Document 3NJgqGnGGRMM7ooEX35X2O6OD

916 CHAPTER 40 1955 Type Table 3. Classification of Motors Speed Chabacteb- Full Voltage Starting Torque Starting Current HP Range Constant Speed Drives Application ' See Footnotes ' (o) to (e) '? Squirrel-cage general Constant purpose Design A Normal 1-2.5 High 6-8 times' times All Squirrel-cage Design Constant Normal 1-2.5 Normal 5-6 Medium times' times Small Squirrel-cage Design Constant High %-2.5 Normal 5-6. Medium- times' times Small I Squirrel-cage Design Constant Low 1.25 Low 4 times Medium Large >* Constant or High 1-2.5 Low 1-3 All variable tunes times (with secondary control) Synchronous high speed Synchronous low speed Exactly con- Normal stant 0.75-1.75 times Exactly con- Low 0.3-0.4 stant times Normal 5-7 times Low 3-4 times Medium Large Medium Large (a) Fans and (c) centrifugal ' >. pumps and v; centrifugal compressors (a) Fans and centri fugal pumps and centrifu gal compressors (6) Reciprocating . pumps (e) and compress* started loaded Fans, centrifugal pumps and compressors (a) Hoists (b) reciprocating pumps and compressors (c) and frequent (e) or hard start (a) Fans and cento- fugal pumps and centrifugal compressors (a) Reciprocating compressors starting un loaded Two value capacitor Constant High Normal Small (b) Pumps and com* Permanent split Constant d capacitor o Capacitor start Constant Ja Repulsion Induction Constant 5 Split phase ca Constant and adjustable Low Moderate High Normal Normal Normal Normal Normal Fractional (o) Fans, Blowers Small Frac- (a) Fans and pump Medium Small Fractional (a) Fans (b) pumps and compressors (a) Fans (6) pumps and compressors (d) fans--direct Adjustable Speed Drives Squirrel-cage high slip. Transformer adjustment Squirrel-cage sepa rate winding or regrouped poles Wound rotor Variable Constant multispeed Variable Normal Normal Normal or high Normal or low High Low (with second ary control) Repulsion Variable High Capacitor low torque tapped winding Capacitor low torque transformer ad justment Split phase re grouped poles Variable two speed Variable Constant Low Low Normal Normal Normal Low Normal Medium Small (a) Fans All () Fans () pumps and (e) compressors All () Fans () centrifugal pumps and compressors Low and Fractional Fractional () Fans, centrifo**1 pumps () compressors (d) Fans, drect Fractional (d) Fans Fractional (d) Fans . Drives having medium or low starting torque and inertia (fFR*) such as fans and centrifugal P or reciprocating pumps and compressors started unloaded. . ,.j . Drives having high starting torques, such as reciprocating pumps and compressors started loao. c. Similar to (o) except where frequent or hard starting (large WR*) requires a higher starting erating torque. d. Fans direct connected. e. Stoker an /. Torque depends on hp rating and speed. See NBMA Standard MGl-4.10 on Motors and Genera Motors and Motor Controls 917 time is prolonged by high WR* and high load torques. In general, driven machines starting more than 4 to 6 times per hour may require special motors and control. ALTERNATING CURRENT MOTORS Alternating current motors are divided into two main classifications: polyphase and single phase (see Table 3), according to the type of power supply. They are further subdivided by type of motor winding. When polyphase power is available it is usually found more economical to apply polyphase motors in preference to single phase motors. A typical 5 hp, 1200 rpm capacitor start-induction run single phase motor, for in stance, will cost approximately twice as much as the corresponding three phase Design B squirrel-cage motor. In addition, the polyphase motor has the advantage of higher efficiency. Table 4. Locked-Rotob Current of Three-Phase, 60-Cycle Motors at 220 Volts*' b HP Design B, C, AND D Design F HP Design B,C and D Design F Amperes Amperes Amperes Amperes 1 or less m 2 3 5 24* 35 45 60 90 30 435 270 40 580 360 50 725 450 60 870 540 75 1085 676 7)4 10 15 ------------------------------------- 120 150 220 290 365 100 1450 900 125 1815 1125 150 2170 1350 200 2900 1800 ,Tke locked-rotor current of three-phase, 60-cycle, constant-epeed, induction motors, measured with raiea voltage and frequency impressed and with rotor locked, shall not exceed the tabulated values. c ^^x&ed-rotor current at other voltages shall be inversely proportional to the voltage, ror ] hp or less the value is given per hp. x-uiyjmase motors The three types of polyphase motors are: sguirrel-cage induction motors, wound rotor induction motors, and synchronous motors. Squirrel-cage motors are specific by NEMA standards providing a variety of speed and torque characteristics. Design A motors provide normal starting torque at starting current in excess of Design B motors, l ff suitable for constant speed application to equipment such as fans ypi "lowers. Design B motors provide normal starting torque with starting current values shown in Table 4, which are acceptable by any power companies for full voltage starting. They are used for the same ^>pe of application as Design A. Design C motors provide high starting star?1 a s^ar^n8 current same as Design B, and are used on compressors ha nT Tthout UIJoaders, and on reciprocating pumps. Design D motors e v? "S*1 slip* and are used with flywheels for widely pulsating loads on Viipment such as reciprocating compressors and pumps where other j, ors wuld draw high peak currents. Design F Motors have low start- can CU/ren^ an^ low torques. They are used on power systems of limited tora^ Careful application must be made since the low breakdown condv Prov`^es nty limited safety margin for overload or low voltage itions. A drop in voltage, for instance, could cause the motor to stall. mot'f * and 2 illustrate the characteristics of squirrel-cage motors. The -_^operates under load from near synchronous speed at light load to efer to Glossary at end of chapter.