INSTALLATION
13-100 Sept. '56
THERMOCOUPLE INSTALLATION
Page 1
General
The thermocouple is the temperature-sensitive element of the potentiometer circuit, and is lo cated at the point where temperature is being measured. It is connected to the instrument with extension wires. In response to changes in the measured (or controlled) temperature, a greater or less EALF. is generated in direct pro
3. To protect the thermocouple at tempera tures high enough to destroy its accuracy.
4. To make it convenient to remove the ther mocouple from a location normally under pressure which cannot be relieved to atmos phere.
portion to the change in temperature of the thermocouple, thereby causing the instrument to indicate or record the temperature.
Thermocouple Installation The thermocouple location must be carefully
selected. Thermocouples must not be immersed, without the protection of a well or protection tube, in fluids or gases of a corrosive or erosive nature.
The connection head should not be subjected to temperatures in excess of about 400*F. In some cases it may be necessary to lengthen the protection tube in order to remove the head to a cooler location, thereby eliminating possible reference junction temperature errors.
Thermocouple Wiring
Extension wires, of the correct type for the particular thermocouple being employed, must
The thermocouple should extend into the me dium whose temperature is being measured so that the measuring junction is subject to the actual temperature. Insufficient immersion may cause errors due to the conduction of heat to or away from the sensitive end of the thermo couple. A thermocouple with protection tube should be Immersed in the heat zone to be meas ured to a depth of at least 4*. Longer immer
be used in connecting the thermocouple to the
instrument. In effect, they extend the thermo
couple to the instrument binding posts, placing
the cold or reference junction of each thermo
couple at the instrument. Temperature varia
tions at this cold junction are compensated for
by a cold junction compensating coil located near
the thermocouple binding posts on the instru
ment.
-m
sion is generally preferable; however, if the thermocouple passes through 6" or 8* of good insulating material, shorter immersion may prove to be satisfactory.
Platinum thermocouples with Flintex porce lain protection tubes can be installed vertically at temperatures up to 2800*F. When mounted horizontally, the practical allowable unsupported length of immersion varies inversely with the temperature. At 2600* F., the unsupported length should not exceed 6".
Most thermocouple assemblies are shipped completely assembled; however, parts for plati num thermocouple assemblies are generally packed separately in order to prevent breakage during shipment.
When two instruments are to read the same
Where thermocouple connection heads are not supplied with short wires assembled to them, connect the extension wires directly into the connection head, following carefully the instruc tions on the instruction, sheet describing the connection head. The positive wire (see color
code on reverse side) must be connected to the positive side of the thermocouple and to the positive instrument binding post; and the nega tive wire is similarly connected to the negative side of the thermocouple and the negative instru ment binding post. Be sure that the extension wires are the correct type to use with the ther mocouple being employed by referring to the tag attached to the wires.
All connections throughout the thermocouple circuit must be tight, and all parts in contact must be clean before being joined together. Con
temperature, do not expect them to read alike if nections should be soldered and taped, or made
the thermocouples are in different locations -- many times disagreement between Instruments is remedied by installing the thermocouples in the same well.
with approved screw connectors. The wiring must be protected from moisture and mechani cal injury. Wiring in conduit should preferably be rubber or polyvinyl plastic insulated and
Thermocouple Protection
Wells or protection tubes should be used for the following reasons:
weatherproof, for ail conduit pipe has a tendency
to "sweat." Only first quality electrical and weatherproof Insulation will prevent leakage be tween the wires and conduit wall.
1. To protect the thermocouple from erosion and corrosion, due to liquids or gases.
2. To protect the thermocouple from mechani cal injury.
Rubber insulated extension wires should not be exposed to temperatures in excess of approx imately 175 F; plastic insulated, 220 F; asbestos insulated, 600 F; glass insulated, 1000 F.
The Foxboro Company
Foxboro. Massachusetts. U S A. 02035
FqxborO
Printed in U.S.A.
CHEV bb 0000068
13-100 Page 2
COLOR CODES FOR EXTENSION WIRE INSULATIONS
Foxboro extension wires are furnished with insulations color-coded RED-NEGATIVE wires. The RED-NEGATIVE color code was first used in 1950 in accordance with Industry standard prac tice.
RED-NEGATIVE COLOR CODE
For Thermocouples: Positive
Copper-Constantan Iron-Constantan Chromel-Alumel
Plat. Rhod.-Platinum
Blue
White Green or
Yellow Black
Negative
Red Red Red
Red
NUMBER OF DUPLEX WIRES IN CONDUIT
The approximate number of extension wires which may be run in conduit of a given size is as follows:
Wires
Insulation
Rubber and Weatherproof Braid
Polyvinyl Plastic, Weatherproof Braid
Polyvinyl Plastic, Lead Sheathed
Asbestos, Twisted Pair
Asbestos, Asbestos Braid
Conduit Size (inches)
mGauge Yz % 1 1%
2 2Yz 3
14 2 4 7 12 16 28 40 64
16 3 5 9 16 22 36 52 80
14 3 5 9 16 22 36 52 80
16 4 7 11 20 28 47 66 100
14 1 1 1 3 5 7 10 20
IS 1 1 2 4 6 9 13 24
14 1 3 5 9 12 24 30 45
16 1 3 6 10 14 26 34 50
14 1 3 5 9 12 24 30 45
16 1 3 6 10 14 26 34 50