CHAPTER 23
.
, - 1946 Guide
drops in pressure per 100 ft of equivalent length of run. The pipe is assumed to be well reamed and without unusual or noticeable defects.
Table 4 may be used for sizing piping for steam heating systems by pre-determining the allowable or desired pressure drop per 100 equivalent ; feet of run and reading from the column for that particular pressure drop. This applies to all steam mains on both one-pipe and two-pipe systems, vapor systems, and vacuum systems. Columns B to G, inclusive, are used where the steam and condensation flow in the same direction, while Columns H and I are for cases where the steam and condensation flow in opposite directions, as in risers and runouts that are not dripped. Columns J, K, and L are for one-pipe systems and cover riser, radiator valve and vertical connection sizes, and radiator and runout sizes, all of which are , based on the critical velocities of the steam to permit the counter flow of condensation without noise.
Return piping may be sized with the aid of Tables 5 and 6 where pipe capacities for wet, dry, and vacuum return lines are shown for the pres sure drops per 100 ft corresponding to the drops in Table 4. It is cus tomary to use the same pressure drop on both the steam and return sides of .a system.
Example 2. What pressure drop should be used for- the steam piping of a system if the measured length of the longest run is 500 ft and the initial pressure is not to -be over
2-psi gage?
Solution.; It will be assumed, if the measured length of the longest run is 500 ft, that
-when the allowance for fittings is added the equivalent length of run will not exceed
1,000 ft. Then, with the pressure drop, not oyer one half of the initial pressure, the drop
could be 1 psi or less. With a pressure drop of 1 psi and a length of run of 1,000 ft, the*
drop per 100 ft would be Ho psi, while if the total drop were 2 psi, the drop per 100 ft
. would be Ho psi. In the first instance the pipe could be sized according to Column D for
^6 psi per 100 ft, and in the second case, the pipe could be sized according to Column C
for H4 psi- 0 completion of the sizing, the drop could be checked by taking the longest
line and actually calculating the equivalent length of run from the pipe sizes determined.
If the calculated drop is less than that assumed, the pipe size is all right; if it is more, it is
-probable that there are an unusual number of fittings involved, and either the lines must
be straightened or the column for the next lower drop must be used and the lines resized.
Ordinarily resizing will be unnecessary.
'-
PIPE SIZING FOR INDIRECT HEATING UNITS
Pipe connections and mains for indirect heating units are sized in a manner similar to radiators, but the equivalent direct radiation must be
ascertained for each row of heating unit stacks and then must be divided into the number of stacks constituting that row and into the number of connections to each stack.
c r t>
Q X 60 X (tl -- <e) 55.2 X 240
Q X (f| - t*) 220.8
0)
where v
.
EDR = equivalent direct radiation, square feet. Q volume of air, cubic feet per minute. te -- the temperature of the air entering the* row of heating units under con sideration, Fahrenheit degrees. t\ = the temperature of the air leaving the row of heating units under considera tion, Fahrenheit degrees. 60 = the number of minutes in one hour.
55.2 = the number of cubic feet of air heated 1 Fahrenheit degree by 1 Btu. 240 = Btu equivalent of 1 sq ft of EDR.
Steam Heating Systems and Piping
419 .
Example 8. Assume that a. 3-row heating unit shown in this chapter in Fig. 3$ is handling 50,000 cfm of air and that the rise.in the first row-is from 0 to 40 F, in the second row from 40 to 65 F, and in the third row from 65 to 80 F. What is the load in.EDR on each supply and return connection?
Solution. For row 1, R = 50,000 X (40 - 0) = 9058 sq ft. 220.8 -
For row 2,
50,000 X (65 - 40)
/ 220.8
5661 sq ft.
For row 3,
50,000 X (80 - 65) = 3397 sq ft. 220.8
Each row of heating units consists of four stacks and.each stack has two connections so that the load on each stack and each connection of the stack is as follows:
Row
Total Load (EDR)
Stack Load* (EDR)
Connection LoAob (EDR)
i
9058
2265
2265 or 1132
2
5661'
1415
1415 or 708
3 " 3397
849
849 or 425
"One quarter of total row load. bOne half of stack load if two steam connections are made: otherwise, same as stack load.
The pipe sizes would then be based on the length of the run and the pressure drop desired, as in the case of radiators. It generally is considered desirable to place the in direct heating units on a separate system and not on supply or return lines connected to the general heating system.
Most manufacturers of heating coils how publish condensing capacities of their coils for all common operating conditions in pounds of steam per hour per square foot of face, area (or free area for some designs). These rates may be used in connection with Tables 4 and 6 to size the piping.
GRAVITY ONE-PIPE AIR-VENT SYSTEM
This system is the most common of all methods of steam heating, especially for small size installations, due largely to its low cost and simplicity.
The downward pitch of a one-pipe air-vent system is indicated in Fig. 2. Low points and ends of steam mains pitched down from the boiler should be dripped. All drips should be sealed below water line before connecting together^ In the risers and radiator connections, steam and condensation flow in opposite directions. In long steam mains it flows in the same direction as the steam arid is removed from the main through the drip. Short mains may'be arranged for the condensate to flow in a direction opposite the steam by sizing them so the critical velocity is not . exceeded. It is customary to drip the heel of each riser in buildings of several stories to avoid counter-flow of the steam and condensate in the riser, runout. In buildings of one or two stories the condensate is returned to the steam main instead of being dripped. Both types of risers are shown in Fig. 2, and riser connections are shown in Figs. 3 and 4. A . typical overhead down-feed system' is illustrated in Fig. 5. While wet-