panel area, and mixer building.
. 5 Two (2) return line headers, each of which will discharge to a flash tank.
1105
FRESH WATER PIPING;
, 1 CONTRACTOR will furnish and install the following above ground fresh water piping for the sintering plant:
. 2 One (1) 2 in. supply line from PURCHASER'S source of supply.
.3 3/4 in. connections from the 2 in. supply line to drinking water fountains. One (1) fountain will be located at the north control center, one (1) at the operating floor, one (1) at the machinery floor and one (1) at the ground floor.
1106
SERVICE WATER PIPING:
. 1 CONTRACTOR will furnish and install the following service water piping for the sintering plant. All piping will be above ground unless otherwise specified.
. 2 One (1) 10 in. underground supply line from PURCHASER'S source of.-supply to a strainer located near the fan motor house.
. 3 One (1) header varying in size from 10 in. to 1-1/2 in. to supply various items of equipment throughout the sintering plant. Header will extend from the strainer to the mixer building.
.4 One (1) 6 in. line from header to rectifier in existing substation.
. 5 Connections from header to water-cooled bearings at sintering fans.
. 6 Connection from header to air compressor.
. 7 Connection from header to ignition furnace.
K-2
ALL INFORMATION HEREON IS THE FROPERTT OF XOFFERS COMPANY. INC. ENGINEERING ANO CONSTRUCTION DIVISION AND IS CONFIDENTIAL AHD MUST HOT RE MADE PUBLIC OR COPIED UNLESS AUTHORIZED BY IT ANO IS SUBJECT TO RETURN UPON DEMAND*
1106
SERVICE WATER PIPING: (continued)
. 8 Connection from header to rod mill bearings.
. 9 Connections from header to outlets at the sinter screens.
. 10 Connections from header to emergency* cooler sprays.
. 11 Connection from header to the primary pug mill.
. 12 Connection from header to the secondaryballing drum.
1107 .1
INDUSTRIAL. DRAIN SYSTEM:
CONTRACTOR will furnish and install an industrial drain system for the sintering plant consisting of the following:
.2 Drains from fan bearings, air compressor, flash tank, 'ignition furnace, rod mill bearings, air duct sumps, and skip hoist pit to covered floor trenches in the sintering machine building.
. 3 Drains from water tank overflow and rectifier to a sump. Floor trenches will also drain to this sump..
, 4 An overhead drain line from this sump to existing manhole No. 2.
1108
RELOCATION OF PIPING:
. 1 CONTRACTOR will dismantle, move or alter existing water, steam, gas . or sewer lines which interfere with CONTRACTOR'S operations in the construction of the new sinter plant.
K-3
ALL INFORMATION HEREON IS THE PROPERTY OF KOPPERS COMPANY. INC. ZMGINEERINS AND CONSTRUCTION OIVISION AND IS CONFIDENTIAL AND MUST NOT RE MADE PUBLIC OR COPIED UNLESS AUTHORIZED BY IT AND IS SUBJECT TO RETURN UPON OEMANO.
(IS
1201
GENERAL;
. 1 CONTRACTOR will furnish and install all electrical equipment, power, light, interlock and grounding wiring for the plant as covered in this specification. Electrical equipment throughout the plant will be We sting house as far as possible.
. 2 CONTRACTOR will obtain 6900 volt, 3 phase, 60 cycle power from dead end tower on top of existing sinter building.
CONTRACTOR will provide new dead end tower on top of sinter building for existing transmission lines as required due to building changes. Six (6) 650 MCM cables are presently dead ended on this tower. PURCHASER shall relocate overhead line, connecting them to the new tower, and shall provide all new insulators and connections. CONTRACTOR will provide new feeders to present and new sinter plant switchgear from this tower. Two (2) 4 in. steel conduits, each containing three (3) 750 MCM 1/0 cables shall be run to each sinter plant H. V. switchgear. Tower strength shall be based on 4000 lb. pull on each conductor. Conductors shall be installed to 2000 lb. pull with strain cage, leaving 2000 lb. for ice and wind load. Calculate breakage strength assuming one-half the total conductors on the tower breaking at once.
CONTRACTOR will inform PURCHASER if enough gain is made in length of cable by relocating tower to offset increase in height, or if additional length is required on cable. PURCHASER shall send CONTRACTOR draw ings of present tower on building and previous tower, and relative loca tions to enable CONTRACTOR to make these calculations.
.3 ' CONTRACTOR will connect new tie breaker to present 6. 9 KV switchgear on second floor of substation. CONTRACTOR will extend bus and provide conduit box for connection on end of present switchgear. Present switchgear is G. E. Co. , ordered on PBG 194341. Two (2) 750 MCM cables shall be provided for tie.
1202
SUBSTATION;
. 1 CONTRACTOR will furnish new substation for the plant. This substation will consist of the existing building of three (3) floors located between column Nos. 6A and 12 on the west side of present sinter machine building,
' The second floor of this building contains sinter plant No. 1 substation.
. 2 Substation will be separated from main building by a concrete block wall without doors or windows except present door on second floor, which will
L-l
AU. INFORMATION HEREON IS THE PROPERTY OP HOPPERS COMPANY. INC. ENGINEERING AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT SE MADE PUBLIC OR COPIED UNLESS AUTHORIZED BY IT AND IS SUBJECT TO RETURN UPON DEMAND.
K*tS
1218
SINTER MACHINE, SINTER COOLER AND SINTER BREAKER CON TROLLERS: (continued)
b) Line and accelerating contactors.
c) Will be wired for remote mounted start-stop pushbutton and test pushbutton and one indicating light to be energized with motor at rest and one energized with motor running.
d) Sinter machine, sinter breaker and sinter cooler will be interlocked so that sinter machine cannot run unless sinter breaker and cooler are running.
e) Sinter machine will be stopped by a photo-electric cell unit, if.the pallets are not in correct position for engagement by the sprocket drive.
. 6 Sinter machine roll feeder shall have controller similar to above, and shal be controlled by a magamp regulator to keep its speed the same as the sin ter machine. Tachometer generator mounted on sinter machine drive shall give controlling impulse to magamp.
. 7 Sinter cooler shall be provided with a drag generator and magnetic brake to prevent pallets from separating at discharge end.
1219
WIRING:
. 1 CONTRACTOR will furnish and install all power, light, interlock and grounding wiring required for the operation of the plant covered in this specification.
. 2 Wiring will in every respect comply with the National Board of Fire Under writers National Electric Code, 1956 edition, and any other local or PUR CHASER'S rules governing this type and location.
1220
CONSTRUCTION AND INSTALLATION:
The following PURCHASER'S rules shall govern the work. (Adapted from Weirton Steel Company "Standard Electrical Installation Specifications". Parts not applic able to this contract have been omitted).
. 1 Material and Workmanship:
a) All materials used will be the best of their representative classes unless specifically noted to the contrary.
L-22
ALL INFORMATION HEREON IS THE FROFERTT OF KOFFERS COMFANY. INC. ENfilMEERINO AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL AND MUST NOT RE MADE FUILIC OR COFIEO UNLESS AUTHORIZED T IT AND IS SUSJECT TO RETURN UFOK DEMAND.
1220 CONSTRUCTION AND INSTALLATION: (continued)
3. 10 to 100, conduits inclusive - add 20% of total conduit as spares.
4. All spare conduits will be 1- 1/2 in. in size.
h) Control cable through six (6) conductor will be installed in 1 in. con duit. Control cable of eight (8) conductor and above will be placed in 1-1/2 in. conduit.
. 3 Conduit Fittings, Pull Boxes, and Cable Trays:
a) Where necessary, approved threaded conduit fittings with steel covers will be used.
b) In damp places, or places where the conduit run is likely to be sub jected to steam or vapor, cast iron covers and gaskets will be used.
c) Pull boxes will be used where necessary to insure the safe pulling of conductors.
d) A maximum of 200 ft. between boxes is permitted for wire #2 AWG and larger.
e) Pull boxes will be of at least 10 gauge steel bent and welded and pro vided with gasketed screw covers of the same thickness.
. 4 Wire and Cable;
a) Cable feeders to individual motors and generators will have a capacity of not less than 125% of the full load nameplate current of the motor or generator.
b) Control cable will be used for motor and generator power where it will safely carry the full load current of the motor or generator.
c) Six hundred (600) volt insulated power cables size No. 1/0 and smalla will be type TW, minimum, 3/64 wall insulation, size limited to Nos. 12 - 10 - 8 - 6 - 4 - 2 and 1/0.
d) Six hundred (600) volt insulated cable Bize 3/0 and larger will be varnished cambric, size limited to 3/0 - 300 M, 500 M, 750 M, and 1000 M.
L-24
Ai.L INFORMATION HEREON IS THE PROPERTY OF KOPPERS COMPANY* INC. EHQIMEZRJMO AND CONSTRUCTION DIVISION AND IS CONFIDENTIAL. AND MUST NOT BE MADE PUBLIC OR COPIED UNLESS AUTHORIZED BY IT AND IS SUBJECT TO RETURN UPON DEMAND.
I*ts
1220
CONSTRUCTION AND INSTALLATION: (continued)
e) The above wire will be used on installations where the total tempera ture of the conductor will not exceed 60C. On installations where the total temperature of the conductor will exceed 60C. , AVC insu lated wire or other insulation suitable to the particular temperature conditions will be used.
f) All 6900 volt cable circuits will be single conductor, varnished cam bric, double braid, with 13/16 varnished cambric wall thickness, 9000 volt insulation and 300, 000 circular mill will be the minimum size.
g) All 6900 volt circuits will be run in conduit.
h) All circuits 600 volts and less may be run in conduit, cable trays and in roof trusses where conditions permit. I
i) Control cables will consist of multi-conductor, NEMA standard, color coded conductors. Each conductor will be 19 strands of No. 25 tinned wire, Anaconda Densheath with plastic filler, or equivalent, and will be limited to the following number of conductors: 2, 3, 4, 6, 8, 10, 12 and 14 conductors only.
j) Ammeter shunt leads will consist of two conductor, 19 strands of No. 22 tinned conductor.
k) Spare control wires will be installed on the following basis:
1. 1 to 3, inclusive - no spare wire.
2. 4 to 7, inclusive - add one spare wire.
3. 8 to 12, inclusive - add two spare wires.
4. Where more than 14 conductors are required, two (2) cables oi half the number plus spares will be used.
. 5 Cable Bushings and Tags;
a) At the switchboard end, the CONTRACTOR will furnish and install the insulated bushings for power and control conduits.
b) For power conduit 1-1/4 in. and larger, the CONTRACTOR will sup ply and install an insulated washer drilled with the correct size holes for the individual power conductors.
L-25
ALL INFORMATION HENEON IS THE FNOFENTT OF KOFFERS COMFANT. INC. ENGINEERING AND CONSTRUCTION DIVISION AHD IS CONFIDENTIAL AND MUST NOT IE MADE FUSLIC OR COFIEO UNLESS AUTHORIZED ST IT AND IS SURJECT TO RETURN UFON DEMAND.
(IS IOM-7-F
we*,**,* *
rI1 '
s C
tc * c c c