CHAPTER 26
1949 Guide
Fig 1. Centrifugal Fan Type Unit Heater--Floor Mounted
Lj
T ........ TT
^-WALL*'f.
1 HEATING ELEMENT -
.SUPPLY | / . JUMPERS
-1 I J
14
RECIRCULATED /
" ./
RETURN
Fig. 2. Centrifugal Fan Type Unit Heater-Suspended
Fig. 4. Propeller Fan Type''Unit Heater--Vertical Blow.
Unit Heaters, Unit Ventilators, Unit Humidifiers
549
Table 2. Constants for Determining the Capacity of Unit Heaters for Various Steam Pressures and Temperatures of Entering Air
(Based on Steam Pressure of t Jmg and Entering'Air Temperature of 60 P)
Temperature op Entering Air SURE PSI -10 0 .10 20 30 . 40 50 60 70 80 90. 100?
0
2
5
10
Id 15
> H
20
X 30
D O'
40
* X
50
H 60
O 70 (9 75
SO
90 . 100
1.54 1.59 1.64 1.73 1.80 1.86 1.97 2.06 2.13 . 2.20 2.26 2.28 2.31 2.36 2.41
1.45. 1.50 1.55 1.64 1.71 1.77 1.87 1.96 2,04 2.09 2.16 2.18 2.21 2.26 2.31
1.37 1.41 1.46 1.55 1.61. 1.68 1.78 1.86 1.94 2.00 2.06 2.09 2:11. 2.16 2.20
1.27 1.32 1.37 1.46 1.53 1.58 1.68 1.77 1.85 1.90 1.96 1.99 2.02 2.06 2.11
1.19 1.24 1.29 1.38 1.44 1.50 1.60 1.68 1.76 1.81 1.87 1.90' 1.93 1.97 2.02
1.11 1.03 1.16 . 1.0S 1.21 1.13 1.29 1.21 1.34 1.28 1.42 1.33 1.51 1.43. 1.60 1.51 1.67 1.58 1.73 1.64 1.78 1.70 1.81 1.72 1.84 1.75 1.88 1.79 1.93 1.84
0.96 0.88 1.00 0.93 1.05 0.97 1.13 1.06 1.19 * 1.12 1.25 1.17 1.35 1.27 1.43 1.35 1.50 1.42 1.56 1.47 1.61 183 1.64 1.55 1.66 1.58 1.71 1.62 1.75 1.66
0.81 0.74 0.85 0.78 0.90 083 0.9S 0.91 1.04 0.97 1.10 1.02 1.19 1.12 1.27 1.19 1.34' 1.26 189, 1.31 1.45 1.37 1.47 1.40 1.50. 1.42 1.54 1.46 1.58 1.50
0.67 0.71' 0.7& 0.840.90 0.95 1.04 1.12 1.19 1.24 1.29 182 . 1.34 1.38 1.42
0 1.48 1.41 1.33 1.25 1.18 1.11 1.03 0.96 0.89 0.82 0.75 0.69
2 1.52 1.44 1.36 1.29 1.22 1.14 1.07 1.00 0.93 0.86 0.79 . 0.73
5 1.57 1.49 1.41 1.33 1.26 1.19 1.11 1.05 0.98 0.91 .0.84 0.77
10 1.64 1.56 1.48 1.40 1.33 1.25 l.ZS 1.11 1.04 0.97 0.90 0.84
CU 15 1.69 1.61 1.53 1.46 1.3S 1.31 1.24 1.17 .1:10 1.03 . 0.96 0.90
H- 20- 1.73 1.65 1.57 1.50 1.42 1.35 1.28 1.21 1.14 1.07 1.00 0.94
X o
30 1.80' 1.73 1.65 1.57 1.50 1.42 2.35 1,28 1.21 1.15 1.08 1.01
D --
O 40 1.86 1.79 1.71 1.64 1.56 . 1.49 1.42 1.35 1.28 1.22 1.15 1.0S
33 H
50 1.93. 1.85 1.77 1.70 1.63 1.55 1.48 1.42 1.35 1.28 1.21 185
60 1.97 .1.90. 1.82 1.75 1.67, 1.60 1.53 1.46 l:40 1.33* 1.26 1.19
OS 70 2.02 1.94 1.87 1.80 1.72 1.65 1.58 1.51 1.44 1.38 181 .184 Q
75 2.04 1.07 1.90 1.82 1.75 1.68 1.61 1.54 1.47 1.40 183 187
80 2.06 1.99 1.91 1.81 1.77 1.70 1.63 1.56 1.49 1.42 185 189
90 2.10 2.03 1.95 1.88 1.80 1.73 1.66 1.59 1.52 1.46 1.39 1.32
100 2.15 2.07 1.99 1.92 1.E5 1.77 1.70 1.63 1.56 1.49 1.43 .186
; To determine capacity at any steam pressure and entering temperature, multiply'constant from table by rated capacity at 60 F entering air and 2 psi.
When increasing steam pressure it is important to determine whether the heater is suitable for the increased pressureapplication and whether thereslilting increased outlet temperatureis satisfactory.'