Document 36EkR5M7bNd5K1zykK8JyMV6
American Society of Heating and Ventilating Engineers Guide, 1937
the time of day and the direction of the wind. A chart showing the increase in resistance of a unit filter of the viscous impingement type when tested with the standard test dust described in the code3, is given in Fig. 2. The resistance to air flow of three typical clean viscous impinge., ment type filters having different media densities is shown in Fig. 3/ Type A is a dense pack used in bacteria control; Type B is a medium pack used for general ventilation work and Type C is a low resistance unit for use where low resistance is the important factor and maximum cleaning efficiencies are not essential. The operating characteristics which might be expected under various dust concentrations with air filters having different dust-holding capacities are illustrated in Fig. 4.
Filters consisting of inexpensive frames of cardboard or similar material filled with viscous-coated glass wool, steel wool or the like are available.
Fig. 4. Maintenance Chart for Unit Type Viscous Filters
Because of their construction these units may be discarded when dirty and replaced with new units at relatively little expense. They are used in
general ventilation work and with warm air furnaces and other instal lations where low first cost and low resistance to air flow are essential. The operating characteristics of these units conform in general with those of the rigid frame type.
Viscous Automatic Filters
The principle of air cleaning used in the viscous automatic filters is the same as in the unit filters. The removal of the accumulated dust, however, is done automatically instead of by hand. The automatic clean ing and recoating of these filters is based on the principle that the viscous fluid itself will perform the cleaning function, thereby eliminating a sepa
rate washing agent. The dust collected by the filter thus is deposited finally inThe bottom of the viscous fluid reservoir from which it may be removed.by. different methods, depending on the design of the filter.
Loc. Cit. Note 1.
312
Chapter 16--Air Cleaning Devices
There are three general types of automatic filters. They are differentiated
from ea^ ther according to the process of self-cleaning and renewing
of the viscous coating used by each type, as follows:
1 The filter medium has the form of an endless curtain suspended vertically, with its lower portion submerged in a viscous fluid reservoir. The curtain rotates slowly through Uis bath, thus performing the cleaning and recoating of the filter medium.
2 The filter screen is arranged in the form of shelves or cylinders, and the viscous fluid is flushed through all parts of the medium in a direction opposite to the air flow.
3 The filter medium is arranged vertically and is stationary. The viscous fluid is flushed from above over the medium, while the air flow is stopped.
The washing and renewing process in automatic filters usually is inter mittent. It is accomplished by an electric motor or by other motive power and is controlled by manual or by automatic timing devices. The operating cycle is of a predetermined frequency and should be so timed as to insure a constant static pressure drop across the filter. The customary resistance to air flow is %-in. water gage at an air velocity of 500 fpm, measured at the filter entrance. Automatic viscous filters are made up in units which are delivered either fully assembled or in parts to be assem bled at the point of installation.
DRY AIR FILTERS
Dry air filters, in which dust is impinged upon or filtered through screens made of felt, cloth, or cellulose, are available in various types. These filters require no adhesive liquid, but depend on the straining or screening action of the filtering medium. Because of the close texture of the filtering media used in most of the dry filters, the surface velocity, or velocity of the air entering the media, ranges between 10 and 50 fpm, depending on the nature and texture of the fabric. This necessitates a relatively large screen surface, and the filter media, are.usually arranged in the form of pockets to bring the frontal area within customary space requirements.
As in viscous unit filters, an average constant resistance and air volume may be obtained by periodic reconditioning or renewal of the filter screens. Since some materials suitable for dry filtering media are affected considerably by moisture which tends to cause a rapid increase in resis tance, they should be treated or processed to minimize the effect of changes in humidity.
Filters using felt and similar materials as filter media usually depend upon vacuum cleaning for reconditioning. A special nozzle, operated from a portable or stationary vacuum cleaner, is shaped to reach all parts of the filter pockets. Permanent filter media should be capable of with standing repeated vacuum cleanings without loss in dust removal efficiency. While most dry filters are cleaned by replacing an inexpensive filter sheet, the useful life of these sheets often may be lengthened by vibrating or vacuum cleaning.
METHODS OF INSTALLATION
The published performance data for all air filters are based on straight through unrestricted air'flow. Filters should be installed so that the face area is at right angles to the air flow whenever possible. Eddy currents
313