Document 2R5bDy6kr05LM69k6nmOBR7D6
V,
Infer ONice
Mr. Darryl Paldan Plant Engineering Livonia Transmission Plant
Personesl and Organization SfeN
15 Docamber 1983
oc R. D. Byron
S. Grendel, M.D.
R. M. Hric
Subject: Asbestos
Rsfereneest 1) Volume 29, Code of Federal Regulations, 1910.1001 2) IRAM Industrial Hygiene Bulletin Ho. 4, 4a, 4b
As requested, the sample vhich you submitted to the Industrial Hygiene Laboratory 11 November 1983 vas analysed for asbestos content.
Test result, as shown on the attached data sheet Sample No. 63-2366, reveal that
the sample contains significant amounts of asbestos. These results along with
a copy of the OSHA asbestos standard regulations should be shared with all
employees with potential exposure to this asbestos-containing material and the
Union Health and Safety Representative.
-
Excessive exposure to airborne asbestos fiber and dust may cause serious irrevers
ible adverse health effects many years after exposure. These include asbeBtosis, a progressively disabling lung disease, and cancer of the respiratory tract and of the chest and abdominal cavities. The long latency period between exposure and when disease may develop emphasizes the importance of preventive industrial hygiene control methods.
Steps must be taken to assure that employees with potential exposure to asbestos are aware of these health effeots and that proper precautions are taken to eliminate asbestos fiber inhalation. These include wet methods of dust suppres sion, use of effective respirators, vacuuming local exhaust ventilation, debris containment, and protective clothing.
If there are questions regarding this report or industrial hygiene control methods for asbestos, please call us at 33-76955*
Jb Attachment
8006 0093
SCF-FORD-3416
PRODUCED BY FORD
> TO 1 SUBJECT!
OBJECT*
'
CONCLUSIONt
TEST DATA* gamltJL.
jj-2363 83-236*1 83-2385
*
83-2388
CENTRAL LABCRATORV SERVICES LABORATORY INVESTIGATION REPORT
L. Latorre
ra 6023
December 6, 1963
3053V
DUMBER
Ceiling Material - FMOC (63-2383) Ceiling Material It floor Tile-Sanduaky (83-236^ A 2365) Pipe Insulatico-Livonia (83*2366)
Batenina if aabestoa la present and if present identify and quantify.
The four (k) samples were identified aa #83-2383 thru 83-2388; of these, two samples oontained asbestos at levels greater than 2*.
Aabeatoa jjffllllM...
52Jt ehzyeotile
ZikislsuL1* fxifrEmfr, Moderate
Balance-Other Coanonenta
Paint, cellulose fiber*
ND
~100Jl
Nigh
Paper backing
ND
Traoea
Not friable Hon-fibroua
treoolite, mineral
granules, eellulose fib
2d volatile 0 475 C*
L8J aaoaita
ND
18 ehxyaotile
High
Mortar
HD - none detected* deteotion limit 1.
(1) Flbergalsat including fiberglass, mineral wool, and slag wool.
Teat Method* Interim Method for The Betermination of Aabeatoa in Bulk
Insulation Samples* U.S. EPA December, 1982.
PRODUCED BY FORD