Document 3J80pr3rRNy5qDLBqBn7XMEgO

ABD00212382 OXYGEN MONITORS ABERDEEN CHEMICAL PLANT FEBRUARY 23, 1988 WORK BY: W. S. Fox, Jr. Contract Proc Engineer REVIEWED BY J./E. Nickerson Senior Process Engineer APPROVED BY: V. E. Messick Chief Process Engineer ABD00212383 OXYGEN MONITORS ABERDEKN-CHSMICAIi-PLANT TABLE OF CONTENTS I. PURPOSE OF DESIGN II. DESCRIPTION III. INSTRUMENT LIST ABD00212384 OXYGEN_MONITORS ABERDEEN CHEMICAL.PLANT I. PURPOSE_OF_DESIGN The purpose of this design is to provide continuous monitoring of ambient air oxygen concentrations. The areas to be monitored were identified in the inert gas/nitrogen system surveys. The survey report said that the following areas will be monitored: 1.- P-1 east side second floor. 2.- The inert gas generator room. 3.- Development Lab near liquid nitrogen storage room 4.- Development Lab storage room. 5.- Development Lab GC room. 6.- Old Module GC room. 7.- V-ll dryer bldg. GC room. ABD00212385 OXYGEN MONITORS ABERDEEN-CHEMICAL-PLANT II. DESCRIPTION The Safety and the Mechanical Department recommend the oxygen analyzer manufactured by Teledyne Analytical Instruments. Several of these instruments have already been purchased as part of the RQIP program for this same purpose. This type of instrument uses a Micro-Fuel oxygen sensor which provides a linear output that is proportional to oxygen concentration. This sensor is an electrochemical design that at the end of its useful life is disposed of like a flashlight battery. Two alarm levels are provided, one at 19.5 % oxygen and one at 19 % oxygen, per the recommendation of the Safety Department. At each entry into the monitored area 3 alarm lights will be provided. A green light will indicate a safe condition. A yellow light will indicate an oxygen content of 19.5 %. A red light will indicate an oxygen content of 19 % or below. Also in each monitored area an audible alarm will be provided. The areas in which the oxygen sensors will be installed are as follows: 1.- p-1 east side second floor.- Used to detect inert gas leakage when area is shut up due to cold weather. 2.- Inert gas generator room-" Used to detect leaks. The rack with the instruments for the above two areas will be located in the P-1 Bldg, control room. The instrument used will be a TAI Model 322/134-2, which is identical to those purchased for RQIP, except that these racks only hold two instruments instead of three. 3.- Development Lab near liquid nitrogen system.- The liquid nitrogen cylinder is stored inside the lab. Relocating the cylinder and/or routing the relief valve discharge outside is not practical and in any case would not eliminate the need for the monitor. Release of nitrogen gas in the past has already occurred. ABD00212386 4.- Development Lab storage room-" This room has been provided with a carbon dioxide fog blanket fire protection system. It also contains a compressed nitrogen system. Both system can be a source of inert gases. 5.' Development Lab GC room.- Nitrogen is used by the GC. The rack with the instruments for the above three areas will be located in the Development Laboratory. The instrument used will be a TAI Model 322/134-3, which is identical to those purchased for RQIP. 6.- Old Module GC room.- Nitrogen is used by the GC. The rack with the instrument for the above area will be located in the monitored area, with remote alarm in the vinyl control room. The instrument used will be a TAI Model 322/134-1, which is identical to those purchased for RQIP, except that these racks only hold one instrument instead of three. 7.- V-ll dryer bldg. GC room.- Nitrogen is used by the GC. The rack with the instrument for the above area will be located in the monitored area, with remote alarm in the vinyl control room. The instrument used will be a TAI Model 322/134-1, which is identical to those purchased for RQIP, except that these racks only hold one instrument instead of three. ABD00212387 OXYGEN MONITORS ABERDSEN_CHEMICAL_PLANT III. INSTRUMENT LIST ITEM AN-101 AN-102 AN-103 AN-104 LOCATION P-1 Bldg. Control Room Development Laboratory Old Module GC room V-ll Dryer Bldg. GC room ABD00212388 nuiT SKIS VKTA !KSSsS?ta,w.VlwIrX HOUSTON, TtXAS SlMCifiMtlOn ShMt '" ^-io\ pqrviprr rrr"""--PROJECT HQ A P e NO onun UAnPRV W- V riATP^/sr/ftft APiTORV M Vexiles i i ' c^A. X 'TkX M,oJUfiA 3ol^.j//i4"~ ^ Dih+c^aa- -0 * ^ O-JU. ; K\ V A-la-*** : (/\ c&*jn-&0 C*> 11 '5 % Oa. (iN^u^ea <?> if,o-A Oq. (j'b "RM i___ "Sjw j'V ` Cl^-*-C4_ M | cvo - ' -w-eJ. Cr P S erl'Jti.LsjL- lib /b<> H->- C<>J^ \ P b*<X. va.0 u>A CaaAv\ 'Ux*x4 <** ^A, (^-\ ^vitt* '/h cJ\A k*cA pmiImAao. u tv'G^-W. ifcvffuyict Cnt m-ow t)w (3 -fl<j. " * *. MONO. SHOT MV. OP Mi ABD00212389 VISTA .V Iw 1/ \ Ss2sS2'Co,w""' HOUSTON. TEXAS SMciflcatlon Shett di^wt Abevcl<r*A ' n PBriiFOT AW-ioa> PROJECT NO------------------------------------------ ----- kVr NO on un MAnPBY \N- S- PX . Jv , , nATg ^Mf/8 8 APP n by VeA*.Jloy "Til-cd^vus- At\x. U Mc-*-A. .^-<.4^cwAtficl-o 1V i HoAeH : TkT KoJlJL 3A5.//3f-JS Ox-j^ "]^cA r ? t*s-cs-^ fM Aa^-i "i-irv" "^4*^ : (9-^5 % Go ved-JL C U.4 wneJl B d-tj4flr2>o<-A. r A'l^ " Al^-VvV\ ' ('} CLA'>'TIoO '(O (/A 'bMJ&tfc. <> ON PA/a- 5"tf/o H.0 7- <?i ' r 1Mi cvt^A Blc-koJL: /'O 1/AC./6 0//* - CtAA-fc <i^\ioJr\cw; Fl ^-oU. ^ 0Me5. rv\ou^vcV o/AA'V>x. 1 "Iom.4 f3\ ^Cvluj 33.3 OAi (Umuavv-cX kvlfrlu Ii2t> \ mou^r d/W4c*v. fi>n>b-u. SFKNa SHEET REV. no 24* ABD00212390 VICta jKsrjs?e,,,^>' *--*-- . Iwl/ \ HOUSTON. TEXAS SMciftcatlon Shoot PROJECT NO. --. APj! no on ^ UAnpnv W- A ero>. At , dn rnoeY e e*\ ^ , ,QATE^>t/ag_ .pu8r f-Apfifuprr o'* i cu^. avutw^ SSdSv!m mo-103 0^1 AW-/of ~ Ve^tSlo* ' ~T^ \ ;hioiceSi T'A.X ^e_i Aw_aJ^-h Ifc 1 Mt^eJl.. 33A.//3^--/ M f^-Vx/v ....... - O"^60/o Oa Yf>-A<rdr CU. rlttL^vveS M oAuJLo K . /M<Ua: (0 CAOTIOKj; @ M ^AtO&Efe fO (fl FA/L I1.5%0a. 1^.0 7* 0^ ^fivv-4^r ' 0^4^- 3"3 M\<^T>pA.-^ C^jUL ^AiovA: //o/Ac/^ //e. Cojrt-i oa- M*-ctA. . M 'Se^ri 0\ l^-auAt` cac\y*I T-ciUrf 3^ cJajI Mui-wJL^ /no\c-4" (jh^ouo^ pY>be* 0 <1 l ` - ,,t SMC NO. SHOT MV. OP M4