Document 2j3LrDJo2Yp9pm13GNK2V23X5
This is the proposed final version of our Asbestos Waste Disposal program. Please look it over and let me know by August 15 if anything should be changed.
Brooks
ARO 017728
-V THIS COPY FOR J. LEMEZIS
' i
1 T- -
FROM E. B. PARKER
. ROCKDALE WORKS
-
^
TO MEMORANDUM
August 6, 1975
RE: ASBESTOS WASTE DISPOSAL CONTROL
Asbestos products at Rockdale Include:
ITEM
.1 5/8" Diameter Rope
2. 1" Diameter Wick 3. Asbestos Paper 4. Asbestos Millboard 5. Asbestos Gloves
. With Leather Palms
6 All-Asbestos Gloves
7. Marinite Shapes
STK. NO.
210-700-0010 210-700-0016 210-235-0001 210-410-0548 220-558-0010
220-557-0012
8. Potlinings installed before 1/1/73
9. Pipe insulation installed before change to fiberglass insulation was made
10. Pot cover insulation installed before change to fiberglass insulation was made
STATUS
Substitute found Substitute found Discontinued
Substitute being evaluated Substitute being evaluated Substitute being evaluated No fabricating done locally-all shapes precut outside Some still in service
Some still in service
Some still in service
Methods of disposal
Items 1 through 7 When items are no longer serviceable, they will be immediately deposited in a heavy plastic bag which will be inside a trash can designated for asbestos waste. This can must be Identified with signs which can be easily used stating:
CAUTION CONTAINS ASBESTOS WASTE AVOID CREATING DUST
The lids of the cans must be well fitting and be marked:
KEEP LID CLOSED
When the plastic bag Is full, it must be tied shut and deposited in a special covered Load Lugger bucket. This bucket will be located in the alley between
E3 ALCOA
r 44 cv ft
ARD 017729
f
MEMORANDUM August 6, 1975 Page Two
Building 44 and Building 34G. It will bear signs sUiii.j:
CAUTION CONTAINS ASBESTOS WASTE i AVOID CREATING DUST
KEEP LID CLOSED
When the Load Lugger is full it will be taken to a designated area of the mine, emptied, and the waste will be burled. This location will change periodically as the mining operation moves, so it will be necessary to check with the IGC Fuel Department each time a bucket is to be emptied.
Yard Service will haul the buckets to the mine.
Item 8 - Potlinings installed before 1/1/73. the insulation in these pots contains asbestos and must be handled with special precautions.
1. Thoroughly wet lining material before dumping in Building 27.
2. People in the area (West End-Building 27) during dumping must wear respirators approved for use in asbestos dust. These are 3M 8710, and Dustfoe 66.
3. Material must be loaded into railcars or hauled to the Class I disposal site while still wet in order to minimize dusting. People Involved in loading must wear approved respirators (see 2, above).
Items 9 and 10 - Pipe Insulation installed before change to fiberglass was made.
- Unless it is definitely known that Insulation to be removed is non-asbestos, the material in question must be thoroughly wetted before demolition. People involved in the demolition must wear approved respirators (Item 8, paragraph 2, above). As it is removed, it must be placed in heavy plastic containers which must be tied closed when full. The full bags will be deposited in the covered Load Lugger bucket designated for asbestos waste and located between Buildings 44 and 34G.
Item 10 - Pot cover insulation Installed before the change to fiber glass was made. The removal of these strips must be done carefully to minimize creating dust. The person removing the strips must wear an approved respirator (Item 8, paragraph 2, above) and must deposit them in plastic bags as they are taken off the covers. Full bags must be tied closed and deposited in the covered.
ARD 017730
t "a
MEMORANDUM August 6, 1975 Page Three
Load Lugger bucket specially designated for asbestos waste and located between Buildings 44 and 34G.
t
E. B. PARKER Chairman, Asbestos Committee
tm 1/1
Copies to: D. D. Mcgregor H. W. Franseen H. D. Franklin J. H. Greene C. L. Valentine J. E. Johnston A. G. Clayton W. T. Eckert J. J. Wright W. E. Davis - IGC
W. 0. Orake J. Lemezis J. D. Shinn J. 0. Tesh T. J. Randall R. E. Seymour E. C. Remaley C. G. Shlring R. L. Wiggins - IGC
f ARD 017731