CHAPTER 39
1951 Guide
operate because it is calibrated to operate on a higher yoltage. As the motor comes up to speed, the voltage across the starting, winding and relay coil increases in proportion to the motor speed. At a definite voltage corresponding to a pre-selected speed, the relay operates and opens its contacts, thereby opening the starting winding circuit. The relay then keeps these contacts open because there is sufficient voltage induced in the starting winding, when the motor is running, to hold the relay in the open contact position.
CONTROL FOR ALTERNATING CURRENT MOTORS
Squirrel-Cage motors are usually linestarted where power company limitations permit. In sizes up to 5 hp at 220 volts, or 7- hp at 440 volts, polyphase motors may be started by means of manual switches
LINE
MANUAL STARTER
ACROSS THE LINE STARTING
LINE
5COMBINATION
LINESTARTER WITH SAFETY SWITCH
2
line:
MOTOR
MOTOR
REDUCED VOLTAGE STARTjNG
LINE
LINE
;S
Amnxementa 8, 4 and 6 provide automatic push-button starting. Fig. 13. Recommended Controls for Squirrel-Cage Motors
having overload current elements for motor protection. In larger ratings a linestarter is usually provided -with eitheran additional safety switch or circuit breaker for disconnecting and short circuit protection. Reduced voltage starting may be either of manual or push button controlled magnetic type. In specifying this type of starter, consideration should be given to the fact that starting torque of squirrel-cage motors varies as the square of the applied voltage. For example, a motor developing 100 Ib-ft starting torque on full voltage would produce only 25 lb-ft torque on starting on half rated voltage. Fig. 13 illustrates recommended control practice for squirrel-cage motors. Typical specifications for squirrel-cage motor controls are shown in Specification G at end of chapter.
Wound Rotor motors require control of both primary and secondary circuits. The primary* control may be the same as for squirrel-cage motors, manual- or magnetic, at full voltage. Secondary* control pro vides means of varying secondary resistance for starting and speed control.
* Refer to Glossary at end of chapter.
Motors and Motor Controls
857
The secondary controller should be specified for starting duty only, or for speed regulating duty. If the secondary controller is to be used for speed regulating duty, the percent speed reduction, the number of speed control points, and the type of load (variable or constant torque) should be speci fied. Fig. 14 illustrates recommended control practice for wound rotor motors. Typical specifications for wound rotor motor control are shown in Specification H at end of chapter.
Synchronous motor starters should provide pull-out protection, auto matic synchronization or automatic stopping of the motor after pull-out, and insurance of complete starting sequence, as well as overload and low voltage protection. The control may be either magnetic or semi-magnetic at full or reduced voltage. Semi-magnetic starters provide automatic field control, but require hand operation for closing the line contactors to start and transfer to full voltage.
In applying reduced voltage starters to synchronous motors it should be remembered that, since these motors are started on damper windings and during the acceleration period function similarly to squirrel-cage
LINESTARTER RHEOSTAT B MOTOR
SPEED REGULATING CONTROLLER
COMBINATION LINESTARTER
RHEOSTAT
B
MOTOR
T1 D UNIT ASSEMBLED CONTROL
Fia. 14. Recommended Controls foe Wound Rotor Motors
motors, the starting torque varies as the square of the applied voltage. Consideration should be given to insure development of sufficient motor torque to accelerate the load. Typical specifications for synchronous motor control are shown in Specification I at end of chapter.
Multi-Speed control may be either manual or magnetic, and at full or reduced voltage. When using, automatic magnetic control with two-, three-, and four-speed separate winding or consequent pole motors, con trol may be obtained from a remote point by means of a push button master switch. The various speeds of the motor are obtained from the master switch by simply depressing the correct push button. This is known as selective speed control. It is commonly used in the smaller theater installations where the fan and motor are located backstage and the speed control is located in the lobby.
Multi-speed motor controllers may be provided with compelling relays, which make it necessary for the operator to press the first speed button before regulating the motor to the desired speed. This insures that the motor is always started at low speed before adjusting to a higher speed.
Timing relays which provide for automatic acceleration may be used for control. With this feature the motor will always start at low speed /