FIRE PROTECTION
within this type of structure is on essential part of maintaining safety to bfe and prop
erty
The amount of combustible material u any one portion of the building should be limited, and the use, handling, and storage of flammable and combustible liquids should be controlled
The budding should be protected both horizontally and vertically from rapid spread of fire or smoke between sections of the building or floors and through wall open ings, elevator shafts, stair wells, ventilating ducts, and pipe lines (see Fig 33-2) Verti cal and horizontal openings should be en
closed and fire-resishve materials used in the mam structural elements
Buildings of the heavy timber construc tion type have bearing walls and bearing partitions of walls that are made of non combustible materials and have a minimum fire resistance rating of two hours with stability under fire conditions (Fig 33-3) Nonbeanng extenor walls are also noncombustible Columns, beams and girders are composed of large, heavy timbers with floors and roofs constructed of wood plank ing
This type of construction, by virtue of the size and mass of timbers and wood
CANT STRIP
WOODEN 'ALL PLATE
ANCHOREO TO WALL
SCUPPER TO AIN FIDO0
CONCRETE FLOOR ONCRETE PIER
Fig. 33-3. Components of a heovy timber budding showing floor froming ond identify ing components of a type known as semimill
Courtesy Nations) Firs Protection Allocation
33-5