Document 2RO2Yp9xzrvkmroz1ddjMOyvg
lTHE BULK TANK STORAGE Monsanto Technical Bulletin No. 0--69
.lbcrta Earkley '.csearch Library Jt. Louis r ------
'
f
y/tt/s-"
<m:.0
THE BULK TANK STORAGE
JSANTO
('ilMIH'US iY.\ST]!'S
k,,, 1.
OF PLASTICIZERS
Monsanto TocKnlcal Bulletin No. 0--69
June 1, 1950
Monsanto Chemical Company, Organic Chemicals Division, St. Louis, Mo.
I OF PLASTICIZERS
)
June 1, 1950
The purchase of plasticizers in bulk tank car quantities is becoming increasingly common for it frequently offers the possibility of effecting attractive economies and operating advantages. There are, however, certain requirements associ* ated with the handling and storage of large volumes in bulk that should be given thorough consideration.
This bulletin briefly outlines a generally applicable system for the bulk tank storage of plasticizers. Included are draw ings of typical equipment types and arrangements, and data on pertinent properties of various Monsanto plasticizers. Adaptations of the system may be made to meet the particular storage requirements of specific installations. The Monsanto technical staff is available for consultation and further detailed information.
j ; ' ' ; |
}
> >
, i
f
061POOb
l|
TOWOLDMON0039087
WATER_PCB-00023556
TABLE of CONTENTS
Page MATERIALS OF CONSTRUCTION.................................................................................. 2
STORAGE TANKS.......................................................................................................................... 2
PIPE LINES...................................................................................................................................... 2
PUMPS AND FILTERS...................................................................................................... 3
TANK CAR UNLOADING................. ............................................................................... 3
PREPARING EMPTT CAR FOR RETURN............................................................................ 3
SAFETY PRECAUTIONS.................................................................................................. 4
DRAWINGS
Vertical Storage Tank (Fig. 1)............................................................................................ Typical Run of Steam Traced Pipe (Fig. 2)................................................................... Flow Diagram From Tank Car To Storage Tank (Fig. 3).......................................... Storage Tank With Ladders and Platform (Fig. 4).......................................................
5 6 7 8
DATA ON MONSANTO PLASTICIZERS
Specific Gravity, Crystallizing Point, Flash Point................................................. Viscosity Curves Phthalate Plasticizers (Fig. 3)..................................................... Viscosity Curves Pbthalyl Glycollate Plasticizers (Fig. 6).................................. Viscosity Curves Phosphate Plasticizers (Fig. 7).....................................................
9 10 n 12
U&1500S
|
TOWOLDMON0039088 WATER_PCB-00023557
MATERIALS OF CONSTRUCTION
In general plasticizers present no great corrosion problem in tbeir storage or handling. All of the standard materials of construction such as common steels, stainless steels. Monel and nickel can be used without difficulty. Common steel is usually recommended for new units however, be cause of its lower cost. The other materials find use principally when existing equipment is converted from other services.
STORAGE TANKS
A. Construction
Figure 1 shows the construction of a typical steel storage tank.
Those recommended are vertical steel units of 15,000-23,000 gallon capacity. The top is fitted with a 24 inch flanged manhole for inspection purposes, four 2 inch flanged nozzles and one 6 inch nozzle. One 2 inch nozzle is fitted with a 2 inch iron pipe goose-neck for vent purposes and another is used as a charging inlet. The other pair of 2 inch and the 6 inch remain as spares.
There is in addition a 2 inch flanged nozzle located at approximately one-half the height in the side sheet with a 2 inch pipe extending through it to the bottom for unloading purposes.
The unit is heated when necessary by external steam coils. The coils consist of At inch to VA
inch steel pipe installed in two sections. One section is made in approximately 18 inch spirals placed directly against the bottom. The other is wrapped on 18 inch centers over about the lower third of the unit. The coil area is then shielded and insulated as shown in Figure 1. Steam pressure on the coils should be of the order of 60--110 pounds.
The tanks are equipped with a vertical ladder and guard, ascending adjacent to the outlet nozzle and a working platform with adequate guard rails is installed on the top of the unit (see Figure 4). Additional devices such as liquid level gauges and temperature regulators may be added where desirable.
B. Preparation For Use
The initial cleaning of steel storage units normally presents somewhat of a problem. Sandblasting of the inside is usually the first step to assure clean and smooth surfaces. When completed the sand is removed and the tank swabbed or mopped with the plasticizer to be stored. This should be done as promptly as possible after sandblasting to prevent re-rusting, particularly under conditions of high humidity. After mopping which removes most of the dirt, a few hundred pounds of the plasticizer is charged to the tank to complete the cleaning. By means of a pump, temporary filter and hose, the plasticizer is pumped from the tank through the filter and sprayed through the manhole down the walls of the tank. This is continued until all of the dirt is removed.
Sandblasting may be omitted if the unit is essentially free of rust though the other steps should followed as given.
PIPE LINES
Recommended piping throughout the system is 2 inch flanged steel. Garlock No. 900 or similar material is suitable for gaskets.
TOWOLDMON0039089 WATER_PCB-00023558
Heating of the lines when necessary is accomplished by tracing with a 3/8 inch or % inch paral
leled steam line carrying 100 pound steam.
Steel, plug type valves are used throughout the system.
PUMPS AND FILTERS
Self-priming, steel or bronze lined centrifugal pumps are recommended. The location and install ation should be such that both the unloading of tank cars to storage and subsequent transfer of product from storage can be accomplished with the same pump. Valves should be located on both sides of the pump to provide shut-offs necessary during repairs or repacking of the pump. As bestos type packings have proven satisfactory in most instances.
It is recommended that a cartridge type filter be installed on the suction side of the pump to re move extraneous matter and dirt, It is difficult to prevent contamination of the product by air-borne particles or tank car rust. A filter as suggested is usually effective however, in removing such from the product. A diagrammatic piping arrangement is suggested in Figure 3-
TANK CAR UNLOADING
It is recommended that tank cars be unloaded by pumping out through a standpipe placed through the dome opening. This is preferred to bottom unloading because of the lesser possibility of product loss by leakage. Air pressure is not recommended for unloading because of the possi bility of car rupture or loss of product by pipe failure.
Care should be exercised to prevent entty of moisture or other foreign matter into the car. The dome opening should be protected when the car is opened for sampling, final unloading or at any other time.
The following unloading procedure is recommended:
1. Spot the car, set brakes and block the wheels. 2. Open car vent pipe and check to insure that there is no blockage of the line. 3. Provide a protective covering and then open the dome cover. 4. Place a 2 inch standpipe in the car and connect to the suction side of the unloading pump. 5. Line up the valves to direct the product to the intended receiver and pump out contents
of car. 6. When car is empty, stop the pump, close all valves necessary and disconnect and remove
standpipe.
In very cold weather it may be necessary to warm the car contents before unloading. In such instances (following step 3 above) steam of 30--100 pounds pressure is connected to the heating coils of the car. Steam is held on the coils until the contents are heated to 30C. The remainder of the above procedure is tben followed.
PREPARING EMPTY CAR FOR RETURN
After the standpipe has been removed, close the dome cover and all other connections securely.
If the beating coils were used, all steam condensate must be removed. To do this the coils are drained and then blown dry with compressed air.
TOWOLDMON0039090 WATER_PCB-00023559
Do not permit water or other foreign matter to enter the car.
SAFETY PRECAUTIONS
Handling of plasticizers generally presents no serious safety hazards. Plasticizers are in general of low toxicity and do not give off appreciable vapors at temperatures ordinarily encountered in handling. However, before entering a tank which has contained a plasticizer it is advisable to to blow clean compressed air into the unit for a few hours. Entry can then be made wearing an air helmet as an added precaution.
Although flash points of plasticizers are rather high, open flames should be kept away from and out of storage units or tank cars. If welding for example must be done in a unit, boil out with
water containing about 1% caustic soda, flush out and rcboil with clear water. Air out the unit
as above and check the safety of the atmosphere within the unit with an explosion meter before proceeding with welding.
Plasticizers splashed into the eyes may be somewhat irritating but no serious eye injuries have been reported. The standard FIRST AID treatment for such is immediate and copious washing with water for at least 5 minutes. If discomfort persists, a physician should be consulted. If gotten on the skin, plasticizers should be washed off using soap and water. They should not of course, be taken internally.
UblSUlr!
|
TOWOLDMON0039091 WATER_PCB-00023560
15' -0'
TOWOLDMON0039092 WATER_PCB-00023561
PIPE SECTION
1/2" Dia. Pipe Steam Tracer
# 14 Wire 4'*0" c.c.
Figure 2 TYPICAL RUN OF STEAM TRACED PIPE
061SQ14
|
TOWOLDMON0039093 WATER_PCB-00023562
TOWOLDMON0039094 WATER_PCB-00023563
Plan of Ladder
061bO16
|
TOWOLDMON0039095 WATER_PCB-00023564
DATA ON MONSANTO PLASTICIZERS
SPECIFIC GRAVITY - CRYSTALLIZING POINT - FLASH POINT
Plasticizer
Specific Gravity at 25 C.
Oyttailixing Point
Flash Point
Tricresyl Phosphate
1.162 .
' Less than (-35C.)
470F.(245C.)
Dibutyl Phthalate Diethyl phthalate Dimethyl Phthalate
1.045
1.120
1.189
Less than (-35C.) Less than (--0.3C.^^
oc.
340F.(170C.) 305F. (152C.) 300F. (149C.)
Santicizer* 107
0.983
-55C. (Gel)
425F. (218C.)
Santicizer 140
1.208
Less than (-35C.)
450F. (232C.)
Saoticizer 141
1.090
--54C.(Pour Point)
435F. (224C.)
Santicizer 160
1.116
Less than (-35C.)
390F. (199C.)
Santicizer B*l6
1.097
Less than (-35C.)
390F. (199C.)
Santicizer E-15
1.180
20C.<1)
386F. (197C.)
Santicizer M-17
1.220
Less than (-35C.)
380F. (193C.)
Buparooola laadily * Rag- U. S. Pat. OH,
0615017
|
TOWOLDMON0039096 WATER_PCB-00023565
Figure 5
VISCOSITY CURVES PHTHALATE PLASTICIZERS
TEMPERATURE DECREES FAHRENHEIT
061SO18
|
TOWOLDMON0039097 WATER_PCB-00023566
Figure 6
VISCOSITY CURVES PHTHALYL GLYCOLLATE PLASTICIZERS
ASTM STANDARD VISCOSITY-TEMPERATURE CHART (D 341-39) MODIFIED
0O1501V
|
TOWOLDMON0039098 WATER_PCB-00023567
Figure 7
VISCOSITY CURVES PHOSPHATE PLASTICIZERS
TEMPERATURE DEGREES FAHRENHEIT
D-650
OfclbO^O
Primed In V3. 8. A.
B
TOWOLDMON0039099 WATER_PCB-00023568
/
Monsanto
Chemicals -Plastics
_ _ _ _ Vi_ _ _ _
For further Information about the Bulk Tank Storafo of PlastieiEors contact tho noarost Monsanto Offico.
MONSANTO CHEMICAL COMPANY
ST. LOUIS
AKRON BIRMINGHAM e BOSTON CHARLOTTE CHICAGO CINCINNATI
CLEVELAND . DETROIT HOUSTON LOS ANGELES NEW YORK
PHILADELPHIA e PORTLAND (Or..) SAN FRANCISCO e SEATTLE
MONSANTO CHEMICALS LTD. London
MONSANTO CHEMICALS (AUSTRALIA) LTD. Melbourne
MONSANTO (CANADA) LTD. Montreal ' Toronto ' Vancouver
Representatives in the Principal Cities of the World
OblSUdi
TOWOLDMON0039100 WATER_PCB-00023569