HEATINC VENTILATING AIR CONDITIONING CUIDE 1944 CHAPTER 7. COOLINC LOAD into three general classes of equipment or devices: (1) electrical ap pliances, (2) gas appliances, and (3) steam heating appliances. In the first group may be found such devices as lights11, fans, motors, toasters, waffle irons, etc. The wattages are usually marked on the name plates and it is only necessary to multiply the aggregate wattage by 3.413 (Btu per watthour) in order to estimate the heat added to the conditioned space by such devices in Btu per hour. Electric motors are usually rated in units of horsepower output. To determine the corresponding input, which is the rate at which heat is added to the conditioned space by full-load operation of such motors, some idea of motor efficiency is necessary. The aggregate input in horsepower should then be multiplied by 2546 (Btu per horsepower hour). When motor efficiencies are not known, the data in Table 9 may be used. Table 9. Heat Generated by Motors Nakr-platb Rating Horsepower to K Hto3 3 to 20 TTwat Gain in Btu per Houb pee Horsepower Connected Load in Same Room 4250 3700 2950 Connected Load Outside of Room 1700 1150 400 In the second group belong such appliances as coffee urns, gas ranges, steam tables, broilers, hot plates, etc. For heat generating capacities of such appliances refer to Table 10. Considerable judgment must be followed in the use of data given in Table 10. Consideration must be giyen to time of day when appliances are used and the heat they contribute at time of peak load. Only those appliances in use at the time of the peak load need be considered. Con sideration must also be given to the way appliances are installed, whether products of combustion are vented to a flue, whether they escape into the space to be conditioned, or whether appliances are hooded allowing part of the heat to escape through a stack. There are no generally accepted data available on the effects of venting and shielding heating appliances but it is believed that, when they are properly hooded with a positive fan exhaust system through the hood, 50 per cent of the heat will be carried away and 50 per cent dissipated in the space to be conditioned." Where latent as well as sensible heat is given off, it is usually safe to assume that all latent heat will be removed by a properly designed and .operated vent or hood. 1 j3 Table 10. Heat Gain from Various Sources1 Source Percent Name- plate Rating Percentage or Btu per Hour Sensible Latent Total Electric Healing Equipment 70 7 Hnt Plate* 20 30 50 80 100 75 70 40 60 50 100 16. Permanent Wave Machine in Beauty Parlor--24-25 w Units- -- 80% 80% 1025 90% 80% 100% 65% 90% 75% 90% 90% 90% 2050 2050 20% 20% 1025 10% 20% 0% 35% 10% 25% 10% 10% 10% -- 100% 100% 100% 100% 100% 100% 100% 100% 2050 Gas Burning Equipment0 17. Gas Heated Oven--Baking-- _____ no vent connection gravity vent connection 18. Open Top Burner--per Hole____ 19. Hot or Closed Top--per Burner-- _____ no vent connection gravity vent connection 20. Coffee Urn--Large 18 in. Diam.--Single Drum 21. Coffee Urn--Small 12 in. Diam.--Single Drum. 22. Coffee Urn--per Gallon of Rated Capacity____ 23. Plate Warmerno vent connection gravity vent connection 24. Steam Table--Water Bath ' * ,,no vent connection gravity vent connection 25. Frying Griddles________ _____ no vent connection gravity vent connection 26. Fry Kettle- ______ no vent connection gravity vent connection 27. Egg Boiler--per Egg Compartment- 28. Cigar Lighter--Continuous Flame Type__ 29. Curling Iron Heater----------------------------------- 30. Pilot Light................................................. ......... 70 35 50 100 70 ,, 60 10 60 42 75 52 70 49 -- 72% 100% 45% 45% 60% 5000 3000 500 90% 100% 50% 81% 90% 72% 80% 2500 2250 2250 180 28% 0% 55% 55% 50% 5000 3000 500 10% 0% 45% 50% 19% ` 10% 28% ' 20% 2500 250 250 20 Steam Heated Equipments 31. Steam Heated Surface Not Polished--per Square Foot of 32. Steam Heated Surface Polished--per Square Foot of Surface 33. Insulated Surface--per Square Foot- ................................ 34.'. Bare Pipes, Not Polished--per Square Foot of Surface_______ 35. Bare Pipes, Polished--per Square Foot of Surface___ 37. Coffee Um--Large, 18 in. Diam.--Single Drum........ 38. Coffee Urn--Small, 12 in. Diam.--Single Drum___ - 39. Egg Boiler--per Egg Compartment. ................ 40. Steam Table--per Square Foot of Top Surface______-- __ -- 330 130 80 400 220 110 2000 1200 2500 300 0 0 0 0 0 0 2000 1200 2500 800 . 330 130 80 400 220 110 4000 2400 5000 1100 Miscellaneous Moisture Through Walls In some applications walls of the conditioned space may be in contact 41. Heat Liberated By Food per Person, as in a Restaurant_____ -- 30 30 60 42. Heat Liberated from Hot Water used direct and on towels 100 200 300 with other spaces which have in them a higher water vapor pressure than that in the conditioned space. It is known, that water vapor will flow "Heat gain from electric or gas residential ranges or cooking stoves depends on size of the,family, socio economic status of the individual, time of day for principal meal, and whether the equipment.is manually or automatically controlled. Total heat gain will probably not exceed 40 per cent name-plate rating. Per cent sensible and latent heat will depend upon use of equipment; dry heat; baking or boiling. "Cooler Footcandles for Air Conditioning, by W. G. Darley (A1S.H.V.E.. Transactions,. VoL. 46, 1940. p. 367). Lighting and Air Conditioning Design Factors, Report of /. E. S.--A.S.H.V.E. Joint Com mittee on Ughting in Air Conditioning (A.S.H.V.E. Journal Section. Heating, Piping and At? Con ditioning, September. 1941, p. 605). Lighting and Air Conditioning, by Howard M. Sharp (Heating and Ventilating, November. 1942, p. 35). b Name-plate ratings of gas burning equipment can be obtained from a Directory of Approved Gas Appliances and Listed Accessories, January 1,1942, obtainable from American Gas Association Laboratories, * Cleveland, Ohio. o Steam Requirements of Process Equipment, Report of the Commercial Relations Committee, National District Heating Association (Heating, Piping and Air Conditioning, November, 1942, p. 675). 158 7: ` 159 i