CHAPTER 40
1955
Type
Table 3. Classification of Motors
Speed Chabacteb-
Full Voltage
Starting Torque
Starting Current
HP Range
Constant Speed Drives
Application '
See Footnotes ' (o) to (e) '?
Squirrel-cage general Constant purpose Design A
Normal 1-2.5 High 6-8
times'
times
All
Squirrel-cage Design Constant
Normal 1-2.5 Normal 5-6 Medium
times'
times
Small
Squirrel-cage Design Constant
High %-2.5 Normal 5-6. Medium-
times'
times
Small
I Squirrel-cage Design Constant
Low 1.25
Low 4 times Medium Large
>*
Constant or High 1-2.5 Low 1-3
All
variable
tunes
times
(with secondary control)
Synchronous high speed
Synchronous low speed
Exactly con- Normal
stant
0.75-1.75
times
Exactly con- Low 0.3-0.4
stant
times
Normal 5-7 times
Low 3-4 times
Medium Large
Medium Large
(a) Fans and (c) centrifugal ' >.
pumps and v; centrifugal compressors
(a) Fans and centri fugal pumps
and centrifu gal compressors
(6) Reciprocating . pumps
(e) and compress* started loaded
Fans, centrifugal pumps and compressors
(a) Hoists (b) reciprocating
pumps and
compressors (c) and frequent (e) or hard start (a) Fans and cento-
fugal pumps and centrifugal compressors
(a) Reciprocating compressors
starting un
loaded
Two value capacitor Constant
High
Normal
Small
(b) Pumps and com*
Permanent split
Constant
d capacitor
o Capacitor start
Constant
Ja Repulsion Induction Constant
5
Split phase ca
Constant
and adjustable
Low Moderate High
Normal
Normal Normal Normal
Normal
Fractional (o) Fans, Blowers
Small Frac- (a) Fans and pump
Medium Small
Fractional
(a) Fans (b) pumps and
compressors
(a) Fans (6) pumps and
compressors
(d) fans--direct
Adjustable Speed Drives
Squirrel-cage high slip. Transformer adjustment
Squirrel-cage sepa rate winding or
regrouped poles Wound rotor
Variable
Constant multispeed
Variable
Normal
Normal
Normal or high
Normal or low
High
Low
(with second ary control)
Repulsion
Variable
High
Capacitor low torque
tapped winding Capacitor low torque
transformer ad justment Split phase re grouped poles
Variable two speed
Variable
Constant
Low Low
Normal
Normal Normal Low
Normal
Medium Small
(a) Fans
All () Fans () pumps and (e) compressors
All () Fans () centrifugal pumps and compressors
Low and Fractional
Fractional
() Fans, centrifo**1
pumps () compressors (d) Fans, drect
Fractional (d) Fans
Fractional (d) Fans
. Drives having medium or low starting torque and inertia (fFR*) such as fans and centrifugal P
or reciprocating pumps and compressors started unloaded.
. ,.j
. Drives having high starting torques, such as reciprocating pumps and compressors started loao.
c. Similar to (o) except where frequent or hard starting (large WR*) requires a higher starting
erating torque.
d. Fans direct connected.
e. Stoker an
/. Torque depends on hp rating and speed. See NBMA Standard MGl-4.10 on Motors and Genera
Motors and Motor Controls
917
time is prolonged by high WR* and high load torques. In general, driven machines starting more than 4 to 6 times per hour may require special motors and control.
ALTERNATING CURRENT MOTORS
Alternating current motors are divided into two main classifications: polyphase and single phase (see Table 3), according to the type of power supply. They are further subdivided by type of motor winding.
When polyphase power is available it is usually found more economical to apply polyphase motors in preference to single phase motors. A typical 5 hp, 1200 rpm capacitor start-induction run single phase motor, for in stance, will cost approximately twice as much as the corresponding three phase Design B squirrel-cage motor. In addition, the polyphase motor has the advantage of higher efficiency.
Table 4. Locked-Rotob Current of Three-Phase, 60-Cycle Motors at 220 Volts*' b
HP
Design B, C, AND D
Design F
HP
Design B,C and D
Design F
Amperes
Amperes
Amperes
Amperes
1 or less
m 2 3 5
24* 35 45 60 90
30 435 270 40 580 360 50 725 450 60 870 540 75 1085 676
7)4 10 15
-------------------------------------
120 150 220 290 365
100 1450 900
125
1815
1125
150
2170
1350
200
2900
1800
,Tke locked-rotor current of three-phase, 60-cycle, constant-epeed, induction motors, measured with
raiea voltage and frequency impressed and with rotor locked, shall not exceed the tabulated values. c ^^x&ed-rotor current at other voltages shall be inversely proportional to the voltage, ror ] hp or less the value is given per hp.
x-uiyjmase motors
The three types of polyphase motors are: sguirrel-cage induction motors, wound rotor induction motors, and synchronous motors.
Squirrel-cage motors are specific by NEMA standards providing a variety of speed and torque characteristics. Design A motors provide normal starting torque at starting current in excess of Design B motors,
l ff suitable for constant speed application to equipment such as fans ypi "lowers. Design B motors provide normal starting torque with
starting current values shown in Table 4, which are acceptable by any power companies for full voltage starting. They are used for the same ^>pe of application as Design A. Design C motors provide high starting
star?1 a s^ar^n8 current same as Design B, and are used on compressors ha nT Tthout UIJoaders, and on reciprocating pumps. Design D motors e v? "S*1 slip* and are used with flywheels for widely pulsating loads on Viipment such as reciprocating compressors and pumps where other j, ors wuld draw high peak currents. Design F Motors have low start-
can CU/ren^ an^ low torques. They are used on power systems of limited tora^ Careful application must be made since the low breakdown
condv Prov`^es nty limited safety margin for overload or low voltage itions. A drop in voltage, for instance, could cause the motor to stall.
mot'f * and 2 illustrate the characteristics of squirrel-cage motors. The -_^operates under load from near synchronous speed at light load to
efer to Glossary at end of chapter.