low pressure steam or hot water
450,000 to 5,050,000 Btuh
No. 5 or lighter oil ... gas...
combination gas-oil
28541
This new steam generator is ideal for office and store buildings, schools, motels, hospitals, small factories, apartments and other build ings of medium size.
Intensive research, added to nearly a century of boiler experience, produced this modern Square-Heat Generator with amazing com pactness, plus highest efficiency, plus Kewanee Time-Proved structural features.
The secret of this remarkable design, which results in highest efficiency, top-quality per formance, and long dependable service, is... exceptionally high proportion of primary (direct) heating surface which is many times more efficient than secondary (indirect) heat ing surface . . . plus. . . extra large furnace volume for complete combustion, smooth starts, clean firing, quiet operation, unre stricted gas flow and low heat release.
The entire unit is listed by Underwriters' Laboratories, Inc.
THREE PASS DESIGN Assures maximum heat transfer with low stack temperature... highest operating efficiency. The large firebox with arched upright crown sheet provides thorough mixing of fuel and air... complete combustion before hot gases enter fire tubes. The second pass is rear to front through the direct fire tubes... the third from front to rear in the return tubes. Gas travel is longer and there are no refractory baffles to burn out and permit short circuiting of gases.
Copyright 1962 by American Radiator & Standard Samtary Corporation
HIGH EFFICIENCY HEATING SURFACE Primary heating surface (exposed directly to the flame) is 4 to 15 times more effective than secondary heating surface (exposed only to hot gases). The Square-Heat Generator design utilizes nearly 50% greater ratio of primary to secondary heating surface than com
petitive units. Square-Heat Generators provide MORE more effective heat transfer surfaces, and LESS less effective heat transfer surfaces.
LARGE FURNACE VOLUME For complete combustion with smooth starts . . . clean firing . . . unrestricted gas flow . . . quiet operation .. . heat release averages 50% less than competitive units.
FORCED-DRAFT OPERATION Provides ample combustion air for stub stack applications. Only a
vent to the outside is needed. Special assemblies available for high
altitude installations.
28542
MORE ENERGY PER SQUARE FOOT
OF OCCUPIED FLOOR SPACE THAN ANY OTHER COMPARABLE UNIT
This Kewanee is the most compact generator you can buy. For example, you can have 80 hp in 42.7 square feet of occupied floor space. Two principal competitive 80 hp generators require 72.7 square feet and 78.0 square feet, respectively. The illustration above shows the contrast. Head room also is minimum.
LARGE STEAM SPACE
Combined with abundant, unbroken disengaging area and ample
water content assures steady water line and a plentiful reserve of
dry steam.
; .-
TUBES ROLLER EXPANDED All tubes are secured to tube sheets by roller expander--none are welded to tube sheets.
WELDED STEEL Flange quality plate. All welded integral construction for strength and durability. Gas tight throughout.
SKID TYPE BASE Refractory filled, provides ventilation under the unit and distributes weight evenly.
INSULATED STEEL JACKET Heavy gauge steel jacket with attractive smooth enamel finish. Glass or mineral fiber insulation minimizes heat loss.
WATER HEATING COILS Standard Kewanee "Kl" (instantaneous) and "KT" (tank)) coils available for all units. Coil opening at front of boiler avoids inter ference with controls, wiring or breeching.
EASY ACCESS TO TUBES Steel flue access cover with insulation securely keyed in place pro vides easy access to flues without disturbing fuel burning equipment.
TESTED-APPROVED ASME Boiler Construction Code requirements have been followed to the last detail ... and the Kewanee name assures design and performance above and beyond any code requirements. These gener ators have Underwriters' Laboratories listing.
COMPLETELY ASSEMBLED
With burner and all accessories--may be moved in by fork truck,
hoist, or rollers. Only service connections are needed to place unit
in operation.
28543
';.'v'Cs|'
Kewanee Square-Heat Generators are available for oil, gas, or combination gas-oil firing. Each Kewanee Forced Draft Burner is custom engineered for the generator it fires, assuring long, dependable and economical service.
Two series of Kewanee Forced Draft Burners cover the entire range of boiler capacities and f =. eIs
The Kewanee KR Burner fires light oil (No. 2 CS12-48), gas, and combination gas-light oil in Units M-45 thru M-265. The oil burner is of the high pressure mechanical atomizing type, and the gas burner is of the multiple jet flame retention type. Units M-45 thru M-175 with the KR burner feature on-off operation (with low fire start on oil-fired Units M-135 thru M-175). Combustion air is regulated by a fixed position damper in addition to an adjustable primary-secondary air shutter. Units M-205 thru M-265 with the KR burner feature on-off operation with con trolled low fire start. Fuel and air supply are regulated for both high and low firing by a two position motor. This provides smooth starting and top efficiency.
The Kewanee Master Burner (Pressure Atomizing) fires light oil i No. 2 CS12-481, gas, and combination gas-light oil in Units (VI-335 thru M-505. The oil burner is of the high pressure mechanical atomizing type, and the gas burner is of the radial jet flame retention type. The Kewanee Master Burner (Air Atomizing) fires No. 5 or lighter oil, gas, and combination gas-oil in Units M-175 thru M-505. The oil burner is of the low pressure air atomizing type, and the gas burner is of the radial jet flame retention type. Units M-175 thru M-265 with the Master burner feature two-stage firing with proved low fire start. Fuel and air supply are regulated at both high and. low firing rate by a two position motor controlled by a boiler mounted pressure or temperature operating control. Units M-335 thru M-505 with the Master burner feature full modulation with proved low fire start. Fuel and air supply are regulated throughout the firing range by a modulating motor controlled by a boiler mounted pressure or tem perature modulating potentiometer
4-
28544
Dual automatic main gas valves (on units over 1000 MBh input) provide added protection. Boiler passages are purged of combustible gases before and after each firing cycle. Combustion is continuously monitored by an electronic flame safeguard.
I
CONTROL CABINET Master programming and flame safeguard relays, switching relays, motor magnetic starter (if required), numbered terminal strips, indicating lights for major operations, and fuel selector switch--all mounted and wired in a heavy-gauge steel, dustproof control cabinet mounted on the boiler unit. Wiring is ready for connection to a source of power.
AfR-OEL UNIT The air-oil unit assembly of the Master burner in cludes air compressor, oil pump, valves, belt drive, motor, and all necessary accessories to provide the fine oil atomization required for clean, efficient oil firing. A thermostatically controlled electric oil heater maintains uniform oil temperature to com pensate for varying viscosities of residual oils. The multi-louvered opposed-blade air damper provides accurately measured air supply to match fuel supply for top operating efficiency at all firing rates.
BURNER PSRINCr H fe: ,% p Exclusive design of burner firing heads provides quiet, stable combustion of gas or oil at all inputs. The intimate fuel and air mixture gives dean, effi cient firing, smooth light off, low fuel consumption, and maximum safety.
28545
K EWA N EE D s M EN S [ ON S
A--Boiler maximum width --Jacket width
B -- Length overall-- KR burner BB --Length overall --Master burner
C --Boiler length -- Jacket length
D--Boiler height --Jacket height from floor
E--Water line height F--Steam or water supply height G--Smoke outlet height H -- Steam or water supply K --Coil connection height L--Return height M --Base length --KR burner MM --Base length --Master burner N --Vent dlameter 0 --Smokebox P--Burner to boiler--KR burner PP-- Burner to boiler--Master burner R --Required tube replacement length Add 5Vs for Top Smoke Outlet
M-45 M-55 M-65
M-95 | M-115! M-135 M-155 M-175 M-205 M-235 M-265 M-335 IM-425 M-505
32 Vs 32 V? 32 V? 32 V? 37 ; 37 ' 37
37
44 44
44 , 44
54
i 54
54 1
31>/j 311/? 31V? 31V? 35V? ; 35 V? : 35V? 35 V? 42 V? 42 V? 42 Vs 42 V? 53 - 53 53
65 V? 71 % 77 V? 83 V? 77'/? ; 85 V? ! 93 102 92 101 109 ! 116
---
i. i 1
96 104 112 |119 131 1152 172
30 V? 36 V? . 42 V? 48 V? 42 V? : 50 V? ; 58 67 56 64 3i y? 37% , 43V? 49V? 43 V? 1 51V? ; 59 68 57 65
72 ; 79 73 80
91 '112 95 116
132 136
55 55 55 : 55 62 62 62 62 71 71
71 71 78 . 78 78
56 56 56 56 63 i 63 63 63 72 72
72 72 80 | 80 80
44 Vs 44 V? 44 V? 44 V? 52 52 52 52 59 V? 59 V? 59 V? 59% 64 V? ` 64 V? 64 V?
55V? 55 V? : 55 V? 55 V? 63 : 63 63 63 75 75 35 V? 35 V? 1 35 V? 35 V? 40 V? ; 40 V? 40 V? 40V? 47% 47%
75 75 83 47 V, 47% 5?
. 83 52
83 52
10 12 14 16 14 17 19 22 16 18 20 . 24 27 38 48
46 V? 46 V? 46 V? 46 V? 54 54 : 54 54 61V? 61V? 61V? : 61V? 66 V? 66 V? 66V;
6!/2 6 Vs 6V2 6 Vs 7
7
7 7 7 7 :7 7
33'/? 39 V? | 45 V? 51 V? 45 V? ' 53 % 61V? 70 59% 67% 75 82 % - - -
- - - - - - - - 89 V? 97 V? 105% , 112% 121% .142 V? 162V? 6 6 6 6 8 8 ' 8 8 10 10 10 10 16 16 18
88838 83n9
0 9 12 12 12
27 27 27 27 27
. 27 27 27 28
28 28
- _
-
- - - - - - - -- 31 31
31 31 28 28 28
33 39 4?
43 53 61 69 53 66
; 4 81 93 114 134
6 28546
R AT iNGS and D AT A
IM-45 M-55 M-65 M-75 M-95 iflfl-115 ilYl-135 M-155 M-175 M-Z05 jM-235 M-265 M-335 M-425 M-505
Rating--MBh . .
450 550 650 750 950 : 1150 1350 1550 1750 2050 2350 2650 3350 4250 5050
-- horsepower
13.4 16.4 19.4 22.4 28.4 34.4 40.3 46.3 52.3 61.2 70.0 80.0 100.0 126.9 150.8
-- steam per hour 212F
lbs 464 567 670 773 979 I 1186 1392 1598 1804 2113 2423 2732 3452 4380 5204
f-* , 'O 00
-- steam (gross)
sq ft 1875 2291 2708 3125 3958 ! 4792 5625 6458 7292 8542 9791 11042
17708 21042
-- steam (MCA net) Firing rate--gas, 1000 btu/cu ft
--oil, 140,000 btu/gal
sq ft 1410 1723 2036 2349 2976 ; 3603 4230 4855 5433 6422 7362 8302 10490 13110 15733 ----------- 1 563 688 813 938 1188 | 1438 1688 1938 2188 2563 2937 3313 4181 5312 6312 ----------- 1
4.0 4.9 5.8 6.7 8.5 I 10.3 12.1 13.8 15.6 18.3 21.0 23.6 30.0 38.0 45.0
--oil, 150,000 btu/gal Heating surface--total
sq ft
1i
14.6 17.1 19.5 22.0 27.9 34.8 41.7
63 78 92 107 127 : 154 180 209 239 275 309 343 450 562 675
-- primary
sq ft 19.0 21.1 23.2 25.4 30.8 : 34.2 37.6 41.4 47.6 51.9 55.9 59.9 86.3 100.2 112.9
Furnace volume
cu ft 8.8 10.4 12.0 13.5 17.2 20.1 23.0 26.3 32 6 37.0 41.1 45.3 72.0 88.1 103.4
Safety valve capacity--steam per hour lbs 450 550 650 750 950 ; 1150 1350 1550 1750 2050 2350 2650 3350 4250 5050
Vent diameter Supply size Return size . .
. . in 6" 6" 6" 6" 8" i 8" 8" 8" 10" 10" 10" 10" 16" 16" 18"
in 4" 4" 4" 4" 4" 1 4" 4" 4" 6"* 6"* 6"* 6"* 8"* 8"* 8''*
in 3" 3" 3" 3" 4" 1
4" 4" 4" 4" 4" 4" 4" 4" 4"
Approx, dry wt. -- KR burner -- Master burner
+150 lb. American Standard Flange.
lbs 1900 2050 2200 2350 2600 1 2950 3300 3650 4000 4450 4900 5300
lbs
ri l;
i 4600 4900 5300 5700
oo
1oo
-10.850
! M-45 ! M-55 M-65 : M-75 ! M-95 M-115 M-135 1 M-155 1 M-175 | M-205 lM-235 lM-265 1 M-335 lM-425 lM-505
Input --gas --1000 btu/cu. ft.
563 688 813 938 1188 1438 1688 : 1938 2188 j 2563 293/ +-3313 , 4181 , 5312 , 6312
--oil --140,000 btu/gal.
4.0 i 4.9 5.8 i 6.7 ; 8.5 10.3 12.1 j 13.8 T 15.6 ; 18.3 21.0 | 23.6 | 30.0 i 38 0 ; 45.0
--oil --150,000 btu/gal.
-- : - - ! - , - __ - -- 14.6 , 17.1 19.5 , 22.0 . 27.9 34 s ; 4i ;
KR BURNER--For Gas--No. 2 Oil--Combination Gas-No. 2 Oil
Fuel control--gas..................
On-Off
Low Fire Start ->i --
--oil.
On-Off
Low Fire Start
- 1-
-
Air control ....
.
Fixed
Two Position -> -- i - ! -
Programming & flame safeguard control <-
T-1A Pre-Purge and Post-Purge Timer with RA890E
->i - -
-
Gas controls--min. inlet press. -- size
6'' 6'' 6" - 6" : 6" 6" 6" , 6" ; 6 A" ' 61/?" J 6A'1 i 6 A" i - _ : _
1" r 11V' VA" 1 " 1 A" 2" r V 2" ?" 2';" - _
Motor--HP --electrical characteristics
i/3 `/a `/a : Vs ; `/a A '/a v? , % 1 : l
l , -- - --
115-60-1
->|230-60-l 208/220/240-60-3 ->: -
-- '-
MASTER BURNER--For No. 5 or Lighter Oil--Combination Gas-No. 5 or Lighter Oil -Gas Only (M-335 thru M-505)
Fuel control--gas --oil
-- - - . - ~ - - - k High-Low-Off
Modulating ->
-- '- - - ~
- '-
- <-
High-Low-Off
><- Modulating >
Air control
-- - - - - - -- - -t- Two Position
Modulating ->
Programming & flame safeguard control --
- -- - - -- - -+
Fireye FP-2
>
Gas control -- mm. inlet press --size.
Motors --Fan --HP --voltage
--- - ------
6 V?'1 6 A" 6 A" 6 A ' ; 7" 8" 8"
-- -- - -- -- -- - r . 2,, 2A" 2A" 2V?" 3" 4"
-- -----_------
3/. A.
1
1 14 2
-- -- _ _ -- "I IT"
208/220/240*60-3
>
--oil pump --press atom. --HP
--
-- voltage --
~-
-_-
-
----A AA
--
-<
230 50-1
V
-- air-oil unit--air atom. --HP
- -- - -- - -- - 1 1 1 1 1'-; 1 V. 1 A
-- voltage --
--------
208-220/240-60- 3
->
Electric preheater---watts
---
--
- - - - 2000 2000 2000 2000 3000 3000 4000
--voltage
----
- - - -^
208/220/240-60-1
->
'No. <1 and No. 5 oil on ly --requires separate fused disconnect switch by others
28547
7
KEWANEE
STANDARD AND OPTIONAL EQUIPMENT
STANDARD EQUIPMENT
OPTIONAL EQUIPMENT
ALL UNITS
1. Three-Pass ASME Code Boiler 2. Refractory Filled Skid Type Base
3. Gas-Tight Insulated Front Smokebox 4. Pyrex Observation Ports (Front and Rear) 5. 2" Firetubes--Roller expanded 6. Gas-Tight Rear Smokebox with Horizontal Discharge (Rear) Vent 7. Wrap-around Insulated Steel Jacket 8. Lifting Loops (Units M-335 thru M-505)
9. Washout Plug Socket Wrench and Flue Cleaner with Handle 10. Forced Draft Operation 11. Operating Limit Control
12. Safety High Limit Control 13. Control Voltage--115 V, 60 cy, 1 ph. Includes Reduced Voltage Trans
former where required 14. Control Cabinet Including: Electronic Flame Safeguard, Programming
Control, Control Circuit Fuse, Burner Switches, indicating Lights (2), Numbered Terminal Strip, Color Coded Wiring, Engraved Name
plates, and Necessary Relays, Magnetic Starters, and Transformers 15. Listed Standard and Selected Optional Equipment Mounted, Piped,
Wired, Ready for Field Connection to Fuel, Water, Steam, and Elec tricity (Exceptions: Items shipped separately to prevent shipping damage) 16. Starting Service
1. Explosion Relief Door
2. Vertical Discharge (Top) Vent 3. Instantaneous or Tank Type Hot Water Coils 4. Flue Gas Temperature Gauge 5. Room Thermostat Control 6. Alarm Bell 7. Circuit Breaker 8. Other Than Standard Voltages 9. One Year Service Period
1 No. 767 Low Water Cut-Off 2. Kewanee Water Column (Units M-335 thru M-505) 3. Safety Valve(s) 4 Compound Steam and Vacuum Gauge 5. Water Gauge and Glass
STEAM UNITS
1. Combination Low Water Cut-Off and Pump Control 2. Combination Water Feeder, Low Water Cut-Off,
Alarm Switch
3. Second Low Water Cut-Off 4. Surface Blow-Off
and
1. No. 764 Low Water Cut-Off 2. Relief Valve(s)
3. Combination Altitude Gauge and Thermometer
w;rr WA'rE^
rr >7\ /
1. High Pressure Mechanical Atomizing Oil Burner for No. 2 Oil 2. Two-Stage Oil Pump direct connected to Burner Motor 3. Motor Horsepower and Voltage--
1/b HP. 115 V. 60 cy, 1 ph. (Units M-45 thru M-75) V? HP, 115 V, 60 cy, 1 ph. (Units M-95 thru M-155) % HP. 230 V. 60 cy. 1 ph. (Unit M-175) 1 HP, 208/220/240 V, 60 cy, 3 ph. (Units M-205 thru M-265) 4. On-Off Firing Sequence (Units M-45 thru M-115) On-Off Firing Sequence with Low Fire Start (Units M-135 thru M-i 5 Fixed Position Air Supply (Units M-45 thru M-175) Two-Position Air Supply Controlled by Modutrol Motor (Units M-205 thru M-265) 6 RA-890 Flame Safeguard with Photocell Flame Detector 7. T-1A Timer for Pre-Purge and Post-Purge Timing 8. Oil Atomizing Nozzle (Dual Nozzles on Units M-95 thru M-265) 9. Oil Solenoid Valve (Dual Valves on Units M-135 thru M-265) 10. Direct Spark Electric Ignition 11. Oil Filter 12 Factory Component and Control Check
. *\ '7 ?.
1. High Pressure Mechanical Atomizing Oil Burner for No. 2 Oil 2. Two-Stage Oil Pump Assembly with Gauge. Relief Valve, V3 HP. 230 V.
60 cy. 1 ph motor 3. Motor Horsepower and Voltage --
1 HP. 208/220/240 V 60 cy 3 ph. (Unit M-335) l*l/.*> *H4P5. 62078*/292*0*/214201V3. 1640 cy. 3 ph. (Unit M-425) 2 HP, 208/220/240 V, 60 cy. 3 ph. (Unit M-505) 4 Modulating Firing Sequence with Low Fire Start 5 Modutrol Motor with Low Fire Interlock to Control Air and Fuel Supply 6 Operating Control for Modutrol Motor (Boiler Mounted) 7 Fireye FP-2 Flame Safeguard System whh Lead Sulphide Flame Detector 3 Air Flow Safety Switch 9 Variable Capacity Oil Nozzle 10. Oil Solenoid Valve 11. Oil Metering Valve 12 Gas-Electric Ignition Assembly 13 Oil Filter 14 Factory Firetest
1. Combination Water Feeder. Low Water Cut-Off, and Alarm Switch
2. Second Low Water Cut-Off
C V^ *1. Fireye Flame Safeguard System 2 DC Voltmeter for Fireye System
3. High-Low-Off Firing Sequence (Units M-95 thru M-265) *4, Modulating Firing Sequence (Units M-135 thru M-265) 5. Manual Potentiometer for Modulating Fire Control 6. Oil Controls for FM *7. Oil Controls for FIA **8 Oil Controls for Local Code Requirements 9 Factory Firetest
1. DC Voltmeter for Fireye System 2. Manual Potentiometer 3. Direct Spark Electric Ignition 4. Oil Controls for FM 5. Oil Controls for FIA *6. Oil Controls for Local Code Requirements
28548
STANDARD equipment
OPTIONAL EQUIPMENT
AIR AroFVllZrNG:O|t^mTS;;W475;tHfM;-M'-505
1. Low Pressure Air Atomizing Oil Burner for No. 5;qf Lighter Oil ------ -
........ T.-'-DC Vqjtmeter for Fireye System
2. Air-Oil Unit Consisting of: Air Compressor. Motor, Inlet Air Filter, Air
2. Modulating Firing Sequence (UnitsM-175 thru M-265)
Pressure Regulating Valve, Check Valve. Air Prttving Safety Switch,
3. Manual Potentiometer for Modulating FireControl
Air Gauge, and Oil Pump Assembly with Gaugeand internal Relief- --------- 4r-Omit Electric Heater for No. 2 Oil
Valve
i" ........................... ~ 5.' OfFControls for FM
3. Air-Oil Unit Motor Horsepower and Voltage--
6. Oil Controls for FIA
1 HP. 208/220/240 V, 60 cy, 3 ph. (Units M-175 thru M-265)
**7. Oil Controls for Local Code Requirements
1% HP, 208/220/240 V, 60 cy, 3 ph. (Units M-335 thru M-505)
4. Blower Motor Horsepower and Voltage--
>/2 HP, 208/220/240 V, 60 cy, 3 ph. (Unit M-175)
% HP, 208/220/240 V, 60 cy, 3 ph. (Units M-205 thru M-235)
1 HP, 208/220/240 V, 60 cy, 3 ph. (Units M-265 thru M-335)
iy2 HP, 208/220/240 V. 60 cy, 3 ph. (Unit M-425)
2 HP, 208/220/240 V, 60 cy, 3 ph. (Unit M-505)
5. High-Low-Off Firing Sequence with Low Fire Start (Units M-175 thru M-265)
Modulating Firing Sequence with Low Fire Start (Units M-335 thru M-505)
6. Modutrol Motor with Low Fire Interlock For Fuel-Air Control-
Two-Position (Units M-175 thru M-265)
Modulating (Units M-335 thru M-505)
7. Operating Control for Modutrol Motor (Boiler Mounted)--
Two-Position (Units M-175 thru M-265)
Modulating (Units M-335 thru M-505)
8. Fireye FP-2 Flame Safeguard Systemwith Lead Sulphide Flame Detector
9. Air Flow Safety Switch
10. Air-Oil Nozzle
11. Oil Metering Valve
12. Air Purge Relay and Valve
13. Thermostatically Controlled Electric Oil Heater--
2.000 Watts (Units M-175 thru M-265)
3.000 Watts (Units M-335 thru M-425)
4.000 Watts (Unit M-505)
14. Gas-Electric Ignition Assembly
15. Oil Strainer
16. Factory Firetest
GAS UNO'S IVM5 thru M-265
1. Multipie-Jet Flame Retention Type Gas Burner
*1. Fireye Flame Safeguard System
2. Motor Horsepower and Voltage-- l/3 HP, 115 V, 60 cy, 1 ph. (Units M-45 thru M-75)
V2 HP, 115 V, 60 cy, 1 ph. (Units M-95 thru M-155) 3/a HP, 230 V, 60 cy, 1 ph. (Unit M-175)
1 HP, 208/220/240 V. 60 cy, 3 ph. (Units M-205 thru M-265) 3. On-Off Firing Sequence (Units M-45 thru M-175)
On-Off Firing Sequence with Low Fire Start (Units M-205 thru M-265) 4. Fixed Position Air and Fuel Supply (Units M-45 thru M-175)
Two Position Air and Fuel Supply Controlled by Modutrol Motor (Units M-205 thru M-265)
5. RA-890 Flame Safeguard with Flame Rod Flame Detector
2. DC Voltmeter for Fireye System
3. High-Low-Off Firing Sequence (Units M-95 thru M-265) *4. Modulating Firing Sequence (Units M-95 thru M-265)
5. Manual Potentiometer for Modulating Fire Control
6. Automatic Safety Gas Valve~?Units M-45 thru M-75) 7. Gas Controls for Other Than Standard Pressures 8. Gas Controls for FM
9. Gas Controls for FIA " `10. Gas Controls for Local Utility Requirements
11. Factory Firetest
6. T-1A Timer for Pre-Purge and Post-Purge Timing
7. Air Flow Safety Switch
8. UL Gas Control Group Including: Automatic Operating Gas Valve;
Automatic Safety Gas Valve (Units M-95 thru M-265 only); Gas Volume
Control Valve (Units M-205 thru M-265 only); Gas Pressure Regulator;
and Manual Gas Cock
9. Gas-Electric Ignition Assembly
10. Factory Component and Control Check
1. Radial-Jet Flame Retention Type Gas Burner 2. Motor Horsepower and Voltage--
1 HP, 208/220/240 V, 60 cy, 3 ph. (Unit M-335) iy2 HP. 208/220/240 V, 60 cy, 3 ph. (Unit M-425) 2 HP, 208/220/240 V, 60 cy. 3 ph. (Unit M-505) 3. Modulating Firing Sequence with Low Fire Start
4. Modutrol Motor with Low Fire Interlock to Control Air and Fuel Supply 5. Operating Control for Modutrol Motor (Boiler Mounted) 6. Fireye FP-2 Flame Safeguard System with Lead Sulphide Flame Detector 7. Air Flow Safety Switch 8. UL Gas Control Group Including: Automatic Operating Gas Valve;
Automatic Safety Gas Valve; Gas Volume Control Va Ive; Gas Pressure Regulator; Gas Pressure Gauge; and Manual Gas Cock 9. Gas-Electric Ignition Assembly 10. Factory Firetest1 2
v- - 50S
1. DC Voltmeter for Fireye System 2. Manual Potentiometer 3 Gas Controls for Other Than Standard Pressures 4. Gas Controls for FM 5 Gas Controls for FIA '6 Gas Controls for Local Utility Requirements
1 Manual Fuel Changeover Switch 2 Standard Equipment Listed Above by Unit Size tor Each Fuel 3. Voltage. Flame Safeguard System, and Firing Sequence for Combi
nation Unit Same as Listed Above for Oil Firing
*Requires Special Control Cabinet
1 Automatic Fuel Changeover Switch
? Optional Equipment as Listed Above by Unit Size and Fuel
**On Special Application Only
28549
9
KEWANEE
SQUARE-HEAT
-OH A LI UNITS A* 45 THHO -'4-505
The contractor shall furnish and install
Model No.
Square-Heat Generator(s) for (No. (2) (4) (5) oil),
(gas), (combination gas-No. (2) (4) (5) oil) firing. The unit(s)
shall be three-pass compact firebox design with arched up
right crown sheet and two passes of firetubes, and constructed
in accordance with the ASME Code for (15 lbs. steam) (30 lbs.
water).
Umt(s) shall have not less than
total square feet of
waterside heating surface including a minimum of
square feet of primary or direct heating surface.
Unit(s) shall contain not less than
cubic feet of
furnace volume and shall have a gross output rating of not less
than
MBh. Heat release shall not exceed 74,000
Btu per cubic foot of furnace volume.
Normal water line of unit(s) shall not exceed
inches.
A pyrex observation port shall be provided at the rear of the
firebox. Front flue access cover, with refractory securely keyed
in place and of a size permitting easy access to all fire tubes,
shall be mounted on a gas-tight, insulated front smokebox.
Gas-tight rear smokebox shall be provided with a (rear) (top)
outlet.
Unit(s) shall be provided with a wrap-around steel jacket with glass or mineral fiber insulation and smooth enamel finish. All tubes shall be set with a roller expander at each end. No welding of tubes to the tube sheets nor use of refractory baf fling to provide the second or third pass will be permitted.
Unit(s) shall be assembled and wired, with burner, controls, trim, insulated steel jacket, and refractory filled skid type base installed at the factory.
Fuel burning equipment shall be forced draft type: Factory assembled, wired, mounted, and tested. The entire unit shall bear the Underwriters' Laboratories label and shall be ready for field connection to power and fuel supply. Equipment shall include forced draft fan with air damper; dual high limit con trols: flame sensing device; and control cabinet containing electronic flame safeguard and programming timer, burner switch, control circuit fuse, two indicating lights for ma|or operations, numbered terminal strips, color-coded wiring, en graved nameplates, and necessary relays, starters and switches for automatic operation.
All motors shall be for
volts.
cycle,
phase operation. Controls shall be 115 volt, 60
cycle, single phase. Magnetic motor starters with thermal over
load protection and a step-down control circuit transformer
shall be provided in the control cabinet when other than 115
volt motors are specified.
Fuel burning equipment shall be set and ad|usted by a factory
authorized representative to burn
G.P.H. of No. (2)
(4) (5) oil (and) (or)
C.F.H. of
Btu/cu.
ft. (natural) (manufactured) (L.P.) gas having a
sp gr. with
inches w.c. pressure at inlet of burner
manual gas cock. Unit efficiency, based on flue gas analysis,
shall be not less than 80%. NOTE- Specify job altitude if over
2.500 ft. above sea level. Owner's representative shall be pres
ent to receive instructions in care and maintenance of the unit at
the time it is started up by ttie service representative. Contrac
tor shall provide a free service period of 90 days after start-up.
NOTE Select applicable paragraphs below according to fuel and unit size The following equipment conforms to UL requirements Specify additional controls if FM or FIA insured, or subject to special utility requirements
"C:k PRESSURE !m rnyg-ijHm 'j:: p.Yf'S v..-i5 ' V 175
Oil burner shall be of the high pressure mechanical atomizing type for No. 2 oil, with atwo-stage oil pump direct connected to the blower motor. Burner shall include oil atomizing nozzles, oil solenoid valves; 10,000 volt ignition transformer; T-1A Timer for pre-purge and post-purge; RA-890E flame safeguard with photocell flame detector; and all necessary controls for "onoff" type of operation. Air control shall be by fixed position air inlet damper and adjustable primary-secondary air shutter.
"OK PRESSURE. ATOMIZING O!L UN>7S iv.-ZOS r-md; % 255
Oil burner shall be of the high pressure mechanical atomizing type for No. 2 oil, with a two-stage oil pump direct connected to the blower motor. Burner shall include dual oil atomizing nozzles; dual oil solenoid valves; 10,000 volt ignition trans former; T-1A Timer for pre-purge and post-purge; RA-890E flame safeguard with photocell flame detector; and all necessary controls and linkage for "on-off" type of operation with con trolled low fire start. Fuel-air control shall provide two-position regulation of the air inlet damper and the high fire oil solenoid valve by means of a modutrol motor.
FOR PRESSURE ATOMIZING OIL Ijfv'.TS iVi-335 ERE, 54-505
Oil burner shall be of the high pressure mechanical atomizing type for No. 2 oil, with a two-stage oil pump assembly with in ternal relief valve mounted on the boiler base. Burner shall in clude variable-flow oil atomizing nozzle; oil solenoid valve; oil metering valve; gas-electric ignition assembly with ringtype pilot burner, 6,000 volt ignition transformer, automatic gas valve, gas pressure regulator, and manual gas cock; air flow safety switch; Fireye FP-2 flame safeguard system with lead sulphide flame detector; low fire interlock; and all necessary controls and linkage for modulated firmg with proved low fire start. Fuel-air control shall provide modulated regulation of the air damper and the oil metering valve by means of a modutrol motor.
Oil burner shall be of the low pressure air atomizing type for No. 5 or lighter oil with an air-oil unit consisting of air compres sor, motor, air pressure regulating valve, inlet air filter, check valve, air proving safety switch, air gauge, oil pump assembly, and relief valve mounted on the boiler base. Burner shall in clude air-oil atomizing nozzle: oil solenoid valve; oil metering valve, air purge relay and valve, thermostatically controlled electric heater (omit for No. 2 oil): gas-electric ignition assembly consisting of a ring-type pilot burner; 6,000 volt ignition trans former, automatic gas valve, gas pressure regulator, and man ual gas cock; air flow safety switch; Fireye FP-2 flame safe guard with lead sulphide flame detector; low fire interlock, and all necessary controls and linkages for (modulated) (twoposition) firing with proved low fire start. Fuel-air control shall provide (modulated) (two-position) regulation of the air damper and the oil metering valve by means of a modutrol motor.
Gas burner shall be of the multiple-jet flame retention type in cluding a main gas control group consisting of an automatic diaphragm gas valve, automatic safety gas valve on inputs over 1,000 MBh, gas pressure regulator and manual gas cock: gaselectric ignition assembly consisting of a 6.000 volt ignition transformer, automatic gas valve, gas pressure regulator and manual gas cock, air-flow safety switch. T-1A Timer for pre purge and post-purge. RA-390E flame safeguard with flame rod flame detector, and all necessary controls for "on-off" type of operation. Aircontrol shall be by fixed position air inlet damper and ad|ustable primary-secondary air shutter
lO 28550
TYPICAL SQUARE-HEAT GENERATOR SPECIFICATIONS
"OR GAS -JN'TS M-205 TMRC -265
Gas burner shall be of the multiple-jet flame retention type, in cluding a main gas control group consisting of an automatic diaphragm gas valve, automatic safety gas valve, gas volume control valve, gas pressure regulator, and manual gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer; automatic gas valve, gas pressure regulator, and manual gas cock, air-flow safety switch; T-1A Timer for pre purge and post-purge; RA-890E flame safeguard with flame rod flame detector; and all necessary controls and linkage for "onoff" type of operation with controlled low fire start. Fuel-air control shall provide two-position regulation of the air inlet damper and the gas volume control valve by means of a modutrol motor.
"OR GAS UNITS Vi 335
V 505
Gas burner shall be of the radial-jet flame retention type in cluding a main gas control group consisting of an automatic motorized gas valve, automatic safety gas valve, gas volume control valve, gas pressure regulator, gas gauge, and manual gas cock; gas-electric ignition assembly consisting of a ringtype pilot burner, 6,000 volt ignition transformer, automatic gas valve, gas pressure regulator, and manual gas cock; air flow safety switch; Fireye FP-2 flame safeguard with lead sulphide flame detector; low fire interlock; and all necessary controls and linkage for full modulated firing with proved low fire start. Fuel-air control shall provide modulated regulation of the air damper and the gas volume control valve by means of a modutrol motor.
hOR COMBINATION uAS-;:ncS3<;t'-.fc ,-Tr< 0!i. . !M7S hr! 35 " t-tr.m v ) ?5
: ; j-
Gas-oil burner shall consist of a combination multiple-jet flame retention type gas burnerand a high pressure mechanical atom izing oil burner for No. 2 oil, including all necessary controls for "on-off" type of operation. Gas controls shall include a main gas control group consisting of an automatic diaphragm gas valve, automatic safety gas valve on inputs over 1,000 MBh, gas pressure regulator, and manual gas cock; gas-electric ignition assembly consisting of a 6,000 volt ignition transformer, auto matic gas valve, gas pressure regulator, and manual gas cock; and flame rod flame detector. Oil controls shall include a twostage oil pump direct connected to the blower motor; oil atom izing nozzles; oil solenoid valves; 10,000 volt ignition trans former; and photocell flame detector. Controls for both fuels shall include T-1A Timer for pre-purge and post-purge; RA-890E flame safeguard; and air-flow safety switch. Air control shall be by fixed position air inlet damper and adjustable primary secondary air shutter. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector switch in the control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned.
-i- :>. ?S5
Gas-oil burner shall consist of a combination multiple-jet flame retention type gas burner and high pressure mechanical atom izing oil burner for No. 2 oil, including all necessary controls for "on-off" type of operation with controlled low fire start Gas controls shall include a main gas control group consisting of an automatic diaphragm gas valve, an automatic safety gas valve, gas volume control valve, gas pressure regulator, and manual gas cock; gas-electnc ignition assembly consisting of a 6,000volt ignition transformer, automatic gas valve, gas pressure regulator, and manual gas cock: and flame rod flame detector Oil controls shall include a two-stage oil pump direct connected
to the blower motor; dual oil atomizing nozzles; dual oil sole noid valves; 10,000 volt ignition transformer; and photocell flame detector. Controls for both fuels shall include T-1A Timer for pre-purge and post-purge; RA-890E flame safeguard; and air-flow safety switch. Fuel-aircontrol shall provide two-position regulation of the air inlet damper, the gas volume control valve, the high fire oil solenoid valve by means of a modutrol motor. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector switch in the control cabi net. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned.
Gas-oil burner shall consist of a combination radial-jet flame retention type gas burner and high pressure mechanical atom izing oil burner for No. 2 oil, including all necessary controls for modulated type of operation with proved low fire start. Gas con trols shall include a main gas control group consisting of an automatic motorized gas valve, an automatic safety gas valve, gas volume control valve, gas pressure regulator, gas gauge, and manual gas cock; Oil controls shall include a two-stage oil pump assembly with internal relief valve; variable-flow oil atomizing nozzle; oil solenoid valve; oil metering valve. Con trols for both fuels shall include Fireye FP-2 flame safeguard with lead sulphide flame detector; air flow safety switch, low fire interlock; and gas-electric ignition assembly consisting of a ring-type pilot burner, 6,000 volt ignition transformer, auto matic gas valve, gas pressure regulator, and manual gas cock. Fuel-air control shall provide modulated regulation of the air damper, the gas volume control valve, and the oil metering valve by means of a modutrol motor. Changeover from one fuel to the other shall be accomplished by means of a manual fuel selector switch in the control cabinet. No changes in linkage, burner position, or mechanical adjustment shall be necessary when changing fuels. Ttie fuel selector switch shall provide, through the combustion control relay, the proper ignition timing for the fuel being burned.
,v...I./5 - t
50/
Gas-oil burner shall consist of a combination radial-jet flame retention type gas burner and low pressure air atomizing oil burner for No. 5 or lighter oil with all necessary controls for (modulated) (two-position) type of operation with proved low fire start. Gas controls shall include a main gas control group consisting of an automatic motorized gas valve, automatic safety gas valve, gas volume control valve, gas pressure regu lator, gas gauge, and manual gas cock. Oil controls shall in clude an air-oil unit consisting of an air compressor, motor, air pressure regulating valve, inlet air filter, check valve, air prov ing safety switch, airgauge, oil pump assembly and relief valve, air-oil atomizing nozzle; oil solenoid valve, oil metering valve, air purge relay and valve; thermostatically controlled electric oil heater (omit for No. 2 oil). Controls for both fuels shall include Fireye FP-2 flame safeguard with lead sulphide flame detector, air flow safety switch: low fire interlock: and gas-electric ignition
assembly consisting of a ring-type pilot burner. 6,000 volt igni tion transformer, automatic gas valve, gas pressure regulator, and manual gas cock. Fuel-air control shall provide (modulated) (two-position) regulation of the an damper, the gas volume con trol valve, and the oil metering valve by means of a modutrol motor Changeover from one fuel to the other shall be accom plished by means of a manual fuel selector switch in the control cabinet. No changes in linkage burner position, or mechamcal adjustment shall be necessary when changing fuels. The fuel selector switch shall provide, through the combustion control relay, proper ignition timing for the fuel being burned.
28551
11
t'j'id VQm t-r OW. - . 'J
American-Standard Industrial Division offers all the major components for air handling and air conditioning. You can look to one company for your total requirements for systems of any size or degree of complexity . . . whether you need boilers, roof ventilators, package units, multi-zone
air conditioners, tans, centrifugal refrigerating machines, water chillers, or dust collectors. You'd be surprised at the convenience. You talk to prod uct specialists who speak your language. You have one source responsible for quality and perform; ance in equipment designed and manufactured to work together.
Experienced sales engineering and service facilities in all principal cities assure each Kewanee owner of proper application and prompt, efficient service for complete and continued satisfaction.
The owner of a new Kewanee Square-Heat Generator receives Starting Service which consists of the initial startup of the unit, checking the general operation of the unit, making adjustments required by local job conditions, instructing the operator in proper operating and maintenance procedures, and service for a period of 90 days after startup.