June 7, 1983
Mr. Bill Stevart (2) Executive Director Texas Air Control Board 6330 Highway 290 East Austin, Texas 78723 Attention: K. A. Langley
Compliance
Dear Mr. Stewart:
RE: NESHAPS Notifications of ' Emergency Asbestos Removal - II Du Pont, Victoria County, Texas
On May 31, 1983, we sent you notice that on May 28, 1983,
E. I. Du Pont De Nemours & Co.(Inc.), the owner, whose address is P. 0. Box 2626,
Victoria, Texas 77902, had started removal of approximately 4,600 sq.ft, of
asbestos containing insulation from five distillation columns in our adipic acid
plant (TACB Permit R-810) under emergency conditions. This letter amends that
notice to include two more columns containing about 6,100 sq.ft, of asbestos
Insulation and an undetermined amount of process piping insulation. We expect
to complete removal of Insulation from all columns by June 27, 1983, and we will
provide you additional information on the piping when we have it.
We have a serious corrosion problem and part of our plant is shut
down until we can determine the extent of the damage and suitable remedial actions.
All asbestos will be disposed of on the Du Pont Victoria Plant in a
disposal area registered by the Texas Department of Water Resources (Solid Waste Registration 30079). All asbestos will be placed in sealed plastic bags at the point of removal and kept sealed during movement and disposal on site.
?leaan contact me at (512)572-1277 if there are any questions or if you need additional information.
1 Very Truly Yours,
DUP 0821243
CC: P. Rutchlnski
TDW& - Corpus
W. T. Palmer TACB - Corpus
A. H. Nlckolaus Senior Environmental
Control Consultant Engineering Division
SETTER THINGS VOR BETTER LIVING . . . THROUGH CHEMISTRV
a
-*
E. I. du Pont de Nemours & Company
Victoria Plant
P. O. BOX 2626 Victoria, Texas 77901
PETROCHEMICALS DEPARTMENT
bcc: 1) J. R. Cooper - Wilm
2) G. J. Hollod
0. G. Jentsch - 570
W. P. Ledet
- 570
J. D. Billings - ACR
2) J. 0. Walling
1) B. Huanta
-
2) M. K. Ahlstrom
V. P. File 60-70
3
May 31. 1983
MR. BILL STEWART, P.E. (2) EXECUTIVE DIRECTOR TEXAS AIR CONTROL B0AR0 6330 HIGHWAY 290 EAST' AUSTIN, TEXAS 78723
ATTENTION: K. A. LANGLEY COMPLIANCE
RE: NESHAPS Notifications of Emergency Asbestos Removal Du Pont, Victoria County, Texas
Dear Hr. Stewart:
On May 28, 1983, E. I. du Pont de Nemours & Co. (Inc.), the owner, whose address is P. 0. Box 2626, Victoria, Texas 77902, started removal of approximately 4600 square feet of asbestos containing insulation from five distillation columns in our Adipic Acid plant (TACB Permit R-810) under emergency conditions. Removal should be complete by June 10, 1983.
-
Removal under emergency conditions became necessary when inspection of some visually deteriorating insulation revealed stress corrosion cracking of the stainless steel columns underneath. This insulation, installed nearly twenty years ago, contains enough chlorides to cause stress corrosion cracking if water gets to the interface between`it and the stainless. We try to water proof the Insulation and we periodically cut windows to inspect, but when we do find corrosion, immediate removal is generally necessary for safety reasons. After repair, these columns will be recovered with non-asbestos Insulation.
The removal job is being supervised by Du Pont personnel to Insure that proper safeguards, work practices, and disposal procedures are followed. All asbestos is being "wetted" before handling. Respiratory protection is . being worn as required. Proper hygiene and p/otectlve clothing is being worn. * Caution signs are appropriately placed to alert workers to the presence of asbestos and that necessary precautions must be taken to enter the area.
I
' ICTTC^TMINOft worn mr*
-
, u.- >-*. .t'ti'CJ&J'
DUP 0821244
Hr. Bill Stewart, P.E May 31, 1983
Page 2
All asbestos will be disposed of on the Du Pont Victoria Plant In a disposal area registered by the Texas Department of Water Resources (Solid Waste Registration 30079). All asbestos will be placed in sealed plastic bags at the point of removal and kept sealed during movement and disposal on site.
Please contact me at (512) 572-1277 If there are any questions.
Very truly yours.
cc: H. P. Kutchinskl TDWR - Corpus
W. T. Palmer TACB - Corpus
A. H. NIckolaus Senior Environmental
Control Consultant Engineering Division
AHN/cgh
DUP 0821245
'i '2esL)ii'SPK.s`V "- w.*'