CHAPTER 50
1960 Guide
creasing the relative humidity to at least 55 percent, if the material being processed is not damaged thereby.
It must be borne in mind that for successful elimination, the air that actually comes in contact with the material in the machine must be at a relative humidity of 55 percent or
more. As some machines consume a great deal of power, which is converted directly into heat, the temperature in the machine may be considerably higher than the tempera ture adjacent to the machine where the relative humidity
Air Conditioning in Textile Mill* (Textile Workers Union of America, CJ.O., Research Department Technical Report).
L. L. Lewis: Air conditioning for textile plants making and using synthetic yams (Rayon Textile Monthly, July, August,' September 1930).
P. L. Davidson: Refrigeration for textile mill air condition ing (Heating and Ventilating, May 1947, p. 57).
C. G. Weber: Bureau of standards studies determine press room conditioning requirements (Heating, Piping and Air Con ditioning, March 1936, p. 137).
is normally measured. In such cases, the relative humidity in the machine will be appreciably lower than that elsewhere in the room, and it may therefore be necessary to maintain
a room relative humidity of 65 percent, or even more, to maintain the desired humidity.
Humidity in the presroom (Heating and Ventilating, May 1932, p. 35).
Dehumidifying with gas in a printing plant (Heating and Ventilating, May 1935, p. 31).
R. T. Williams: Air conditioning the newspaper plant (Heating and VentHating, September 1937, p. 63).
Control of Conditions for Material Test Labora tories
Laboratories having controlled conditions of temperature and humidity, are common, not only for the purposes of scientific research, but also for routine testing and for quality production control. A control of temperature and humidity within fairiy-close plus or minus limits is usually required. Laboratories designed for scientific research may require control of conditions over a wide range, whereas the routine testing laboratory or quality control laboratory will usually be designed to maintain the ASTM Standard Conditions of 50 percent relative humidity and 23 C (73.4 F) temperature.
CALCULATIONS
The methods for determining the heating and cooling loads for the various industrial processes are similar to those outlined in Chapters 12 and 13. Some factors affecting heating or cooling requirements are given in Table 1. Be cause of the large number of motors and heat producing units usually found in an industrial application, it is particularly important that operating allowances, for the latent and sensible heat loads, be definitely ascertained and used
Air conditioning in the [taper industry (Heating and Ven tilating, October 1935, p. 23).
C. G. Weber: Air conditioning requirements of multicolor
6o)ff.set printing (Refrigerating Engineering, December 1836, p.
C. G. Weber and L. W. Snyder: Reactions of lithographic papers to variations in humidity and temperature (17.8. Bureau of Standards Journal of Research, January 1934).
C. G. Weber and M. N. Geib: The treatment of offset papers for optimum register (U. S. Bureau of Standards Journal of Research, February 1936).
H. E. Ryerson: Silica gel air conditioning system serves rotogravure printing plant (Heating, Piping and Air Condi tioning, August 1937, p. 497).
Air conditioning for clothing research laboratory (Healing and Ventilating, July 1943, p. 69).
C. S- Leopold: Controlled air supply for supercharger, car buretor and engine testing (Refrigerating Engineering, August 1943, p. 85).
R. P. Dewey: Close machine tolerances possible through 6te0m).perature control (Healing and Ventilating, April 1944, p.
F. M. Johnson: Moisture control by liquid absorption offers a useful air-conditioning tool (Heating, Piping and Air Con ditioning, December 1938, p. 782).
S. C. Rothman: The engineering control of some solvent hazards in war industries (ASHVE Transactions, Vol. 50, 1944, p. 319).
in the calculations to determine the total design load.
BIBLIOGRAPHY
H. A. Mctsber: When is complete air conditioning of the modem factory advisable? (Heating, Piping and Air CondiHoning, June 1945, p. 305; July 1945, p. 385).
N. N. Wolpert: Air conditioning design conditions for vari ous industries (Heating and Ventilating, May 1949, p. 70; June 1949, p. 73; July 1949, p. 79; August 1949, p. 102).
N. N. Wolpert: Air conditioning design data for commercial applications (Heating and Ventilating, February 1950, p. 68).
ASRE Data Book Applications 1956-57 (American Society of Refrigerating Enchneess ).
W. L. Fleisher: Air conditioning in the bakery (ASHVE Transactions, VoL 37, 1931, p. 141).
W. W. Reece: Air condition the bakery throughout (Heating, Piping and Air Conditioning, August 1936, p. 419).
H. R. Gable: The air conditioning of processes in the bread bakery (ASHVE Journal Section, Heating, Piping and Air Conditioning, October 1947, p. 107).
A. E. Stacey, Jr: Proper air conditions for the manufactur ing of confections (ASHVE Journal Section, Heating, Piping and Air Conditioning, October 1937, p. 640).
J. Johnson and W. B. Ogden: Relation of Air Conditions to Tobacco Caring (Wisconsin Agricultural Research Bureau, 110:1-48, 1931).
D. C. Lindsay: Air conditioning as applied in theatres and film laboratories (Society of Motion Picture Engineers Trans actions, Vol. XI, 1927, p. 335).
F. F. Stevenson: Industrial air conditioning (Heating, Pip ing and Air Conditioning, May 1948, p. 100; June 1948, p. 94).
J. F. Salsburg: Industrial air conditioning (Heating, Piping and Air Conditioning, July 1943, p. 83; October 1948, p. 93).
C. S. Cave: Industrial air conditioning (Industry and Power, July 1945, p. 67; September 1945, p. 57).
L. R. St. Onge: Reducing heat loads in industrial air condi tioning (Refrigerating Engineering, January 1946, p. 35).
Air, light, and sound controlled in Western Electric's new plant (Heating, Piping and Air Conditioning, November 194S, p. 79).
J. T. Browne: New IBM plant addition, Poughkeepsie, N. Y. (Heating, Piping and Air Conditioning, January 1949, p.
E. E. Herbacek: Photo studios need conditioning for both processing and comfort (Heating, Piping and Air Conditioning, June 1949, p. 85).
A. D. Benjamin: Maintaining constant relative humidity (Air Conditioning, Heating and Ventilating, May 1955, p. 83).
C. P. Strickland, Jr: Today's improved lemon storage (Re frigerating Engineering, December 1956, p. 43).
G. A. Warner: Laboratory climates automatically controlled (Refrigerating Engineering, June 1957, p. 50).
J. C. Siegesmund: Heating, air conditioning and insulation for penicillin production (Heating, Piping ana Air Condition ing, August 1944. p. 475).
/
H. E. Rex: Refrigerating equipment for the citrus industry (Refrigerating Engineering, November 1957, p. 43).
R. 8. Ash: Greenhouse climate control (Refrigerating En gineering, February 1958, p. 41).
CHAPTER 51
CONTROL OF THE INDUSTRIAL ENVIRONMENT
Heat Control of Industrial Work Areas, Thermal Standards, Control of Heat Exposures, Radiation Shielding, Roof Ventilators, Local Relief Methods, Physiological Aspects of System Design, Types and Requirements of Systems, Outlet Types and Design, Control of Contaminants
ONTROL of the industrial environment is concerned of this process heat or to offset it completely by the usual
C with the design and application of equipment for pro methods of comfort ventilation and air conditioning. In the viding the nece&ary conditions within industrial areas for design and operation of control measures it is frequently nec
rpflint&ining the efficiency, health, and safety of workers. This essary to accept some heat exposure in excess of simple com
chapter includes a comprehensive list of the requirements fort requirements.
for heat control and for control of gases and vapors, and dust
The engineer must distinguish between the control needs
and fumes.
for hot-dry industrial areas and warm-moist conditions. In
General ventilation may be relied upon in some cases to the first case, the process gives off only sensible and radiant
control the industrial environment, as outlined in this chap heat without adding moisture to the air. The heat load on ex
ter. Additional information on natural ventilation may be posed workers is thereby increased but the rate of cooling
found in Chapter 11. If mechanical ventilation is to be used, by evaporation of sweat is not reduced. Heat balance may
Chapter 20, Air Distribution; Chapter 21, Air Duct Design; be maintained although this will be at the expense, perhaps,
Chapter 22, Fans; Chapter 24, Air Cleaning; Chapter 40, of excessive sweating. In the warm-moisture situation, the
Evaporative Apparatus for Heat Rejection; Chapter 41, wet process gives off principally latent heat. There may be
Evaporative Air Cooling and Humidification; and Chapter no significant rise in the heat load on the worker but the
43, Automatic Control; will furnish information covering a increase in moisture content of the air will seriously reduce
broad range of industrial design conditions. Chapters 13, 23, the heat loss by evaporation of sweat. The warm-moist situa
and 38 provide data for mechanically cooled systems..Chap tion is potentially more hazardous than the hot-dry.
ter 52, Industrial Exhaust Systems, should be consulted for
Examples of hot-dry work situations are seen around hot
the design of hoods and their exhaust duct systems. For fur furnaces, forges, metal-extruding and rolling mills, glass-
ther information on estimating radiant heat conditions see forming machines, and the like. Typical of warm-moist oper
Chapters 5 and 30.
ations are laundries, dye houses, and deep mines where wa
Information on globe thermometers and other instruments ter is extensively used for dust control.
used to measure the industrial environment may be found in
The industrial heat problem varies in magnitude with
Chapter 44, Instruments and Measurements. More complete local climatic conditions. Solar heat gain and an elevated
information will be found in References1 and* at the end of outdoor temperature will increase the heat load at the work
this chapter.
place but these contributions may not be very important
Specialists in the field of industrial hygiene should be con compared with the locally generated heat of the process it
sulted in case of doubt concerning the presence of airborne self. The moisture content of the outdoor air, on the other
industrial hazards to health. Chapter 7, Air Contaminants; hand, is a most important climatic factor affecting hot-dry
Chapter 6, Physiological Principles; and Chapter 8, Air work situations and on a moist summer day will seriously
Conditioning in the Prevention and Treatment of Disease, restrict evaporative cooling. For the warm-moist job, in
will be of help in establishing the atmospheric conditions contrast, solar beat gain and elevated outdoor temperature
that should be maintained around the worker.. Local codes, are the more important, since, compared with the moisture
ordinances, or state labor laws must likewise be observed, release on the job, that contributed by the outdoor air will
particularly with regard to ventilation requirements for haz be of little significance.'
X
ardous trades. Comfortable conditions, if possible, or toler able conditions at least, are desirable because they are likely
Thermal Standards for Industrial Work Areas
to increase the efficiency and, hence, the output of workers. The majority of air-conditioning and ventilation installa tions in a typical industrial plant are concerned with the control of sensible, latent, or radiant heat.
The work situations considered here are those in which the attainment of simple thermal comfort is cot always prac ticable. The heat stress must be kept below the level of out right hazard, but how much below? On what criteria should
HEAT CONTROL IN INDUSTRIAL WORK AREAS
the specifications for control be based? How should the standards be varied in recognition of the differing demands
In certain industrial work situations there is considerable and work rates from one kind of job to another? What dif
release of heat from the process equipment to the environ ferences exist between older and younger workers or between
ment. It is not economically feasible to stop the escape of all workers with differing degrees of physical fitness? To what
709