INTERIM BULLETIN SP-1TC
"Nothing containod harem is to be construed as a recommendation to usa any product in conflict with any patent. MONSANTO MAKES NO WARRANTIES AS TO THE FITNESS OR MERCHANTABILITY OF ANY PRODUCT REFERRED TO, no guarantee ot satisfactory results from reliance upon contained information or recommendations, and disclaims all liability tor any resulting loss or damage."
Monsanto
0481529
TOWOLDMON0033209 WATER_PCB-00017678
THERMINOL CONVERSION BUI.LETIN
INTRODUCTION Thermlnol Fl6 fire-resistant heat transfer fluids have long provided Bafe, dependable, economical performance for hundreds of users in dozens of appli cations. The presence of poly-chlorinated biphenyl (PCB) in the Thermlnol FR formulation provided fire-resistance, giving Therminol FR an added margin of safety which was especially desirable in hazardous applications.
Most recently, PCB has been identified as a potential hazard to the environ ment. Monsanto has accordingly elected to discontinue the manufacture and sale of Thermlnol FR fluids for heat transfer applications. This bulletin is to inform you about two alternative products sold by Monsanto which do not contain PCB, namely Therminol 55 and Thermlnol 66.
These products offer most of the excellent heat transfer characteristics of Thermlnol FR fluids, and even a few additional advantages, such as a lower specific gravity for improved pumpabllity requiring less horsepower. We would point out that Therminol 55 and 66 are not fire-resistant to the extent the Thermlnol FR fluids were, and due consideration must be given this fact in con verting to these newer Therminol fluids. You may vi6h to consult with your insurers on any conversion from Therminol FR.
.Conversion from a Therminol FR fluid to a Therminol 55 or 66 fluid will be a relatively simple, low-cost procedure in the majority of cases. Incorporation of proper fire protection equipment will be the only consideration of major consequence in most cases. But even this modification becomes academic, for
0461530
|
TOWOLDMON0033210 WATER_PCB-00017679
with the discontinuation of Therminol FR fluids, fire protection equipment becomes necessary for any and all low pressure heat transfer media available today, since the Therminol FR fluids were unique in their fire-resistance.
Should questions arise with respect to the conversion from Therminol FR fluid, Monsanto's Specialty Products Group Invites you to call upon Its staff or qualified systems engineers for consultation at any time. Call...
(314) 694-2514 and ask for a Monsanto Heat Transfer Specialist.
Therminol 55 and 66 and Your Heat Transfer System Table I shows the typical physical, chemical and thermal properties of Therminol FIR-1, Therminol 55 and Therminol 66. As you will note, Therminol 55 and 66 are quite similar except with regard to AIT, Fire Point and density. The substantially lower density of Therminol 55 and 66 means that pumps used in a Therminol FR-1 system should be adequate for a Therminol 55 and 66 system. In most cases, pumping rates will be increased with a resultant saving in horsepower requirements.
Therminol 55 and 66 have outstanding heat transfer properties, so heating and cooling performance will not be sacrificed in a change from Therminol FR-1. The specific heat and thermal conductivity of Therminol 55 and 66 are shown, along with other physical properties, in Tables 2, 3 and 4, and in Figures 1, 2 and 3. The lower pour points of Therminol 55 and 66 will provide easier cold startup of the system.
Generally speaking, then, a well designed system currently operating on Therminol FR-1 can be converted to Therminol 55 and 66 with few, if any, basic
TOWOLDMON0033211 WATER_PCB-00017680
TABLE I
TYPICAL PHYSICAL, CHEMICAL & THERMAL PROPERTIES
Therminol FR 1
Therminol 66
Therminol 55
Composition
Maximum Bilk. Temperature Rating (F.)
Recommended Use Range (F.) Pour Point (F.)
Pounds/Callon (75F.) Flash Point (F.)
Fire Point (F.)
AIT (F.) '
Bolling Range (F.)
Molecular Height Expansion Coefficient cc/cc/F.
Polychlorinated Biphenyl
600F
Modi fled Terphenyl
650F.
Alkylated Aromatic
600F.
45 - 57 5F.
2 11.55
350 None to Bolling 1206F. 620 - 680 265 0.00031
' 45 - 635F. 20 - 575F
-15 8.35
-40 7.4
355 374 - 392
355 410
705 644 - 745 240 0.00039
670 635 - 734 340 0.00047
3048IS38
TOWOLDMON0033212 WATER_PCB-00017681
Table 2. THERMIHOL FB-1 VARIATION OP PROPERTIES WITH TEMPERATURE
Temp e ratu re
Density
Specific Heat
Thermal Conductivity
Viscosity
'P c lb/ Kg/m3 BTU/lb Kcal/Kg BTU/ft Kcal/m Cp
gal
*P C hr P hr C
50 10 11.68 1399.6 0.272
100 38 11.46 1372.7- 0.282
150 66 11.22 1343.7 0.291
200 93 10.99 1316.7 0.3047
250 121 10.76 1289.1 0.3151
300 149 10.53 1261.3 0.3255
350 177 10.30 1233.5 0.3359
400 204 10.07 1205.8 0.3464
450 232 9.83 1178.0 0.3568
SCO 260 9.60 1150.2 0.3672
550 288 9.37 1122.5 0.3776
600 316 9.14 1094.7 0.3880
650 343 700 371
8.91 1066.9 .0.3985 8.68 1039.3 0.4089
0.272 0.282 0.291 0.3047 0.3151 0.3255 0.3359 0.3464 0.3568 0.3672 0.3776 0.3880 0.3985 0.4089
0.0609 0.0907 0.0605c 0.0902 0.0602j O.0896 0.0597* 0.0889 0.05927 0.0882 O.O507' 0.0874 0.0581s 0.0866 0.0576c 0.05697 0.0848 0.0563< O.O838 0.0556c 0.0827 0.0548- 0.0817 0.0540S 0.0805 0.0532! 0.0793
in
0CO d
308 23.2 6.6 3.4 2.3 1.4 1.0 0.8 0.6 0.5 0.4 0.4 0.3 0.3
Cs
220 16.9 4.9 2.6 1.8 1.1 0.8 0.7 0.5 0.4 0.4 0.3 0.3 0.3
0`.61533
vapor Pressure
mmHg
Kg/cm2
absolute
---- -
--
- -- '
'- '
-
10 0.0135
27 0.0357 65 0.0884 143 0.1945
291
0.3958
550
0.7480
l8.8psla 1.3218
31.9psla 2.2429
TOWOLDMON0033213 WATER_PCB-00017682
Table 3IHEHMIMOL 66 VABIATIOK OF PHOPEHTIES WITH TEMPERATURE
Tempe rature
Dans.tty
Specific Heat
Theraal Conductivity
A' c lb/ Ke/o3 ETU/lb Kcal/TvS
gal
"P C
0 8.67 "io4o 0.320 0.320
50 10 8.51 1020. 0.350 ICO 38 8.34 1000 0.380
0.350 0.3S0
150 66 8.14 200 93 7.91
975 950
0.405 0.430
0.405 0.430
250 121 300 149
7.77 7.59
930' 0.455 910 0.480
0.455 0.480
350 177 HOO >04
7.33 7.17
885 0.505 860 0.530
0.505 0.530
!i50 ?32
jOO 150
7.04 6.75
840 810
0.555 0.580
0.555 0.580
550 288
>00 . 315 550 343 '00 371
6.62
6.42
6.24 -6.09
793 0.605
770 0.630
750 0.655
_DP... 0.680
0.605
O.630
0.655 0.680
C<i81534
ETU/ft Ecal/m hr F hr C 0.C720 0.1072 0.0711 0.105S 0.0703 0.1046 0.0695 0.1034 0.0687 0.1022 0.0678 0.1008 0.0670 0.0997 0.0662 0.0985
O.C653 0.0972 0.0545 0.0959 0.0637 0.0948 0.0528 0.0935 0.0520 0.0923 0.0613 0.0912 0.0605 0.0900
Viscosity
Cp Cs
62000 50000
255
250
28.0
28.0
9.75
10.0
4.18
4.40
2.42
2.60
1.55
1.70
1.06
1.20
0.77
0.90
0.58
0.69
0.45 0.36
0.55 0.45
0.34
0.44
0.27 0.20
0.36 0.28
vapor Pressure
nunHS absolute
Kg/cm2
0.1
2.0
20.0 50.0 100.0 200.0 350.0 760.0 1000
0.003
0.C27 0.068 0.135 0.272 0.476 1.034 1.360
TOWOLDMON0033214 WATER_PCB-00017683
Table 4 THEBMINOL 55 VARIATIONS OF PROPERTIES WITH TEMPERATURE
Temp e ratu re
Density
Specific Heat
Thermal Conductivity
Viscosity
*P *c lb/ Kg/m3 BTU/lb Kcal/Kg
gal
P C
0 -18 100 38 200 93 300 149 400 204 500 260 600 316
.7.62 7.31 7.00 6.69 6.39 6.07 5.76
915 878 -
0.420 0.472
840
0.522
803
0.572
766 7on
0.520 0.670
691
0.718
0.420 0.472 0.522 0.572 0.620 0.570 0.718
BTU/ft Kcal/ra hr P hr C
0.0313 0.1210 0.0764 0.1167 0.0753 0.1121 0.0724 0.1077 0.0592 0.1030 0.CS51 0.0384 0.0630 0.0938
CP Cs
1472
1610
25.4
30.1
4.20
5.0
I.69
2.10
0.904
1.18
0.583 0.415
0.80 0.60
Vapor Pre33ure
mmKs absolute
Kg/cm
0.5 3.0
10 40 . 100 250
'. 0.001
0.004 0.014 0.054 0.136 0.330
aV
CD
UJ
TOWOLDMON0033215 WATER_PCB-00017684
0481536
C E N T IS T C X E S
-
V
Figure 1 THERM INOL FH-1 - PHYSICAL PROPERTIES
TOWOLDMON0033216 WATER_PCB-00017685
T
.
'
S
O
Figure 2 THEHMDJOL 66 - PHTSICAL PHOPEBTIES
O vC
SPECIFIC HEAT -- 3TU/L3
TOWOLDMON0033217 WATER_PCB-00017686
Figure 3 IHEHKINOL 55 - PHYSICAL PROPERTIES
o
SPECIFIC KEA? -- 3TU/L
WATER_PCB-00017687
changes in design - and without sacrifice to heat transfer efficiency. With the similarity of the heat transfer properties of the three fluids thus established, let us turn to the Important differences between Therminol FR-1 and Therminol 55 and 66: namely, fire resistance and oxldation-resistance.
Fire-Rcsistance
As stated In the Introduction to this bulletin, the Therminol FR fluids were
unique in their inherent fire resistance. No other commonly used heat
transfer medium could be so classified. Even so, the Therminol FR fluids
could be made to bum under certain conditions, as indicated by their AIT of
about 1200F.
.
It is important to realize that Therminol 55 and 66 are less fire-resistant than Therminol FR-1, and to modify the heat transfer system accordingly, it is equally important to understand that Therminol 55 and 66 are not volatile, highly flammable fluids but rather combustible as defined by FM and NFPA (NFPA No. 321).
Protecting the System There are two major fire protection considerations in changing to Therminol 55 or 66 -- system leakage and possible tube rupture (in the heater). The former is actually part of the larger subject of good system maintenance, and should be considered regardless of the heat transfer medium employed. A tight, wellmaintained system is usually a good, safe system! Following are some suggestions to prevent leakage when you convert to Therminol 55 or 66.
First, if your system has rotary mechanical seals, you should provide a spray shield and a drip pan with a drain to a collection sump. Canned and seal-less pumps offer excellent protection against leakage.
TOWOLDMON0033219 WATER_PCB-00017688
The best way to prevent piping leakage la to veld all connections. Where you must have access, use raised-face flanges with appropriate gasketing and high-temperature bolting. Control of piping leaks Is especially Important, since fluid-soaked insulation poses a more serious hazard than the leaking fluid, Itself.
Organic compounds such as Therminol 55 and 66 exhibit a slow oxidation reaction with the air trapped Inside the voids of the insulating material when system temperatures reach about 500F. Saturated insulation offers a large fuel surface in the face of poor heat dissipation conditions, and this, along with possible catalysis from the insulating material (magnesia, silicate-bonded asbestos or calcium silicate) can cause a temperature build-up in the mass. This temperature build-up can result in ignition of the fluid when the space between the piping and the saturated insulation is exposed to air (i.e., should the insulation be broken for repair, etc.)
This phenomenon is not fully understood, but appears to occur less with closed cell insulation than with the insulating materials mentioned above. Closed cell materials, then, are preferred, especially where leakage is a possibility despite all precautions.
The principle problem areas are near instrument connections, valve packing glands, flanges, and where cracks develop in relatively impermeable insulation cement adjacent to oil soaked Insulation.
To obviate this problem, eliminate any source of leakage promptly. Replace leaky gaskets, oil soaked insulation, and re-pack valve stems. Cover insulation where leaks might occur with a hydraulic setting, oil-resistant cement. In stall valves, where possible, with the stems in a horizontal position so that
-5- 0461539
TOWOLDMON0033220 WATER_PCB-00017689
leaks will drip away from the Insulation, And again, use closed cell Insulating materials on suspect piping areas.
Tube Kupture In Fired Heaters Generally speaking, where fire protection is concerned, it is best to consult your insurance underwriter for guidance and councel. Likewise, you will want to discuss your fire safety equipment requirements with qualified suppliers of fire protection equipment. Selection and sizing of fire protection equipment is important to safeguard the installation.
A commonly used method of preventing fire in the event of tube rupture in fired heaters is piping steam of CO2 as a snuffer into the combustion chamber of the heater. Usually a properly-sized line with a remote manual valve for activation la the preferred arrangement. This snuffer system could be automated by the use of an exhaust stack temperature switch. This switch would then energize a solenoid valve and alarm upon excessive temperature rise, automatically flood ing the chamber with a fire extinguishing agent.
In practice the temperature switch is often set about 100P. over the normal ex haust temperature to prevent nulance shutdowns. Where steam snuffer systems arc used, It is a good idea to employ a steam trap to avoid slugging the com bustion chamber with water when the system activates, or is activated manually.
You can obtain a basic guideline in the selection of CO2 protection equipment (again, it is best to consult your Insurance underwriter) from the National Fire Protection Assn., 60 Batterymarch Street, Boston, Mass. 02110 AC 617 482-8755. NFPA Bulletin No. 12 dated 1968 should be requested. This bulletin should be helpful in determining the amount of CO2 and the concentration of CO2 needed to extinguish a fire based on your specific application.
6- 0461540
TOWOLDMON0033221 WATER_PCB-00017690
C02 cylinders are available from Cardox Division of Cheraetron, Chicago, 111, as veil as other suppliers, Some standard sizes are 50, 75, 100 and 150 pound cylinders. Prices usually include drawings of the units, fully charged cylinders, flexible piping connectors, spray nozzle, pressure svltch, alarm and automatic control, provided C02 release signal is supplied by customer device. Piping, wiring, and Installation labor to be provided by the customer. Recharging of spent cylinders is available at an additional cost from a variety of "Fire 6 Safety Equipment Suppliers" listed in the Yellow Pages of your phone book.
Selection of all equipment and Installation recommendations should be obtained from qualified suppliers; however, it is Important to insure that sufficient COg is available to prevent re-ignition while the heater is cooling.
The llalon Fire Suppression System is a possible alternative to a C02 arrange ment because It can be used in closed spaces with personnel in the area. One supplier of HaIon systems is the Cardox Division of Chemetron Corporation, Chicago, 111. 60611.
Again, we strongly recommend that the advice of fire protection companies be solicited in either case to insure proper equipment selection and installation.
If steam is to be used rather than the other alternatives suggested above, please refer to the NFPA Volume I, Section 86A (1970-1971) to obtain the volume of steam required.
Oxidation-Resistance
.
With a Therminol 55 or 66 system, some provision should be made to prevent
oxidation caused by air contact at fluid temperatures exceeding 200F. This
vos not the case with Therminol FR fluids, but must be observed for Therminol 55
0<t815<il
|
-7-
TOWOLDMON0033222 WATER_PCB-00017691
and Thermlnol 66. Oxidation can result in sludge formation, eventually leading to carbonaceous deposits on heat transfer surfaces and at mechanical seal faces.
Oxidation of fluid can develop by air contact In an open, vented expansion tank. Therefore we recommend that the expansion tank be blanketed ulth an Inert gas (sucb as nitrogen) as shown In Figure 4. If this is not possible, air contact can be minimized by a cold seal arrangement as shown in Figure 5. An Inert gas pressure of one to two psi Is adequate, as Thermlnol 55 and 66 do not require pressurization to maintain liquid phase.
.You can design the cold seal arrangement quite simply by piping the expansion tank vent to a second tank where the vent line projects subsurface and can be flooded with additional Thermlnol 55 or 66 to minimize sir ingress to the ex pansion tank vapor space.
In converting from Thermlnol FR to Thermlnol 55 or 66, it is important to remember that many lhcrminol FR systems were designed with a hot bleed line into the expansion tank to eliminate moisture accumulation. Moisture accumula tion In the presence of hydrogen chloride gas released during the decomposition of the FR fluids could contribute to acidity problems. This is not the case with Thermlnol 55 or 66; therefore, this bleed line should not be used during normal operation of a Thermlnol 55 or 66 system. This line should be valved off during operation but It could be retained as a convenient means of venting the system during initial startup after conversion.
Further protection against a hot expansion tank occurence would be the re moval of any expansion tank Insulation and feeder line insulation.
-8-
CH8154f
TOWOLDMON0033223 WATER_PCB-00017692
Figure 4. .SUGGESTED INERT GAS ARRANGEMENT
FOR EXPANSION TANK
0481543
TOWOLDMON0033224 WATER_PCB-00017693
Figure 5. SUGGESTED COLD SEAL ARRANGEMENT
FOR EXPANSION TANKS
0*8154*
TOWOLDMON0033225 WATER_PCB-00017694
Carbonaceous deposits can also occur at the pump seal face due to leakage at high temperatures. The use of a seal flush system or a double mechanical seal is helpful in preventing excessive seal wear.
Convertina to Therminol 55 and 66 With fire-protection and oxidation-resistance procedures well in mind, let us turn to the matter of preparing the Therminol FR system for Therminol 55 or 66.
Accumulation of debris over the years in the system could cause serious pro blems, especially to mechanical seals, rotary joints, etc. All heat transfer systems should be cleaned from time to time as a part of normal preventive maintenance. Since a fluid change is necessary at this time, it would seem practical to use the downtime to thoroughly clean the system prior to startup on a fresh charge of fluid. We strongly advise you not to simply drain and change, but to take this opportunity to clean your system. Many potential problems will be pre vented by so doing.
Another reason for cleaning your system at this time Is to assure complete re moval of the Therminol FR fluid. A system cleanout is the only sure way to do so. How to go about the cleanout is a matter of choice, but here are some alternatives for your consideration:
A. Fluid Flush Cleaning This method is probably the fastest and most effective where heating surfaces are not heavily fouled. It also offers the
advantage of not having to introduce foreign chemicals into the system.
-90481545
TOWOLDMON0033226 WATER_PCB-00017695
With this method, the system is drained of Therminol FR, rc-filled with Therminol 55 or 66, operated for a reason able period of time, drained once again, and finally, re charged with fresh Therminol 55 or 66.
Both the drained Therminol FR and the Therminol 55 or 66 used to flush the system may then be returned to Monsanto for disposal.
B. Solvent Cleaning This method is satisfactory for cleaning a slightly soiled system, but chlorinated solvents must be avoided. Typical solvents used are acetone, benzene, and xylol (caution should be used with low flash point solvents). Do not use trichlorobcnzcne or perchloroethyiene. (CAUTION: ALL SOLVENTS SHOULD BE COMPLETELY REMOVED FROM THE SYSTEM PRIOR TO CHARGING WITH THERMINOL 55 OR 66). Normally this is accomoplished by drying the residual with warm air or by operating the refilled Therminol system at a temperature slightly above the boiling point of the solvent until the residual is vented from the system. Some caution should be used in drying the system to prevent flashing of the solvent with resultant discharge of Therminol from the system. Both the drained Therminol FR and the flushing solvent may then be returned to Monsanto for disposal.
.
Fluid Disposal Monsanto offers an incineration service for the disposal of PCB heat transfer fluids and the flushing fluids mentioned above. For details of this service
-10-
0 <101546
TOWOLDMON0033227 WATER_PCB-00017696
and how to return fluids to Monsanto for disposal, please write:
Monsanto Company P.0. Box 14617 St, Louis, Missouri 63178
...or call (314) 694-2514 and ask for a Monsanto Heat Transfer Specialist.
Handling; General Information Heat transfer fluids are intended only for indirect heating purposes. Under no circumstances should any Therminol heat transfer fluid be allowed to come in contact with or in any way contaminate food, animal feed, food products, food packaging materials, food handling equipment, pharmaceuticals or any food-related items.
Therminol 55 and Therminol 66; Safety of Handling
-.
According to the definitions of the U. S. Federal Hazardous Substances Label
ing Act, Therminol 55 and 66 are not toxic substances since the oral and dermal
lethal doses in animals are greater than 5 grams per kilogram of body weight.
Additional animal studies indicate that they do not have significant skin
or eye irritation potential. It is suggested however, that good industrial
practice relating to the avoidance of repeated and prolonged skin contact to
any industrial chemical, heat transfer fluids, or petroleum product be followed.
Therminol 55 and 66 have such low vapor pressures at ambient temperature that inhalation of vapors during transfer of fluid from shipping containers to a heat transfer system presents no hazard. Vapors emitted by either fluid at elevated temperatures may be irritating as would be the case with excessively heated petroleum oils. In heat transfer installations, the fluids are used in a closed, unpressurized system free from leaks and with the expansion tank
-11-
0481547
|
TOWOLDMON0033228 WATER_PCB-00017697
vent trapped so as to condense any vapors and thus prevent their escape to the work environment. Consequently, there should be little or no opportunity for workers to experience any contact or exposure,
While It is believed chat Thcrmtnol 55 and 66 pose no serious problems with respect to the environment, as a concerned supplier to industry, Monsanto urges the user to maintain a tight system, to correct leakage promptly, and to exercise care In the handling and disposal of this and all other such products. A tight maintenance program not only protects the environment, but keeps employes comfortable, the working area clean, and the system running smoothly.