Document 3Q9aV3b2j7Q5jM7KMdo5rjnYJ

American Society of Heating and Ventilating Engineers Guide, 1929 for any radiator with steam or water at temperatures other than 215 deg. fahr. and with room temperatures other than 70 deg. fahr., when the emission for 215 deg. fahr. and 70 deg. fahr. are known, These factors have been based on the method outlined in the Report of the Advisory Committee on Radiation, Journal of the American Society of Heating Table 1.* Heat Emitted by Direct Radiation Steam Temperature 215 deg. fahr. Room Temperature 70 deg. fahr. Type Standard " u " " " Hospital Wall U W indow No. of Columns Height Inches i 38 i 32 i 26 i 23 i 20 2 45 2 38 2 32 2 ` 26 2 23 2 20 3 45 3 38 3 32 3 26 3 22 3 18 4 45 4 38 4 32 4 26 4 22 4 18 2 45 2 38 2 32 . 2 26 2 23 2 20 _ _ 29 22 17 ._... 20 Itf- 13 Rated Surface PER 8ection Sq. Ft. 3.00 2.50 2.00 1.66 1.50 5.00 4.00 3.33 2.66 2.33 2.00 6.00 5.00 4.50 3.75 3.00 2.25 10.00 8.00 6.50 5.00 4.00 3.00 5.00 4.00 3.33 2.66 2.33 2.00 9.00 7.00 5.00 5.00 3.75 3.00 B.t.u. per 8a Ft. per Hour Intermediate Section. End Section 243 250 257 266 263 217 225 233 240 242 246 206 211 215 219 226 236 191 198 207 216 222 233 230 240 250 256 261 265 289 293 310 211 375 380 385 394 395 378 396 400 413 415 411 374 380 370 366 380 390 309 321 333 346 358 375 393 407 418 423 428 430 316 319 331 342 226 361 Condensed from Research Laboratory Standard Data--American Society of Heating and Ventilating Engineers--Result of Cooperative Work with U. S. Bureau of Mines Experiment Station, Pittsburgh, Pa. Copyright 1921. and Ventilating Engineers, March 1927, making use of the relation that the heat outputs vary as the 1.3 power of the temperature ranges. In order to convert the heat emission from steam radiation with steam at 215 deg. fahr. and room temperature at 70 deg. fahr. to, heat emission from hot-water radiation with mean water temperature at 170 deg. fahr. and room temperature at 70 deg. fahr., the heat emission from the steam radiation should be multiplied.by the factor, 0.617. 68 Chapter II--Radiators and Heaters Table 2. Heat Emission of Direct Pipe Coil Radiation for Steam Steam Temperature 215 deg. fahr. Room Temperature 70 deg. fahr. WALL COILS--Coils Placed Vertical--Pipes Horizontal B.t.u. per Lineal Feet of Coil per Hour (Not Lineal Feet of Pipe) Size op Coil Twelve.............................................. ......... r 132 252 440 567 651 732 812 IK' 155 312 545 702 796 907 1005 \yf 185 348 616 793 907 1020 1135 WALL COILS--Coils Placed Vertical--Pipes Vertical Emission varies in inverse ratio of the height of the coil Use 100 B.t.u. per lineal feet of pipe as an average for 1}4 in. coil, 10 ft. high. CEILING COILS--Coils Placed Horizontally--Pipes Horizontal Emission is equal to that of a single row coil Allowance must be made, however, if the coil is at the ceiling in a higher temperature. Jn this case use: 126 B.t.u. per lineal feet of pipe for 1 in. coils. 146 B.t.u. per lineal feet of pipe for 11/\ in. coils. 175 B.t.u. per lineal feet of pipe for 1J4 in. coils. Table 2 has been developed by a method of deduction from the avail able data on such experimental work on pipe coils as has been recorded, ^ and does not represent definite results of tests as in Table 1. The values ` are, therefore, approximately only, but can be used with assurance that they are more accurate than those obtained by the usual method for calculating pipe coil surface. EXTENDED SURFACE HEATERS Extended surface heaters in general, consist of one or more steam carrying tubes or spaces to which the fins or sheets of extended surface are attached. The heating elements in themselves are not generally com plete and require a duct, stack or chimney in order to give satisfactory . results. There are heating elements, however, of this type which are complete within themselves, and most other such units are now assembled in accompanying casings to form a complete unit, known either as a heat cabinet, a concealed heater or some appropriate name. When installed between the walls of a building a sheet metal stack js used between the inlet and the outlet. When the heater is installed in the room it is equipped with a closely fitting box or cabinet which takes place of the stack and gives the necessary chimney effect. The heating elements are mac|e of brass, copper, aluminum or other highly conductive non-ferrous metal, generally with extended surfaces ranging from about in. to 4x8 in. in size and from 0.002' to 69