CHAPTER 56
1959 Guide
perature at which the lime, magnesia, etc., collect on hot sur faces, varies with the character and proportions of the solids, but generally such deposits are not a serious trouble below HOF.
Direct-Fired Water Heaters
Coal-burning, direct-fired water heaters may be constructed of cored cast-iron sections, or of steel. In some cases the ex ternal appearance of the cast-iron sections is the same as in hpAting boilers, but internally the cores are changed to en able the sections to withstand the city water pressure. In small capacity water heaters, efficiency is not considered so important as low first cost and ability to maintain a fire at a low rate of combustion, and consequently, such heaters are generally built with a dry section or firebrick lining at the base of the firepot to prevent too much chilling of the fuel. While mud and scale will eventually clog the waterways of any direct-fired heater, increased life may be obtained by providing a three-way cock in the return line between the heater and the bottom of the storage tank, so that water can be blown through the heater or the tank separately, at full line pressure, to clean out loose sediment. Cleanout openings in the bottom of the heater are advantageous, if used by op erators of water heaters for periodic cleaning out of sedi ment.
Oil-burning, direct-fired water heaters usually are of steel, and operate with higher flame temperature and better effi ciency than commensurate sized coal-burning heaters. As they have the same tendency as coal boilers to accumulate lime deposits, the water passages should be large in crosssection and accessible for periodic cleaning.
Gas-burning, direct-fired water beaters may be of the instantaneous or storage type. Instantaneous heaters are generally constructed of spiral water tubes of copper, around . which the products of combustion circulate upward from high capacity burners. Storage-type heaters may include in one unit an insulated storage tank, a combustion chamber, flues, burner equipment, and controls, or may consist of a separate storage tank and external direct-fired water heater, which may be a so-called side-arm heater for small capacity, or a gas-fired boiler for larger capacity. Gas boilers used for direct hot water supply must be able to withstand the city water operating pressure. While direct-fired gas heaters are used generally for residences and small installations of 100 gal storage capacity or less, indirect heaters are recommended for larger installations.
Chimney connections for all direct-fired, fuel-burning wa ter heaters are an important consideration. Refer to Chapter 36.
Electric Water Heaters
Electric water heaters for hot water service in residences and commercial buildings are predominantly of the automatic storage type. These generally have a cylindrical tAnk mounted vertically, with a primary electric heating element or re sistor near the bottom and a secondary unit located within the upper one-quarter of the tank. Water heaters of single heating-unit type have an element only at the bottom. The first cost of automatic electric heaters is somewhat higher than that of fuel-fired types, owing to the need for larger tank storage to compensate for the limitation of recovery rate, since for economical electric service the connected load should be kept low. Large tank capacity is necessary also with off-peak operation, where there are low electric rates .for this class of service.
Table 11 .... Standard Rated Capacities of Electric Water Heaters
Tank Six* GaOon*
Nominal
Rang*
Bated Input, Wottj
Two-Unit Hooter Primary Secondary
Single-Unit Heater
30
30 to 35
600 1000
1500
40
35 to 45
750 1250
2000
52
45 to 55
1000.
1500
2500
66
55 to 70
1250 ' 2000
3000
80
70 to 90
1500
2500
4000
no 120 140'
90 to 115 115 to 135 135 to 175
2000 2500 3000
3000 4000 4000
Instantaneous heaters are used in special cases only, be cause of the high electric power input required, for example, 15 kw to deliver 1 gpm with 100 deg temperature rise.
Capacities of household automatic storage-type water heaters, as partially standardized within the electrical in dustry, range from 30 to 140 gal nominal tank capacity with input 1600 to 7000 watts. Wattage input, ratings of two-unit heaters are based on approximately 30 watts per gallon of tAnk capacity for the secondary unit and 20 watts for the primary unit. Single-unit heaters have tank sizes up to &) gal with an input of 4000 watts, the ratings being based on 50 watts per gallon. The schedule of heater capacities shown in ASA Standard C72.1-1949 is reproduced in Table 11.
The wattages listed in Table 11 are minimum recommended values for continuous service. Some departure from the standardized watts-per-galion ratios is to be expected, as experience indicates that increased hot water use with auto matic laundry machines and dishwashers may call for larger heating units than have heretofore been found desirable. With off-peak operation the watts-per-galion ratio likewise must be raised.
Rated voltage for water heaters is 240 volts, with a range 220 volts minimum to 248 volts minimum, but specified test performance is required to be met only at the 236 volts taken as normal design voltage. Thermostats controlling the heating units are normally set for 150 F, with upper limit of adjustment range of 170 to ISO F.
Heating units are of three general types, all of which give approximately the same service efficiency if selected to suit the operating conditions, as follows:
1. Immersion element, inserted horizontally through a
. threaded or flanged opening in side of tank:
..
2. Strap-on unit, externally mounted directly against the tank
shell and held in close contact by a band or strap encircling the tank.
3. Side-arm or outside circulation unit, consisting of a vertical cylindrical housing or heat exchanger which contains an
immersion heating element, connected by pipes into top
and bottom of the storage tank.
For the third type, which is less commonly used, thermo stats separate from the heating units are mounted within the storage tank.
A fourth type of heater, applied only in exceptional cases and for large installations with alternating current, employs the water itself as a resistor in which electrodes are im-
Wfltfii' Services
mersed. Close temperature regulation and compensation for the effect of variable amount and composition of solids and gflfipg in the water are difficult to obtain with small un attended heaters of this kind. The electrode type of con struction has in the past been used also for generating steam in so-called electric boilers, mainly for industrial plants; however, in only few instances today is electric energy ob tainable at cost low enough to make it competitive with fuelfired boilers for steam production.
Tanks of electric heaters are regularly constructed to with stand a 300 psig hydrostatic test pressure and are rated for a safe working pressure of 127.5 psig. Materials in contact with the water are selected to resist corrosion caused by solid and gaseous impurities occurring in some locations. It may be desirable also to provide sacrificial metal anodes of mag nesium, tine, or alloys to protect the tank and its piping connections. A safety relief valve of pressure-actuated type must be included; it may optionally be actuated also by internal temperature. A heat trap at the hot water outlet, if not provided by manufacturer within or outside the tank shell and inside the insulated jacket, may be placed in the ex ternal piping. The trap consists of vertical pipe at least 6 in. long having downward flow, to retard circulation of hot water within the distribution piping system under standby condi
tions. Occasionally, an uninsulated tempering tank is installed
ahead of an electric water heater, enabling the cold inlet water to absorb beat from the basement or room air--if conditions are such that objectionable sweating does not occur. The practice of connecting a tempering tank with a firebox coil, so that the electric heater furnishes heat only when there is deficiency from the boiler or furnace, is not recommended.
Delivery performance efficiency of heaters meeting the electrical-industry standard 24-hour operation test is 90 per cent minimum, which allows 10 percent for thermal loss through the jacket insulation. In service, the quantity of wa ter withdrawn from an automatic storage heater has con siderable influence on overall efficiency. With increasing quantities, service efficiency rises and approaches the upper limit fixed solely by the jacket thermal loss; on the other hand, if little or no water is drawn, efficiency approaches zero since no useful work is done. Hence oversiting a water heater by having too large a tank impairs the service efficiency. Ex cessive heating-unit wattage causes undesirably high electric demand. Undersizing of heaters obviously results in inade quate and unsatisfactory hot water service.
757
Selection of electric heater capacity for residences is made by reference to rating tables which take into account the number of oceupants, number of bathrooms or plumbing fixtures, and presence of appliances such as laundry, equip ment, dishwashers, and the like. Information of this kind is given in Tables 2, 8, 9 and 10 and in design manuals issued by the electric utility industry and by beater manufacturers. For commercial applications, the hourly hot water require ments must be analyzed and the best combination of tank capacity and heating element rating determined, with due consideration of electric power demand created in relation to the user's other electric demands.
A common type of electric service for water heating is the off-peak service under which the charge for energy consumed during designated hours is lower than for nonnal or unre stricted service. With this system, the operation of heaters is confined to such hourly intervals during the 24 hours as will (a) avoid creating peak electrical demands by the custo mer in excess of the demand resulting from the customer's other uses of electricity, or (6) keep the water heating load off the electric utility system during peak hours. In general, Case (a) occurs where rate schedules contain a demand charge component, and Case (6) where a special low rate applies to off-peak consumption. Water heater circuits are controlled with relays actuated by an electric-clock mecha nism or by a carrier-current impulse impressed at suitable intervals on the electric distribution system, or by an auto matic load-limiting type of control.
For general information on automatic control see Chapter 43.
One arrangement of domestic hot water heater for off-peak .service, shown in Fig. 8, has the lower heating unit under control of an.off-peak switch. Upper unit is connected di rectly to the line, so that if the reserve of hot water becomes depleted, the top thermostat brings its heating unit into op eration only until the upper .portion (usually about 25 per cent) of tank contents reaches the thermostat temperature setting. .
Indirect Water Heaters
In the indirect method, either steam or hot water is used for heating the water. With steam, the water to be heated is preferably circulated around the outside of the steam tubes which are submerged within a tank. A typical indirect heater using steam is shown in Fig. 9. The coils usually are of cop per, and are U-shaped to permit expansion and contraction. The shell may be of steel, with a protective coating or with a special inside protective lining, or may be of copper or cop per alloy. Where straight heating tubes are used, one end of the tube is usually expanded into a floating head to take
Fig. 8 .... Domestic Hot Water Heater for Off-Peak Service