Document 2Rxp14aKaz8r6Ee7xzJzdj79R

December 22, 1992 Rodney Bordelon Building 4601 cc: Terry Vavasseur Methanes Building 4601 Doyle Haney Methanes Building 4601 Bruce Miles Methanes Building 4601 Lionel London Methanes Building 4601 On December 22, 1992, the fume hoods in the Methanes Plant, Building 4601 were checked for face velocity. The Alnor Model 8925 Thermo Anemometer was used to take the face velocity measurements. These hoods have a(n) "A" classification because of the work being performed in them and/or the chemicals stored in the hoods. These hoods were checked at a(n) 18** or 14" sash opening. Fume hood #2 is restricted for use at a 14" sash opening. I would like to commend Terry Vavasseur for doing a fantastic job of keeping the lab in good working condition. He has instituted many helpful techniques and recommendations that have improved the ventilation systems in the lab. Great job! The Recommendation(S), Observation(S), and Testing Data Sheet(S) are attached to this evaluation report. The Ventilation Inventory (Appendix A), The Criteria For Hood Classification (Appendix B page 3), The Weekly Check Of Flow Measuring Device (Appendix C), and The Annual Fume Hood System Maintenance Sheet (Appendix D) are found in the Industrial Hygiene Plant Manual in Section 10-Ventilation. Please respond in writing to Industrial Hygiene within one month as to action taken or planned in regard to these recommendations. Please feel free to contact me with any questions. Thank you. Darlene S. Creel 3502-W Industrial Hygiene DONFTDFNTT Al DO 008219 Page 6 LOUISIANA DIVISION INDUSTRIAL HYOIKNF. HOOD PERFORMANCE TESTING DATA PLANT: Methanes Building 4601 HOOD I.D.: Loading Rack Hood DATE: 'November 25, 1991 TESTED BY: Darlene Creel Static Pressure Reading .30 TSI INSTRUMENTATION. Hood Face Velocity Readings at a(n) 17" (because of mechanical stop in place) Sash Opening. 1182 179 I1 16 1160 155 jl i6t> 1171 157 1 L3*l 165 160 itt> 165 1561 1 m 1601 1 (* 1581 1 Smoke Tube Observations with a(n) 17" (because mechanical stop in place) Sash Opening: ****GOOD (Air capture by hood is strong and well defined with minimal internal turbulence, and no observable smoke swirling back to hood face when person stands at hood face.) Desi ^nation (FPM) Sash Hood Opening FV Loading Rack Hood 17" 164 (FPM) FVm _ 155 Classification "A" Used the Alnor Model 8925 Thermo Anemometer. FV = Average Face Velocity FVm = Minimum Measurement FPM = Feet Per Minute CONFTDFNTTAI DO 00Q2P0 Page 5 LOUISIANA DIVISION INDUSTRIAL HYGIENE HOOD PERFORMANCE TESTING DATA PLANT: Methanes Building 4601 HOOD I D.: Lab Hood #3 DATE: December 22, 1992 TESTED BY: Darlene Creel Static Pressure Reading Smoke Tube Observations With a(n) 18" Sash Opening - MODERATE (Air capture by hood is positive but with some internal turbulence observed approaching the hood face. No smoke escaping the hood.) (FPM) (FPM) rDesignation Sash HofxiNOoenine Lab Hood #3 Ll 8" FV^^ FVm no Classification "A" Used the Alnor Model 8925 Thermo Anemometer. FV = Average Face Velocity FVm = Minimum Measurement FPM = Feet Per Minute conftdfnttai. DO 008221 Page 3 LOUISIANA DIVISION INDUSTRIAL HYGIENE HOOD PERFORMANCE TESTING DATA PLANT: Methanes Building 4601 HOOD I D.: Lab Hood #1 g - p-l DATE: December 22; +992--" TESTED BY::PPaarrfeiepaeeCi rreeeelj___ _ n Static Pressure Reading 0.55. 7 (p (J Hood Face Velocity Readings at a(n) 1|T Sash Opening. Smoke Tube ** """MODERATE (Air capture by hood is positive but with some internal turbulence observed approaching the hood face. No smoke escaping the hood.) (FPM) (FPM) Designation Sash Hood Opening FV__________ FVm Lab Hood #1 18" 158 131 Used the Alnor Model 8925 Thermo Anemometer. FV = Average Face Velocity FVm - Minimum Measurement FPM = Feet Per Minute Classification "A" CONFtOFNTTAL DO 000222 Qm C- Page 2 Observations: The laboratory hood designation, the average face velocity (FV) and minimum measurements (FVm) reported in feet per minute (FPM), and its rated classification is as follows: Designation__________Sash Hood Opening Lab Hood #1 18" Static Pressure 0.55. Smoke Observation MODERATE. (FPM) (FPM) FV__________ FVm 158 131 Classification "A" Lab Hood #2 14" Static Pressure 0.35, Smoke Observation GOOD. 146 113 "A'.' Lab Hood #3 18" Static Pressure 0.45. Smoke Observation MODERATE. 150 110 "A" Load Rack Hood 18" Static Pressure 0.35. Smoke Observation GOOD. 184 173 "A" Recommendations: 1. Lab Hood #2 is restricted at a 14" sash opening. 2. The hood(s) should be placed on the C-9 checklist for a weekly check of the flow measuring device and an annual maintenance checklist performed on it. 3. Air flow monitor(s) are installed on the hood(s) to provide the means for checking velocity before hood use. Documentation of an air flow monitor device performance is to be done once per week. An example of the documentation needed so that these hoods mav go on a two-vear survey rotation is located in the Industrial Hygiene Plant Manual in Section #10. Appendix C. Inspection, zeroing and calibration of air flow device is to be done once per year. This documentation is to be part of the Industrial Hygiene records for your department. Please forward documentation to the Plant Industrial Hygiene Contact for your plant.. CONFTDFNTTAl DO 008??3 confidential do 008224 n?[G?) no (lt>0) lUb 9? Itl (C,(i\ His 2CQ U0tb I (pb (J/>oo0o^ I *> 6 \bt} ^ 2-A^, ^ zO' cot^FTOFNTTAl DO 008225