Document 2R22E0VVV01bD7K91Va0M2MxN
900
CHAPTER 40
1954 Guide
winding circuit. The relay then keeps these contacts open because there is sufficient voltage induced in the starting winding, when /the motor is niiiningji-tri hold the relay in the open contact position.
CONTROL FOR ALTERNATING CURRENT MOTORS
: Squirrel-Cage motors are usually linestarted where power company limitations permit. In sizes up to 5 hp at 220 volts, or hp at 440 volts, polyphase motors may be started by means of manual switches having overload current elements for motor protection. In larger ratings a linestarter. is usually provided with either an additionalsafety switch or circuit breaker for disconnecting and short circuit protection. Reduced voltage starting may be either of manual or push button controlled magnetic type;- In specifying this type of starter, consideration should be given to., the fact that starting torque of squirrel-cage motors varies as the square of the applied voltage. For example, a motor developing 100 lb-ft starting
;i
Motors and Motor Controls
901
In applying reduced voltage starters to synchronous motors it should be remembered that, since these motors arc started on damper windings and function during the acceleration period similarly to squirrel-cage motors, the starting torque varies as the square of the applied voltage. Consideration should be given to insure development of sufficient motor torque to accelerate the load.
Multi-Speed control may be either manual or magnetic, and at full or reduced voltage. When using- automatic magnetic control with two-, three-, and four-speed separate winding or consequent pole motors, con trol may be obtained from a remote point by means of a push'button master switch. The various speeds of the motor are obtained from the master switch by simply depressing the correct push button. This is known as selective speed, control. It is commonly used in the smaller theater installations where the fan and motor are located backstage and the speed control is located in the lobby.
SPEED REGULATING CONTROLLER
UNIT ASSEMBLED
CONTROL
Fig. 5. Recommended Controls for Wound Rotor Motors
torque on full voltage would produce only 25 lb-ft torque on starting, on
half rated voltage. Fig. 4 illustrates recommended control practice for .,
squirrel-cage motors.
ij.
Wound Rotor motors require control of both primary and secondaryJgji
circuits. The primary* control may be the same as for squirrel-cagg^g
motors, manual or magnetic, at full voltage. Secondary* control prdi?t>?
vides means of varying secondary resistance for starting and speed control.Vi
The secondary controller should be specified for starting duty only, or for L
speed regulating duty. If the secondary controller is to be used for speed "
regulating duty, the percent speed reduction, the number of speed,control/"
points, and the type of load (variable or constant torque) should be specif
fied. Fig. 5 illustrates recommended control practice for wound rotor ^
motors..
Synchronous motor starters should provide pull-out protection, autoj;/%
matic synchronization or automatic stopping of the motor after pull-out,
and insurance of complete starting sequence, as well as overload and low <
voltage protection. The control may be either magnetic or semi-magnetic ;.
at full or reduced voltage. Semi-magnetic starters provide automatic
field control, but require hand operation for closing the line contactors to`
start and transfer to full voltage.
H J `x
* Refer to Glossary at end of chapter.
V*
Arrangements 2, 3 and 4 are optional for motors up to 7Vi hp. 220 volts.
Fig. 6. Recommended Controls for Single Phase Motors
Multi-speed motor controllers may be provided with compelling relays which make it necessary for the operator to press the first speed button before regulating the motor to the desired speed. This insures that the motor is always started at low speed before adjusting to a higher speed.
Timing relays which provide for automatic acceleration may be used for control. With this feature the motor will always start at low speed and automatically accelerate to the desired speed. Decelerating relays may be used to reduce the shock effect of the braking action on the motor and drive when the speed is reduced from a higher to a lower speed.
Single Phase motor control usually consists only of a linestarter, either manual or magnetic. In some cases it is desirable also to provide a dis connect switch. Fig. 6 illustrates the recommended controls.
MOTOR RATING
The rating of an electric motor depends upon the total temperature which the motor attains under operating conditions. This total tempera ture depends on both the ambient temperature and the temperature rise f the motor. As motor temperature rise is in turn determined by the ability of the motor to dissipate heat, circulation to the motor should not