HEATINC VENTILATING AIR CONDITIONING CUIDE 1944
CHAPTER 7. COOLINC LOAD
into three general classes of equipment or devices: (1) electrical ap pliances, (2) gas appliances, and (3) steam heating appliances.
In the first group may be found such devices as lights11, fans, motors, toasters, waffle irons, etc. The wattages are usually marked on the name plates and it is only necessary to multiply the aggregate wattage by 3.413 (Btu per watthour) in order to estimate the heat added to the conditioned space by such devices in Btu per hour.
Electric motors are usually rated in units of horsepower output. To determine the corresponding input, which is the rate at which heat is added to the conditioned space by full-load operation of such motors, some idea of motor efficiency is necessary. The aggregate input in horsepower should then be multiplied by 2546 (Btu per horsepower hour). When motor efficiencies are not known, the data in Table 9 may be used.
Table 9. Heat Generated by Motors
Nakr-platb Rating Horsepower
to K Hto3 3 to 20
TTwat Gain in Btu per Houb pee Horsepower
Connected Load in Same Room
4250 3700 2950
Connected Load Outside of Room
1700 1150 400
In the second group belong such appliances as coffee urns, gas ranges, steam tables, broilers, hot plates, etc. For heat generating capacities of such appliances refer to Table 10.
Considerable judgment must be followed in the use of data given in Table 10. Consideration must be giyen to time of day when appliances are used and the heat they contribute at time of peak load. Only those appliances in use at the time of the peak load need be considered. Con sideration must also be given to the way appliances are installed, whether products of combustion are vented to a flue, whether they escape into the space to be conditioned, or whether appliances are hooded allowing part of the heat to escape through a stack. There are no generally accepted data available on the effects of venting and shielding heating appliances but it is believed that, when they are properly hooded with a positive fan exhaust system through the hood, 50 per cent of the heat will be carried away and 50 per cent dissipated in the space to be conditioned." Where latent as well as sensible heat is given off, it is usually safe to assume that all latent heat will be removed by a properly designed and .operated vent or hood.
1 j3
Table 10. Heat Gain from Various Sources1
Source
Percent Name-
plate Rating
Percentage or Btu per Hour
Sensible Latent Total
Electric Healing Equipment
70
7 Hnt Plate*
20
30
50
80
100
75
70
40
60
50 100
16. Permanent Wave Machine in Beauty Parlor--24-25 w Units- --
80% 80% 1025 90% 80% 100%
65% 90%
75% 90% 90% 90% 2050 2050
20% 20% 1025 10% 20%
0%
35%
10%
25% 10% 10% 10%
--
100% 100%
100% 100%
100%
100%
100%
100%
2050
Gas Burning Equipment0
17. Gas Heated Oven--Baking--
_____ no vent connection
gravity vent connection
18. Open Top Burner--per Hole____
19. Hot or Closed Top--per Burner-- _____ no vent connection
gravity vent connection
20. Coffee Urn--Large 18 in. Diam.--Single Drum
21. Coffee Urn--Small 12 in. Diam.--Single Drum.
22. Coffee Urn--per Gallon of Rated Capacity____
23. Plate Warmerno vent connection
gravity vent connection
24. Steam Table--Water Bath '
* ,,no vent connection
gravity vent connection
25. Frying Griddles________
_____ no vent connection
gravity vent connection
26. Fry Kettle-
______ no vent connection
gravity vent connection
27. Egg Boiler--per Egg Compartment-
28. Cigar Lighter--Continuous Flame Type__
29. Curling Iron Heater-----------------------------------
30. Pilot Light................................................. .........
70 35 50 100 70
,,
60 10 60 42 75 52 70 49
--
72% 100% 45% 45%
60% 5000 3000
500 90%
100%
50% 81% 90% 72% 80% 2500 2250 2250 180
28% 0%
55% 55% 50% 5000 3000 500
10% 0% 45% 50% 19%
` 10% 28%
' 20% 2500
250 250
20
Steam Heated Equipments
31. Steam Heated Surface Not Polished--per Square Foot of
32. Steam Heated Surface Polished--per Square Foot of Surface
33. Insulated Surface--per Square Foot-
................................
34.'. Bare Pipes, Not Polished--per Square Foot of Surface_______
35. Bare Pipes, Polished--per Square Foot of Surface___
37. Coffee Um--Large, 18 in. Diam.--Single Drum........
38. Coffee Urn--Small, 12 in. Diam.--Single Drum___ -
39. Egg Boiler--per Egg Compartment.
................
40. Steam Table--per Square Foot of Top Surface______--
__
--
330 130 80
400 220 110 2000 1200 2500
300
0
0 0 0 0 0 2000 1200
2500 800
.
330 130
80 400
220 110 4000 2400
5000
1100
Miscellaneous
Moisture Through Walls In some applications walls of the conditioned space may be in contact
41. Heat Liberated By Food per Person, as in a Restaurant_____ -- 30 30 60 42. Heat Liberated from Hot Water used direct and on towels
100 200 300
with other spaces which have in them a higher water vapor pressure than that in the conditioned space. It is known, that water vapor will flow
"Heat gain from electric or gas residential ranges or cooking stoves depends on size of the,family, socio economic status of the individual, time of day for principal meal, and whether the equipment.is manually or automatically controlled. Total heat gain will probably not exceed 40 per cent name-plate rating. Per
cent sensible and latent heat will depend upon use of equipment; dry heat; baking or boiling.
"Cooler Footcandles for Air Conditioning, by W. G. Darley (A1S.H.V.E.. Transactions,. VoL. 46, 1940. p. 367). Lighting and Air Conditioning Design Factors, Report of /. E. S.--A.S.H.V.E. Joint Com mittee on Ughting in Air Conditioning (A.S.H.V.E. Journal Section. Heating, Piping and At? Con ditioning, September. 1941, p. 605). Lighting and Air Conditioning, by Howard M. Sharp (Heating and Ventilating, November. 1942, p. 35).
b Name-plate ratings of gas burning equipment can be obtained from a Directory of Approved Gas Appliances and Listed Accessories, January 1,1942, obtainable from American Gas Association Laboratories, * Cleveland, Ohio.
o Steam Requirements of Process Equipment, Report of the Commercial Relations Committee, National District Heating Association (Heating, Piping and Air Conditioning, November, 1942, p. 675).
158 7: ` 159