Chapter 10--Cooling Methods
preceding unit, the alumina adsorbs approximately 25 per cent of moisture in the air and takes up about 1.3 per cent of its weight of W; During the second step when it is operating alone, it takes up 100 per of the moisture in the air until the weight of the water adsorbed is brou up to about 6.7 per cent. During the third step when the unit is operau with the succeeding unit, it extracts about 75 per cent of the moisture the air until the water weight adsorbed comes up to about 10 per cents the weight of the adsorber. The time allowable for reactivating is en, to the time occupied by the second unit adsorbing alone, plus the tli jf when the second and third units are adsorbing in series, plus the tiT when the third unit is adsorbing alone, at the expiration of which time first unit will be again required.
- The temperature of air-used-for-alumina reactivation is-usually betwu. 300 and 700 F and the air flow rate will have to be higher with the 1$ temperature air than it will be with reactivating air of higher temperatu^ For example, air at 400 F for reactivating will, at 10 cu ft per hour -3 pound of alumina, require about 6 hours for reactivation. In the tl unit system, after reactivation the cooling of the activated alumina 1.. be carried out with considerable rapidity by using dry air from the adso tion unit for circulation through the unit which has just completed rea vation. The final temperature of the unit before it goes back into sen should be not over 200 F. As a basis for computing the amount of coo' air required for reactivation, each cubic foot of cooling air has been fo; capable of removing 2.2 Btu when heated from 85 to 200 F and of pro ing a sufficient margin of safety in operation.
Design of System
When designing air conditioning systems, the capacity of equipment; decided by selecting apparatus of sufficient size to maintain predeterrain temperatures and humidities in treated spaces when arbitrarily es lished maximum atmospheric temperatures occur coincident with gi conditions of population, lighting, and power consumption. These fact determine the maximum duty of the cooling system. The duty does necessarily determine the size or capacity of the refrigeration apparat The refrigerating capacity is expressed in tons, each ton being equal to absorption of the heat given up by one ton of ice at 32 F melting to wa at 32 F in 24 hours. This is equivalent to heat absorption at a rate approximately 200 Btu per minute, or 12,000 Btu per hour.
After the maximum duty is determined, the other factors concemi. the installation must be investigated. The total heat to be removed the cooling system has many sources, some substantially constants others extremely variable. These sources can be. roughly classified follows, the first column indicating the order in amount and the `
the order in variability:
1. Fresh air supplied. 2. Population. 3. Transmission through the structure. 4. Light and power consumed.
1. Fresh air supplied. 2. Transmission through the struc' 3. Light and power consumed. 4. Population.
By combining these two columns, a third grouping is obtained follows:
170
l- TS.hsmirJonPthrough the structure.
3. Population. 4. Light and power consumed.
t this last arrangement, the first two items are governed by atmosL - conditions and they are therefore subject to tremendous fluctuP"-enC in value. As they generally form 40 to 60 per cent of the entire attVniim load, the duty of the cooling system will be much less than Smum most of the time.
The transmission through the structure is especially influenced by the
* (See Chapter 8.) In many cases, because of the heat flow resistance Sfthe structure, the heat from the sun is retarded until it is compensated
forTMy a reduced general temperature out-of-doors.
survey of-Weather Bureau recqrds_indicates_that_maximum tempera-tures occur less than 5 per cent of the cooling period and also that the duration of peak conditions is never more than three or four hours.
Two factors control the size of the refrigeration system, the evaporator or suction temperature, and the condenser or head temperature. With the knowledge that the system will operate most of the time with a load of not over 60 per cent of maximum, and that maximum demands will occur infrequently and only for short periods, some provision must be made to insure economical operation under average conditions. This can be done by overloading the machine under extreme demands and basing the design on normal or average loads. Flexibility in arrangement can be provided
in several ways.
Variations in load change the efficiency of any machine and a refrigera ting system can be costly and inefficient if improperly designed or operated. Fortunately, the trouble can be concentrated in the compressor and the problem relieved of many complications. It is comparatively easy to furnish condensers and evaporators to carry the maximum load so arranged that they will function properly at small demands. They affect the compressor performance to some extent but most of the compressor problems are in the machine itself.
Variations in load are usually effected by lowering the suction tem perature and pumping a larger volume of gas per ton through a greater pressure range. This is possible because the latent heat of the refrigerant remains nearly constant throughout the small range used and the specific volume varies rapidly with change in pressure. As the compressor must remove'-the refrigerant evaporated, the evaporator temperature fixes the displacement required. The objection to such method is that the total P?f?Ii9I?sumed remains nearly constant and the power per unit of cooung.increases rapidly as the total output is reduced. Such operation is satisfactory as long as the load is kept within 10 per cent of the rating
j.e. compressor but this condition does not commonly occur in air conditioning applications.
Operating Methods
Itispossffile to divide the entire refrigeration system into a number of
*1. I , ,, allow cutting in and out of compressors and conthe load fluctuates. This, however, is an expensive method as -Wa 7" 01 sm3ll units are usually more expensive than one large unit. ' v3, certain amount of duplication of equipment necessary, which