CHAPTER 15
1958 Guide
passes to secure good heat transfer, the use of materials resistant to the
corrosive effects of products of combustion, and draft hoods are notable
features. Control equipment includes gas pressure regulators, automatic
pilots, and limit controls designed to protect the appliance and to insure
safety of operation. A boiler, designed for gas-burning is illustrated
in Fig. 19.
' . '~
Gas designed boilers for hot water or steam heating are available in
cast-iron, steel, and non-ferrous metals. The burners are located beneath
the sections, and the flue gases pass upwards between the sections to the
flue collector. Some boilers are designed to provide domestic hot water
through the use of tankless or instantaneous heaters.
Warm air furnaces are of two types, gravity and forced air. The former
Automatic Fuel Burning Equipment
405
bonnet for forced air and gravity furnaces is 80 and 75 percent, respectively, of the approved input to the burners.
Conversion Burners
Conversion burners are usually complete burner and control units de signed for installation in existing boilers and furnaces. A typical gas con version burner is shown in Fig. 20. Atmospheric conversion burners may have drilled port, slotted port; or single port burner heads. Single port types have become increasingly popular in the last few years due to their simplicity of construction and ease of installation. In rectangular or round, drilled and slotted port burners,baffles of clay or metal are usually used to direct the products of combustion toward the side walls of the combustion chamber. In single port burners the flame usually impinges against a horizontal cast-iron, stainless steel, or ceramic distributor plate which directs the products of combustion toward the side walls. For certain applications, particularly wet base boilers, a horizontal single port burner
depends upon a thermal head to provide circulation of air over the heat exchanger and thence directly to the space to be heated, usually through ducts. Most gravity furnaces can be equipped with humidifiers. Forced warm air furnaces utilize a motor-driven blower to circulate air over the heat exchanger and through the ducts. A common type is quite similar to Fig. 18 except that gas burners, pilots, controls, and gas pressure regu lator are substituted for the oil burner, and a draft hood is attached to the outlet of the furnace. Due to the pressure developed by the blower, ductwork becomes smaller and the location of the furnace less critical than in gravity systems. Designs of forced air furnaces vary from the conven tional types that deliver heated air to overhead ductwork to the downblow types wherein the heated air is delivered at the bottom of the furnace, this latter type being designed for perimeter or radiant panel heating. Several
types of low height horizontal furnaces are available for installation in attics or under floors of unexcavated houses. These furnaces are designed
for compactness. The A.G.A. listed output at the boiler nozzle or at the
Fig. 20. Typical Single Pout Gas Conversion Burner
uu--ii-ia--e--u-. x ms design produces a horizontal flame which strikes a curved baffle that spreads the flame in a fan shape.
Several power burners in domestic sizes are available. These are of gun burner design and feature small mechanical blowers for supplying all the air required for combustion. These are particularly desirable for handling restricted flue boilers or furnaces where an atmospheric burner cannot obtain the desired output.
Conversion burners for domestic application are available in sizes ranging trom 50,000 to 400,000 Btu per hr capacity. It should be noted that the American Standard Approval Requirements are limited at present to con version burners of capacities up to 400,000 Btu per input hr. Burners of ~er capacity, for use in large steel boilers, are usually engineered by a ontractor specializing in this type of work, or by the local utility company,
ney are available in a large number of sizes and types. In some cases the jTer may be an assembly of multiple burner heads filling, the entire 400 nnn For conversion burner installation in boilers requiring more than
w,uuo Btu per hr input, reference should be made to the American naard Requirements for Installation of Gas Burning Equipment in
Coders, ASA Z21.33-1950.
arH sizes of conversion burners should conform to American Stand^tmg Requirements of Conversion Burners; ASA Z21.17-1948. As