SCOPE ENGINEERING OESIGN MEMORANDUM
PROJECT: RG-244 FACILITY PHASE II _________ EXPANSION - 935-1128
BY: 0. Holt DATE: August 15, 1973
DESIGN MEMO NO. 8
Revision
0
Subject: Environmental Protection
INTRODUCTION
It Is Corporation policy that all new facilities be designed to meet or exceed pol lution control regulations and standards, for the protection not only of the environment, but also of the health and comfort of our employees.
GENERAL
The toxicology and Industrial hygiene aspects of chrysotile asbestos are well covered in literature. The maximum permissible concentration, as stated by the California Industrial Safety Emergency Regulations, that an employee may be exposed to shall not exceed a weighted 8-hour average concentration of airborne asbestos fibers of more than 5 fibers, longer than 5 micro meters, per cubic centimeter of air as determined by the membrane filter method using phase contrast Illumination and 400 x to 450 x magnification. This 8-hour weighted concentration of airborne asbestos fibers is scheduled to be reduced to 2 fibers per cubic centimeter on July 1, 1978. Tests conducted for the Corporation by Mellon Institute have Indicated that RG-244 is no worse than chrysotile when Inhaled, so It is assumed that the same MPC would apply. Airborne dust concentrations throughout the plant are monitored by plant personnel under the direction of the UCC Industrial Hygiene Department.
Due to the fine particle size, RG-244 product is readily dispersed in air. However, possibly because of the static charge on the fibers or some other reason, It tends to clump together In feathery agglomerates which settle readily and are easily collectible In bag filters. Dust counts In the RG-244 packaging area have consistently been below the MPC, even though abundant visible airborne asbestos was present. The grinding and packaging area Is, and should continue to be, a Fesplrator area, because of bags occasionally bursting when being filled.
am,
The off-gas from the Roto-Louvre dryer should be cleaned In a high efficiency cyclone followed by a bag dust collector before release to the atmosphere. Stack sampling ports should be provided near the top of the stack for periodic checking of the solids
emission. Stack height should be at least 5 feet above the roof peak of the mill
building, or equipment in close proximity.
A Mlkro-Pulsalre bag collector is installed in the grinding and packaging circuit.
Even though no dust is visible In the discharge, It should be tested occasionally
to build up a case history. All possible precautions should be taken to prevent
RG-244 from spills, broken bags or reblendlng from becoming airborne In the Salinas
Val ley zephyrs.
X414277