HEATING VENTILATING AIR CONDITIONING GUIDE 1944
liberated by the fuel. Under such conditions no manual attention to the fuel bed should be required, other than the removal of clinker in stokers which operate on this principle of ash removal.
As in all combustion processes, the maintenance of the correct pro portions of air and fuel is essential. It is desirable to supply the minimum amount of air required to properly burn the fuel at the rate of feed.
While there may be only slight variations in the rate at which the coal is being fed due to variations in the size or density of the coal, there may be wide variations in the rate of air flow as the result of changes in fuel bed resistance. These changes in resistance may be caused by changes
For reference in selecting or designing boilers and furnaces for stoker firing. Dimensions shown are for net inside clearance at grate level using coalwith beating valueof not less than 12,000 Btu per pound. Under, certain conditions smaller fireboxes will permit satisfactory performance but these dimensions are preferred normal minimurns
in the porosity of the fuel hed due to variations in size or friability of the coal, ash and clinker accumulation, and variations in depth of the fuel bed' Because of this variable- fuel bed resistance, many bituminous stokers, even in the smaller domestic sizes, incorporate air controls which automatically compensate for these changes in resistance and maintain a constant air fuel ratio.
It is desirable on most stoker installations to provide automatic draft regulation in order to reduce air infiltration and provide better control during the banking or off periods of the stoker. The efficiency of com bustion may be determined by analyzing the flue gases as explained in Chapter 8.
Furnace Design
Although there is considerable variation in stoker, boiler, and furnace
design, the stoker industry, from long-time experience, has established certain rules for the proportioning of furnaces for domestic, and com-
- 208
-
CHAPTER 10. AUTOMATIC FUEL BURNING EQUIPMENT
mercial stokers. The stoker installer, and designer of stoker-fired equip ment should give careful consideration to these factors.
The Stoker Manufacturers Association has published standard recom mendations on setting heights for stokers having capacities up to 1200 lb
of coal per hourl2. * The empirical formulas for determining these setting heights are:
For burning rates up to 100 lb coal per hour H = 0.1125 B + 15.75
. (1)
For burning rates from 100 to 1200 lb coal per hour H = 0.03 B + 24
(2)
where
H = minimum setting height, inches, for steel boilers. may be % H.
B = burning rate coal per hour, pounds.
For cast-iron boilers height
Standards for minimum firebox dimensions and base heights also have been formulated by the Stoker Manufacturers Association as shown in
Fig. 11s. In considering these recommendations, it should be understood that
they show the average recommended minimum. There are many factors affecting the proper application of stokers to various types of boilers and furnaces, and, in certain instances, setting height or firebox dimensions shown in the standards may be modified without impairing performance. Such modification rests with the experience of the installer, or designer, with a particular stoker, the type of fuel used, and the construction of the
boiler or furnace.
Sizing Stokers and Stoker Ratings
The capacity or rating of small underfeed stokers is usually stated as the burning rate in pounds of coal per hour. The Stoker Manufacturers Association has adopted a uniform method of rating stokers which is published in convenient tables and charts for selecting the size of stoker4. The required capacity of the stoker is calculated as follows:
Load (Btu per hour)
Stoker burning rate
------------------------------------------------------------;------------------------------- = required (pounds of
Heating value of coal (Btu per pound) X over-all efficiency of coal per hour)
stoker and boiler or furnace
. In determining the total load placed on a stoker-fired boiler by a steam or hot water heating system, a piping and pick-up factor of 1.33 is com monly used in sizing the stoker, but this factor should be increased at
times due to unusual conditions.
lMinimum Setting Heights. Copies of this standard may be obtained from the Stoker Manufacturers
Association, 307 N. Michigan Ave.. Chicago X, 111.
*Suggested Minimum Firebox Dimensions and Base Heights. Copies of this standard may be obtained'
from the Stoker Manufacturers Association, 307 N. Michigan Ave., Chicago 1, III.
4Uniform Stoker Rating Code. Copies of this standard may be obtained from the Stoker Manufacturers