Document 2NrkBJOQBXLkmYOeKOQ7dL1Va
S&L
1/ SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 173G6 Austin, Texas 78760
Client:
SwL Dallas
Attn; Tony Robertson
Client No.
Report No.
Report Date
505093-175 November 3, 1992
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 10/27/92. Analyzed on 10/29/92.
Site:
Southwestern Bell Telephone, 909 Colorado St., Austin, Texas 1107 Water St., Bastrop, Texas 309 SW San Antonio St., Lockhard, Texas
Eifem
SwL lab No.
909 Colorado St, Austin, Texas
RESULTS
Tima FR
(mini m
Old Bldg. Basement Hall @ Rm. B-24
COL-1
150 11.5
Old Bldg. Basement Power Room
COL-2
150 11.5
Old Bldg. 3rd Floor Sev. Lobby @ Rm. 303
COL-3
147 11.5
Old Bldg. Rm. 301
COL-4
140 11.0
New Bldg. Basement Mech. Rm. #0-1
COL-5
135 11.0
New Bldg. Basement Power Room
COL-6
137 11.5
New Bldg. 1st Floor Rm. 122
COL-7
133 11.5
New Bldg. 1st Floor Beet. Rm. 124 (Inside Rm. 122)
COL-8
132 11.5
New Bldg. Sth Floor Elev. Lobby @ Rm. 521
COL-9
132 11.0
New Bldg. 5th Floor Rm. 521
COL-10
135 11.0
New Bldg. 8th Floor Rm. 804
COL-11
135 11.5
Volumes (liters).
1725 1725 1690.5 1540 1485 1575.5 1529.5 1518
1452 1485 1552.5
FB/FL
4.5/100 3.5/100 10.5/100 1.5/100 0/100 2.0/100 2.0/100 2.0/100
1.5/100 1.0/100 6.5/100
MFA
Fibers/cm3
0.00787 <0.003
0.00787 <0.003
0.00787
0.003
0.00787 0.00787
<0.003 <0.003
0.00787 <0.003
0.00787 <0.003
0.00787 <0.003
0.00787 <0.003 0.00787 <0.003 0.00787 <0.003
s
004068
Page 2
QBslLEL
SwL-lab. No.
009 Colorado St.. Austin. Texas (Com.)
Time (min)
New Bldg. 8th Floor Elev. Lobby @ Rm. 805
COL-12
137
Field Blank
COL-13
-
RESULTS
FR Volumes fl/m) (liters)
11.5 1575.5
--
a 5.0/100 0/100
tto? Water St, Bastrop, Texas.
Switch Room
BAS-1
Air Handler Room
BAS-2
Field Blank
BAS-3
145 11.5 145 11.5 --
1667.5 1667.5
.
2.0/100 1.0/100 0/100
MFA
AC* Fibers/cm3
0.00787 <0.003
0.00787
P X
^
0.00787 <0.003
0.00787 <0.003
0.00787
309 SW San Antonio St., Lockhart. Texas
South end of Bldg.
LOC-1
North end of Bldg.
LOC-2
Field Blank
LOC-3
145 11.5 145 11.5
,,
1667.5 1667.5
.
1.5/100 3.0/100 0/100
0.00787 0.00787 0.00787
<0.003 <0.003
AC determined using a minimum 10 PB/10Q R. Reliable Quantitation Unit where applicable. Rbers/ce are blank corrected where applicable.
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dalton Asbestos Coordinator
Hilary D. Johns Senior Programs
Our letter* end report* are for the exclusive use of the client to whom they are addressed. The letters and report* shall not ba reproduced except In full without the approval of testing laboratory. The use of our name must receive our prior written approval.
004069
SwL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O, Box 173668 Austin, Texas 78760
Client:
SwL Dallas Attn: Robert Garrison
Report No.
Report Date Page
505092-656 June 1, 1992 1 of 2
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 5/26/92 Analyzed on 5/29/92.
Site: Southwestern Bell Telephone, 909 Colorado Street, Austin, Texas
EBsJJL
Old bldg., basement hallway at B-24
Old bldg., basement power room
Old bldg., 3rd floor, hall at Room 303, elevator lobby
Old bldg., 3rd floor, Room 301
New bldg., basement, mechanical room 0-1
New bldg,, basement, power room
New bldg., 1st floor, Room 122
New bldg., 1st floor, electric room #124, Inside Room 122
New bldg., 5th floor, elevator lobby at Room 521
New bldg., 5th floor, Room 521
New bldg., 8th floor Room S04
RESULTS
^P
SwL lab No.
Time (min)
Col-1
140
FR fl/m)
11.5
Volumes (liters)
1610
FB/FL 2.0/100
MA 0.00787
AC* Fibers/cm'
<0.003
Col-2
145 11.5
1667.5
1.0/100
0.00787 <0.003
Col-3
145 12.0
1740
11.0/100
0.00787
0.003
Col-4 Col-5 Col-6 Col-7 Col-8
144 12.0
1728
6,5/100
0.00787 <0,003
145 12.0
1740
1.0/100
0.00787 <0.003
143 12.0
1716
1.0/100
0.00787 <0.003
151 11.5
1736.5
3.0/100
0,00787 <0.003
146 11.5
1679
2.0/100
0.00787 <0.003
Col-9
137 12,0
1644
4,5/100
0.00787 <0.003
Col-10 Col-11
136 11.5
1564
7,0/100
0,00787 <0.003
137 11.5
1575.5
4.5/100
0.00787 <0.003
004070
SwL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 173668 Austin, Texas 78760
Client:
SwL Dallas Attn: Robert Garrison
Report No. Report Date
Page
505092-656 June 1, 1992 2 of 2
Site: Southwestern Bell Telephone, 909 Colorado street, Austin, Texas
Filter i.D.
New bldg., 8th floor, elevator lobby at Room 805
Blank
RESULTS
SwL Lab No.
Time (mini
FR (i/ml
Col-12
120 11.5
Volumes (liters)
1380
PB/FL 4,5/100
MFA 0.00787
AC* Fibers/cm
<0.004
Cot-13
-
0.5/100
0.00787
*AC determined using a minimum 10 F8/100 FL Reliable Quantitation Unit where applicable. Fibers/cc are blank corrected where applicable. Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Methodology 7400.
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except m lull without the approval of testing laboratory. The use of our name must receive our prior written approval.
GG4071
/P2- C>fo
S&1
SOUTHWESTERN LABORATORIES
Client:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 173668 Austin, Texas 78760
SwL Dallas Attn: Robert Garrison
Client No. Report No. Report Date
505092-121 December 20, 1991
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 12/16/91. Analyzed on 12/20/92.
Site: Southwestern Bell Telephone, 909 Colorado Street, Austin, Texas
Filter l,D.
Old bldg, basement; hall at Room B24
Old bldg, basement; power room
Old bldg, 3rd floor; elevator lobby at Room 303
Old bldg, 3rd floor; Room 301
New bldg, 5th floor; main elevator lobby
New bldg, 5th floor; Room 521
New bldg, 8th floor; main elevator lobby
New bldg, 8th floor hall at Room 813
New bldg, 1st floor Room 122
Hew bldg, basement; power room
New bldg, basement; mech. room 0-1
New bldg, 1st floor mech. room 128
RESULTS
Swl lab No.
Time (min)
FR 0/m)
SWB-1
120 10,0
Vclumes filters)
1200
FB/Fl 3.0/100
MFA 0.00787
AC* Fibers/cm'
<0.004
SWB-2
120 10.0
1200
1.0/100
0.00787 <0.004
SWB-3
120 10,5
1260
12.0/100
0.00787
0.005
SWB 4 SWB-5 SWB-6 SWB-7 SWB-8 SWB-9 SWB-10 SWB-11 SWB-12
120 10.0
1200
120 11.0
1320
120 10.0
1200
120 10.0
1200
120 10.0
1200
120 10.0
1200
120 10.5
1260
120 10.0
1200
120 10.0
1200
5.0/100
0.00787 <0.004
2.0/100
0.00787 <0.004
1.5/100
0.00787 <0.004
4.5/100
0.00787 <0.004
5.0/100
0.00787 <0.004
1.5/100
0.00787 <0.004
1.0/100
0.00787 <0.004
1.0/100
0.00787 <0,004
3.0/100
0.00787 <0.004
004072
S&L
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Sox 173668 Austin, Texas 78760
Client:
SwL Dallas Attn: Robert Garrison
Client No. Report No. Report Date
305092-121
December 20, 1991
Project:
Airborne asbestos samples taken by Kenneth Williamson with swL on 12/16/91. Analyzed on 12/20/92.
Site: Southwestern Bell Telephone, 909 Colorado Street, Austin, Texas
Filter I.D. Blank
RESULTS (Continued)
SwL Lab No,
Tima (mini
FR (I/ml
Volumes (liters)
SW8-13
FB/FL 1.5/100
MFA 0.00787
AC* Fibers/cm'
Remarks:
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dalton Asbestos Coordinator
Hilary D. Johnshrllanagw Senior PrognBti
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of testing laboratory. The use of our name must receive our prior written approval.
fn: ASBDALLAS
0J4073
S&L
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
DAILY LOG
Reoort Date:
12/16/91
To: SwL - Dallas, Attn: Robert Garrison
Project Name: Southwestern Bell
Project No: 909 Colorado - Austin, Texas
SwL Time Start:
7:30 a.m
o<2
p
uo
dm
PAGE 1 OF 2
Samoie Date:
12/16/91
No. of Samoies Taken:
13
Method of Test: NIOSH 7400-A
SuDerintendent:
SwL Technician: Kenneth Williamson
Foreman:
Sample location
Old bldg, basement; hall at Room B24
Old bldg, basement; power room
Old bldg, 3rd floor; elevator lobby at Room 303
Old bldg, 3rd floor; Room 301
New bldg, 5th floor; main elevator lobby
New bldg, 5th floor Room 521
New bldg, 8th floor main elevator lobby
New bldg, 8th floor hall at Room 813
New bldg, 1st floor Room 122
New bldg, basement; power room
New bldg, basement; mech. room 0-1
New bldg, 1st floor mech. room 128
ID SWB-1 SWB-2 SWB-3
Time Start
10:55 am
Time Stop
12:55 pm
Total Time (min)
120
Flow Rate 0/m)
10.0
Volume (liters)
1200
Fibers/ Field
3.0/100
MFA 0.00787
FJcc <0,004
11:02 am
1:02 pm 120
10.0 1200
1.0/100
0.00787 <0,004
11:16 am
1:16 pm 120
10.5 1260
12.0/100
0.00787
0 005
SWB-4
11:20 am
1:20 pm 120
10.0 1200
5.0/100
0.00787 <0.004
SWB-5
11:38 am
1:38 pm 120
11.0 1320
2.0/100
0.00787 <0.004
SW8-6
11:41 am
1:41 pm 120
10.0 1200
1.5/100
0.00787 <0.004
SWB-7
11:44 am
1:44 pm 120
10.0 1200
4,5/100
0.00787 <0.004
SWB-8
11:53 am
1:53 pm 120
10.0 1200
5.0/100
0.00787 <0,004
SWB-9
12:00 pm
2:00 pm 120
10.0 1200
1.5/100
0.00787 <0.004
SWB-10
1:15 pm
3:15 pm 120
10.5 1260
1.0/100
0.00787 <0.004
SWB-11
1:20 pm
3:20 pm 120
10.0 1200
1.0/100
0.00787 <0,004
SWB-12
1:30 pm
3:30 pm 120
10.0 1200
3.0/100
0.00787 <0,004
0j!074
j{ P lioCl^
S&L
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
DAILY LOG
Report Date:
12/16/91
To: SwL - Dallas, Attn: Robert Garrison
Project Name: Southwestern Bell
Project No: 909 Colorado - Austin, Texas
SwL Time Start:
7: 30 a.m.
SIod:
4:30 D.m.
PAGE 2 OF 2
Sample Date:
12/16/91
No. of Samoles Taken:
13
Method of Test: NIOSH 7400-A
Superintendent:
SwL Technician: Kenneth Williamson
Foreman:
Sample Location
Blank
ID SWB-13
Time M
,
Time Stop
,,
Total Time (mini
Flow Rate fl/ml
.
Volume (liters)
.
Fibers/ Field
1.5/100
MFA 0.00787
Remarks:
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dalton Asbestos Coordinator
Our letters end reports are for the exclusive use of the client to whom they ere addressed. The letters and reports shell not be reproduced except in full without the approval of testing laboratory. The use of our name must receive our prior written approval.
fn: ASBDALLAS
G'jy'071
SWL * P.O. Bo* 224227
SOUTHWESTERN LABORA TORIES
2575 Lor* Star Drive Dallas, Texas 75222 e 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Beil Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Report Date: Date Received: Report Number:
June 7, 1993 May 27, 1993 9305286
Identification:
1107 Water, Bastrop, IX
SAMPLE NO, 01052193 02052193 03052193
04052193 0S052193
LQATIQN Mechanical Room #1 A/H Generator Room Mechanical Room #2 A/H, below attic opening Field blank Field blank
VQMMJLl 1080 1080 1080
FIBERS PER CC <0.004 <0.004 <0.004
2.0/100 fids. 1.5/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
Analyst:
SOUTHWESTERN LABORATORIES, INC.
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in lull without the approval of the testing laboratory. The use of our name mu* receive our prior written
zmOj
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services 2575 Lone Scar Drive R . Box 22-4227 Dallas. Texas 75222 21-4/263-1 133
Type of Activity:
Decontamination_____Background Abatement
... -- ----------
ReiDKks!/<&[
/i C
MdL,
-----------------
n;idOT7
HOUSTON DALLAS AUSTIN BEAUMONT CONROE! GALVESSTTOBN COUNTY PtO GRANDE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 17366 Austin, Texas 78760
Client:
SwL Dallas Attn8 Tony Robertson
Client No. Report No. Report Date
505093-175
November 3, 1992
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 10/27/' Analyzed on 10/29/92.
Site:
Southwestern Bell Telephone, 909 Colorado St., Austin, Texas 1107 Water St., Bastrop, Texas 309 SW San Antonio St., Lockhard, Texas
RESULTS
10- SwL Lab No. 909 Colorado St- Austin. Texas
Time (mini
FR fl/ml
Old Bldg. Basement Hal @ Rm. 8-24
COL-1
150 11.5
Old Bldg. Basement Power Room
COL-2
150 11.5
Old Bldg. 3rd Floor Bev. Lobby @ Rm. 303
COL-3
147 11.5
Old Bldg. Rm. 301
COL-4
140 11.0
New Bldg. Basement Mach. Rm. #0-1
COL-5
135 11.0
New Bldg. Basement Power Room
COL-6
137 11.5
New Bldg. 1st Floor Rm. 122
COL-7
133 11.5
New Bldg. 1st Floor Beet Rm. 124 (Inside Rm. 122)
COL-8
132 11.5
New Bldg. 5th Floor Bet. Lobby @ Rm. 521
COL-9
132 11.0
New Bldg. 5th Floor Rm. 521
COL-10
135 11.0
New Bldg. 8th Floor Rm. 804
COL-11
135 11.5
Volumes (liters)
1725 1725 1690.5 1540 1485 1575.5 1529.5 1518
1452 1485 1552.5
FB/FL
4.5/100 3.5/100 10.5/100 1.5/100 0/100 2.0/100 2.0/100 2.0/100
1.5/100 1.0/100 6.5/100
MFA
Fibers/cm'
0.00787 <0.003
0.00787 <0.003
0.00787
0.003
0.00787 0.00787
<0.003 <0.003
0.00787 <0.003
0.00787 <0.003
0.00787 <0.003
0.00787 <0.003 0.00787 <0.003
0.00787 / <0.003
C04078
asm
SwL Lab No,.
Time fminl
909 Colorado St.. Austin Texas (Corn.)
New Bldg. 8th Floor Eiev. Lobby # Rm. 805
COL-12
137
Field Blank
COL-13
-
RESULTS
FR Volumes n/mi Alters?
11.5 1575.5
--
FB/FL 5.0/100 0/100
HOT Water St., Sastroo. Texas
Switch Room
BAS-1
AJr Handler Room
BAS-2
Reid Blank
BAS-3
145 11.5 145 11.5 --
1667.5 1667.5
-
2.0/100 1.0/100 0/100
MFA
AC* Elbeacm
0.00787 <0.003
0.00787
)/ : ) '
x -
0.00787 <0.003
0.00787 <0,003
0.00787
-
309 SW San Antonio St... Lockhart. Texas
South end of Bldg.
LOC-1
North end of Bldg.
LOC-2
Field Blank
LOC-3
145 11.5 145 11.5 -
1667.5 1667.5
.
1.5/100 3.0/100 0/100
0.00787 0.00787 0.00787
<0.003 <0.003
.
AC etefarmlned using a minimum 10 PB/100 FI RelJabla Quantitation Unit wbera applicable, nbara/ee art blank corrected where applicable.
SOUTHWESTERN LABORATORIES, INC.
Robert N. Oaiton Asbestos Coordinator
Hilary D. Johns Senior
Our letters and reports are for the exclusive use of the client to whom they ere addressed. The letters and reports shall not be reproduced
except In flit without the approval of testing laboratory. The use of our name must receive our prior written approval.
004079
SWL /T* ' P.0. Box 224227
SOUTHWESTERN LABORATORIES
2575 Lone Star Drive Dallas, Texas 75222 214/651-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
March 11,1994 March 4, 1994 9403043
Identification:
1107 Water, Bastrop, TX
SAMPLE NO. 01022894 02022894 03022894 04022894 05022894
LOCATION Emergency Engine Room Mechanical Room #1 Mechanical Room #2 Field blank Field blank
VOLUME (L) 1068 1218 1199
FIBERS PER CC <0.004 <0.004 <0.004 1.0/100 fids. 2.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Kyle Env
and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be
reproduced except in full without the approval of the resting laboratory. The use of our name must receive our prior written approval.
004080
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2373 Lone Star Oriva P O. Box 234327 Dallam. Taxas 75222 214/363-1 133
Report of test on:
r/-> i
i,
Date tested:
Project:
/ / 6) 7
/)/// f? f
f~ , ^ cl tA > -f / <n
Lab Number:
Sample Number / ID
Location
Pump Number Time
Flow and Det. Volume Limit
Fibers per Field
Fibers per cc
am>m
&
Ate#--.
otntfty
jifi &tjjr
i*t
Me* 1
Off
i.maiiyy.
On//.* / J
^.4'
L/Hin
Elapsed
'3*3S
Off
1 Oi/d L
V5V
nrtb On 3* Elapsed
3*1 V
Off
L/Min
/3-lg
L
a-
Onfl'.JO
nn7 Elapsed
Al-o
L/Min
//
L
Off
txloiWf
On L/Min Elapsed
Off On L/Min Elapsed
Technician: __ __________ ____________
Analyst: ;________________ _____
CIH/IH:
__Manager:
Type of Activity:
Decontamination
Background
Abatement
Remarks:
_________________________ _____________________________
Chain of Custody:
------------- ----------------
-------------------------------
----- G j 4.0 81
HOUSTON QALUAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANOE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKAMA SHOPMAN
ScuL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2575 Lone Star Drive Dallas, Texas 75222 # 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
September 1, 1992 August 31, 1992 9208277
Identification:
801 Runnels, Big Spring, TX
On August 25, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 801 Runnels in Big Spring, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NQ,
LOCATION
VOLUME. (L) FIBERS PER CC
082592 SBBS-01
Field blank
1,0/100 fids.
082592 SBBS-02
Field blank
0.0/100 fids.
082592 SBBS-03
1st floor, old Switch Room
1071 <0.005
082592 SBBS-04
Basement, Power Room
1071 <0.005
082592 SBBS-05
Basement, AHU Room
1071 <0.005
082592 SBBS-06
Basement, hallway
1081 <0.005
082592 SBBS-07
1st floor, new Switch Room
1111 <0.005
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
:kz and Analytical Services
G,,'40S2
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be
`
reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
?/ sw
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 a 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 117 San Antonio, Texas 78216
Identification:
801 Runnels, Big Springs, TX
Report Date: Date Received: Report Number:
March 2, 1992 February 25, 1992 9202249
X?
On February 19, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 801 Runnels in Big Spring, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
gAMPLEm
LOCATION
VQLIfflSiL), FIBERS PER CC
021992 SBBS-01 021992 SBBS-02 021992 SBBS-03 021992 SBBS-04
021992 SBBS-05 021992 SBBS-06 021992 SBBS-07
Field blank Field blank Basement, Cell area Basement, Office area near Emergency Generator 1st floor, Switch Room 1st floor, Frame Room 1st floor, Frame Room
864 1 855
902 824 902
4.5/100 fids. 1.5/100 fids. <0.006 <0.006
<0.005 <0.006 <0.005
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst
Bob Garrett, Manager Environmental and Analytical Services
001083
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SOUTHWESTERN LABORATORIES
Report of: Report to:
2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
April 20, 1994 April 18, 1994 9404143
Identification:
530 Deahl, Borger, TX
SAMPLE NO. 01041294 02041294 03041294 04041294
LOCATION 1st floor, Air Handler Boiler Room Emergency Engine Room Mechanical Penthouse Field blank Field blank
VOLUME (L) 1085 1120 1075 763
FIBERS PER CC <0.005 <0.004 <0.005 <0.006 0.0/100 fids. 3.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
Kyle Burroughs :kz Environmental and Analytical Services
01/4084
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical entineering, nondestructive, metallurgical and analytical services
2573 Lone Star Drive R O. Box 224227 Dallas. Texas 75222 214/2B3-1133
: - Ai>b,4os Ai < Report of test on
. 4:| ^ Date tested
Project:
jplOrC^-Cr^
Lab Number:
Sample Number / ID
Location
Pump Number Time
Flow
and Det. Volume Limit
fe<- f<
Off 4-S'2~
DtOfiXq^
S&ilep L
mi- On (iCT L/Hi n
Elapsed 94o
om3"'
msu on /a os L/Min
Elapsed /iSLO L
o-jioHa^H 040<{(23<f
Off
th\C\ &na
inri On/^'OS Elapsed '2/fo
Off
TIG,
/7/7<*
On/>/5
Elapsed
(10
Off
On
M* L/Min
to'JS
L
L/Mi n 73
L/Min
Elapsed
Fibers per Field
Fibers per cc
CIH/IH: Type of Activity: Remarks:
Analyst: Manager: Decontami nati on_____Background____ Abatement
Chain of Custody:
004085
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANGE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. Box 224227
SOUTHWESTERN LABORATORIES
2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Identification:
Deahl, Borger, IX
Report Date: Date Received: Report Number:
August 30, 1993 August 12, 1993 9308160
/ p a; - ;
SAMPLE NQ, 01081193 02081193 03081193 04081193
05081193
LOCATION Emergency Engine Mechanical Room Boiler Room 2nd floor, Mechanical Room Field blank Penthouse Field blank
VOLUME (L) 1085 1072 1090 1075
1078
FIBERS.PER CC <0.005 <0.005 <0.004 <0.005 0.0/100 fids. <0.005 0.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
Analyst:
SOUTHWESTERN LABORATORIES, INC
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0j4086
SOUTHWESTERN LABORATORIES
Mmrmh, tmHnmmuml amt gm$skwM tmmmmt. mmiatmam, amtaMurgiemt ami amafyUeml
3976 Lomu Sear Qrtvw R Q. Box 834337 Oates, Dmm 75222 214/363*1133
sh*>fc it a. MokiJi
Report of test on: *
Oate tested: JkJlaa
Project:
Sample Number / 10
oioiiws
* BofCrj^r
Attn ZtJatcetL
! *h Nunber:
V1
Location
Pump Humber Time
Flow and | Oet. Volume Limit
Fibers f Fibers per per Field cc
&IM). EXq
Off^^ f,sz
0n|*5S L/Hin
*y^3i Elapsed IDt
Q*k)
l
Off^^P
i
oot
On^pi l/Min
Elapsed o /*>'
3sisSsi.
j2f^v
_fljgdsi_
Bk**=
Off]-
OnSW L/Hin
^$ed G
iorio
L
Off] .(O
On 3 It) L/Min rM3 Elapsed o
4Hc
Off
On L/Hin
Elapsed
L
Technician:
Analyst:
CIH/IH:
_______________________ Manager: __________________
Type of Activity: ____Decontamination____ Background____ Abatement
Remarks:
Chain of Custody: --......... ...... ' . -- ------------ --------- -------
- _____
HOUSTON OPU-AS AUSTIN BEAUMONT CONRO* OAt.VC8TON COUNTY MO QRAMOC VUCV MJXANQMA AN ANTOMQ PORT WORTH * !_GSVSTMU* MOUNO MONK* SH-MvZPOfW TSXA/MKAMA BMSRMAN
, Gj4087
Materials, aarirmmetttel ami gamaeknkal emwmormg, MarfHtraKftW, metelmpesl mid mmfytkal sambas
SS79 Lon Star Qrtw * R CL Beat S2M227 * OaMM. IhMM 75222 814/263*1133
Pdhtd&> iiY Moni
Date tested: ^llf J^3
Report of test on:
project:
DAaHWn l__________
SlBojrgcr
g-eWi 'ffetierson
Lab Number:
Sample Number / ID
Location
Pump Number Time
Row
and Det.
Volume Limit
Fibers Fibers per per Field cc
ixwUxflJS<~
ofrr.5 f-M
on?: L/HIn
IHT7 Elapsed o'?
Off
SP On L/HIn
Elapsed
L
Off
On L/Min
Elapsed
L
Off
On L/Min
Elapsed Off
L
On JsMe
Elapsed
L
Technician: ____________ Analyst: ______
CIH/IH:
____ Manager: _____________
Type of Activity:
Decontamination Background Abatement
Remarks:
Chain of Custody: ------- - --... . ______ _________ __
wouerow
*ustw haumqnt coNfvjg tww.vaTON countv no o**no \mujv ALmxANomA
HAN ANTONK3 * PQHRT WORTH V.MBVTU.e MUQUMMO MOfSC* HRWVSPCWT TWXARRKANA ShaiRMAN
01*4088
StvL
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2S75 lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Beil Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
September 2, 1992 August 31, 1992 9208290
Identification:
530 N. Deahl, Borger, TX
On August 31, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 530 N. Deahl in Borger, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
082892 SBB-01
Field blank
0.5/100 fids.
082892 SBB-02
Field blank
1.0/100 fids.
082892 SBB-03
1st floor. Frame .Area
1071 <0.005
082892 SBB-04
1st floor, Toll Area
1081 <0.005
082892 SBB-05
1st floor. Switch Room
1071 <0.005
082892 SBB-06
Basement, Emergency Eng. Room
1042 <0.005
082892 SBB-06
Basement, Power Room
1042 <0.005
Analysis performed by Histe Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
:kz Environmental'and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
OL-4089
S&1
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 # 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 117 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
March 2, 1992 February 25, 1992 9202252
Identification:
530 Deahl, Borger, TX
On February 21, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 530 Deahl in Borger, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VQMJME (L) FIBERS PER CC
022192 SBB-01 022192 SBB-02 022192 SBB-03 022192 SBB-04 022192 SBB-05 022192 SBB-06
Field blank Field blank Switch Room Toll Room Basement, Cell area Basement, Emergency Eng. Room
1460 1326 1450 1432
2.0/100 fids. 1.5/100 fids. <0.003 <0.004 <0.003 <0.003
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst
Bob Garrett, Manager Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
004090
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2375 Lone Star Drive R . Box 224227 Dallas. Texas 75222 214/263-1133
Report of test on: -
Date tested: 3 ~ f)Cj -Cf
Project:^ X p (JU \
I jpCXj
Lab Number:
Sample Number / ID
Location
HI !&mj A CR*itrrr*-
,C\i
3c
0^
P-Q,L~- ).~itL-r-ri
^Loiyw-.
vt.
i? V 3
. ^-Q^n
1
.3
U 3
3
Pump Number
M
Time
Flow and Volume
Det. Limit
0
/\y
O7
Off.
i
0n /<X: 30 L/Min
Elapsed /o & L
Off SV>->
On , j ! >0
Elapsed
<7^
^10 L/Min
L
H' :>
3
Or
3
Elapsed ct-IOfn,
L/Min
(5)
<l0
\rf (P
\
4
Off5.00
On /*U*>
Elapsed
jRs
Oft ,
5.w On
/2. Jj Elapsed
Z) ^
**r _) L/Min
a. 3
L/Min
/fifr
L
Fibers per Field
Fibers per cc
Technician;
Analyst:
Chain of Custody:
CIH/IH:
Manager:
Type of Activity:
Decontamination Background_____Abatement
Rem^s
L :7/f<? a^: Pi di^ ! QL
--^23
"/v ~) 7<?*-} (~___________
.
004091
HOUSTON n*i LAS AUSTIN * BEAUMONT CONROE GAi_VESTQN COUNTV RIO GRANGE VALUEV ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MJOLAinC VONRC* SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2373 Lon Scar Drive R Q. Box 224227 Dallas, Texas 75222 214/263-1 133
Report of test on:
Date tested: 3 -Ztf.fJ
Type of Activity: Remarks
Decontamination____ Background_____ Abatement "7/3*7 Seir\j -Q(Lj - /<^4
------- --/X____________________________________ __________________ ________ __
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GAl.VEStQN COUNTY RIO GRANDS VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MIOLANC VONRQE SHREVEPORT TEXARKANA SHERMAN
SWL ' P.O. Sox 224227
SOUTHWESTERN LABORA TORIES
2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
April 20, 1994 April 18, 1994 9404142
Identification:
1608 5th, Canyon, TX
SAMPLE NO, 01041394 02041394 03041394
LOCATION Emergency Engine Room Air Handler, Basement 1st floor. Air Handler Field blank Field blank
VOLUME (Lj 763 841 990
FIBERS PER CC <0.006 <0.006 <0.005 0.0/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC
Analyst;
Kyle/oti: :kz EnvW>: lenfeHmd Analytical Services
Our letters and reporta are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in fiill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0 G 4092
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lot Star Oriva R O, Sox 224227 Dalles. Texas 75222 214/263-1133
Report of test on: fj S fat'St& ^ /hC
Date tested:
CIH/IH: Type of Activity: Remarks:
Manager: Decontamination Background
Abatement
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANOE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. Box 224227
SOUTHWESTERN LABORATORIES
2575 Lon* Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
April 11, 1994 March 28, 1994 9403242
Identification:
11200 Pellicano
SAMPLE NO, 19032394 20032394 23032394 24032394
LOCATION Mens Restroom, 1st floor Const. Work Center Field blank Field blank
VOLUME (L) 1085 1204
USERS PER CC 0.005
<0.004 3.5/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC
Kyle JBurrougbs r Environmental and Analytical Services
Our tetters and reports are for the exclusive use of the client to whom they are addressed. The letters snd reports shall not be reproduced except in full without the approval of the testing laboratory. The uae of our name must receive our prior written approval.
004094
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2375 Lone Star Drive R O, Box 224227 Dalles, Texes 75222 214/2B3-1133
Report of test on
r\ o
Date tested: /) 3 * " Vc/
Project:
Lab Number:
Sample Number /ID
Location
Pump Number Time
Flow and Det. Volume Limit
/Vjfcn a n<j?'yiycei^n I rL
Off H'52-
On ^.;Lc3 L/Min
Elapsed
L
j2J0 3-i35</ I^VI 5 / jki CY ft C. Sm-
Off $0m
On f ^ ?m Elapsed
`3.10 Off
WU
L/Min /*o</
L
On L/Min Elapsed
Fibers Fibers per per Field cc
o^03^c|
v*--
Off On L/Min Elapsed
Off On L/Min Elapsed
Technician: CIH/IH: Type of Activity: Remarks:
Analyst: Manager: Decontamination__ Background
Abatement
Chain of Custody:
0j409o
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV WO GRANGE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. Box 224227
SOUTHWESTERN LABORATORIES
2575 Lon* Star Drive Dallas, Texas 75222 e 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, IX 78216
Report Date: Date Received: Report Number:
July 15, 1993 July 1, 1993 9307009
Identification:
11200 Pellican, El Paso, TX
SAMPLE NO. 01062493 02062493 03062493 04062493 05062493 06062493 07062493 08062493
LOCATION Room 103 Room 116 Construction area outside of Room 118 Room 216, Adm. area Room 216, Copy Room 2nd floor. Conference Room Field blank Field blank
VOLUME (L) 1080 1080 1080 1080 1080 1080
FIBERS PER CC <0.005 <0.005 <0.005 <0.005 <0.005 0.005 0.0/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:.
:kz (^Analytical Services
Our letters and reporta are for the exclusive use of the client to whom they are addressed. 'The letters and reporta shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0o4096
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services 2373 Lon Star Orfva * R CD. Box 224227 Dallas. Taxaa 75222 si 4/2B3-1133
: jAdO?/Report of test on
Date tested:^
Project: //2 bd j- V f f'j/ f
fp l)
Lab Number:
I
Sample Number /ID
Location
A*
P
$)
ft* i o 3
Ll~
A
i j I L,:
/ v
7TT7
f) 3.1L . 4 HA/)irt. -CL
^yyx ov ( C-
!A Xli-^ P
,4
--
Pump Number Time
Flow and Det. Volume Limit
A
(Off a
p.o
On0s0 L/Hin
fty
Elapsed
.3 1
L
Off , 4
Aoin * ^
* Elapsed
fan W
fc-
L/Min
/Op
\
r \
\
Off ^ <3:* S
On.?
! j)
Elapsed
"o
P- -
L/Min
/op
L-
Off 3-
>o
On/^-co
Elapsed
L/Min 4^>
L
\V
.1 A \
Off y*>
On
10 \ 00
Elapsed
</ o L/Min
(S<>
/
Fibers per Field
Fibers per cc
i?
'$Aa..cL-p ^ e. ^
Technician:
Uf. ^.Analyst:
CIH/IH:
Manager:
Chain of Custody:
Type of Activity:^ _ Decontamination
Background
Abatement
Remarks
/ C'Z&> /i' /?&! r <Xu.j
5kr- /-ioQ> /->fc
Oj4097
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV 0 GBANDS VALLEY ALEXANDRA SAN ANTONIO PORT WORTH LSSSVILLS MIDLAND MONBOe SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2373 i ornmn Rt-jw Driva R O. Box 224227 Dallas, Texas 75222 214/2S3-1 133
,-JlSlDOil
Report of test on
. 0 ft Project:! /f ; ) iM- ^ L
I i(lyy^
Q kci, - Xa
Date tested: (* LV / Lab Number:
Sample Number / ID
Location
, nh OSA.<^ Ujbi\ Ct^----
So
0
4"V
\s y
AV o
/a. U
/'
r3 v*
>A,
JV
uu
Technician:VU >j
iLil t
Pump Number Time
Flow and Det. Volume Limit
V>
r\\\ J
\
m"5 o >'
</.<
On ifr.A L/Wn
Elapsed /&' 9^t?
Off
On t/Min
Rapsed
Fibers Fibers per per
Field cc
Off On,..''^ L/Min Elapsed
Off
On L/Min
Elapsed
Off On
L L/Min
Elapsed
L
Analyst:
Chain of Custody:
CIH/IH:
Manager:
Type of Activity:
Decontamination
Background
Abatement
Remarks rSC'J AU( fftfk - .JXI.cl, u M'J , +6_~`
Vf)'// <Tj a, t
_cv/i'_ ~ /- II y^ |&I- . !
/i
4 7 ^/ C-
HOUSTON QALJLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY WO GRANGE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESV1U-E MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
0j4098
SwL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2575 lone Ster Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
XA 0^
July 2, 1992 June 29, 1992 9206275
Identification:
11200 Pellicano, El Paso, Texas
On June 25, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 11200 Pellicano in Ei Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE N&
yKAUQN
VOLUME fLl FIBERS PER Cg
062592 SBP-01
Field blank
1.0/100 fids.
062592 SBP-02
Field blank
0.0/100 fids.
062592 SBP-03
1st floor. Office, Room 102
1318 0.004
062592 SBP-04
1st floor. Large Office, Room 116
1287
0.004
062592 SBP-05
1st floor, Large Administration area, north side of building
1307
<0.004
062592 SBP-06
1st floor. Mail Room
1297
<0.004
062592 SBP-07
2nd floor. Discussion Room
1463 <0.003
062592 SBP-08
2nd floor. Conference Room
1432
0.006
062592 SBP-09
Southwest comer cubicle at
1390
0.009
Analyst! performed by Fbue Coclrsit Microscopy in accordance with NIOSH Method 7400. SwL Dtllts is rated proficient by the KK>SH Proficiency Analytic*! Te*t (PAT) Program, Laboratory I.D. No. 75212-001.
Analyst:,,
'{Lt
:kx
SOUTHWESTERN LABORATORIES, INC.
/hyi-
Bob Garrett, Manager^" Environmental and Analytical Services
Our letters and reports are for the exclusive use ofthe client to whom they are addressed. The letters and reports dull not be reproduced except in fill! without the approval of the testing laboratory. The use of our name must receive our prior written approval.
004099
S&L
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 2, 1992 June 19, 1992
9206182
Identification:
366 Cypress, Abilene, Texas
On June 15, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 366 Cypress in Abilene, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
061592 SBA-01
Field blank
1.0/100 fids.
061592 SBA-02
Field blank
1.0/100 fids.
061592 SBA-03
Basement, A/C Room
1327 <0.004
061592 SBA-04
Basement, A/C Room
1356 <0.004
061592 SBA-05
Basement, A/C Room
1403 <0.003
061592 SBA-06
Basement, Boiler Room
1384
<0.003
061592 SBA-07
Basement, Boiler Room
1394 <0.003
061592 SBA-08
Basement, Mechanical Room
1260
<0.004
061592 SBA-09
Basement, Special Services Room
1270
<0.004
061592 SBA-10
Basement, At & T Area, east end
1298 <0.004
061592 SBA-11
Basement, At & T Area, north central
1251 <0.004
061592 SBA-12
Basement, At & T Area, west end
1251 , <0.004
061592 SBA-13
6th floor, Penthouse, A/C Room
* 1566
<0.003
061592 SBA-14
3rd floor, A/C Room
1518 <0.003
OLi 4100
SOUTHWESTERN LABORATORIES, INC.
Report No: Report of: Reported to: PAGE 2 of 2
9206182 Air Monitoring Southwestern Bell Telephone
.SAMPLE NO, 061592 SBA-15 061592 SBA-16
LOCATION 2nd floor, A/C Room 1st floor, A/C Room
VOLUME (L) 1508 1317
FIBERS PER CC <0.003 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. Swi, Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. Hie use of our name must receive our prior written approval.
004101
SwL
SOUTHWESTEHiy LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 117 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
March 2, 1992 February 25, 1992 9202251
Identification:
3120 Eddy, Amarillo, TX
On February 20, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 3120 Eddy in Amarillo, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SMgLENQ,
LOCATION
VOLUME (L) FIBERS PER CC
022092 SBA-01 022092 SBA-02 022092 SBA-03 022092 SBA-04 022092 SBA-05 022092 SBA-06
Field blank Field blank Break Room, Mail Room Directory Assistance TOPS, Toll & Assistance Mechanical Room, southwest end of bldg.
1143 1153 1045 1143
2.0/100 fids. 1.5/100 fids. <0.004 <0.004 <0.005 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program. Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
y
Bob Garrett, Manager Environmental and Analytical Services ,
Our letters and reports are for the exclusive use of the client to whom they are addressed. The tetters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0 Ls 4102
MAXIM TECHNOLOGIES, INC.
222 Cavalcade Street 77009 * P.O. Box 8768 * Houston, Texas 77249 * (713) 692-9151
Client: Rebecca Perderson Soutwestem Bell Telephone One Bell Plaza, Room 910 Dallas, TX 75265
Client No.: Report No.: 95-10-178 Report Date: 10/17/95
Project: Airborne asbestos samples recieved on 10/17/95. Analyzed on 10/17/95. 1616 GUADALUPE, AUSTIN, TX
Samnle Tvpe/Locarion 01101195; Fan Room #1 02101195; Fan Room #2 03101195; Mech. Room #2 04101195; Mech. Room #3 05101195; Mech. Room#l 09101195; 3rd Floor, Return Air
RESULTS
Sample No. 95-10-178-1 95-10-178-2 95-10-178-3 95-10-178-4 95-10-178-5 95-10-178-6
Volume 937 1212 1204 1085 1142 1432
AC* Fibers/c 0.003 <0.002 <0.002 <0.003 <0.003 0.0015
" AC detnmuned using s mmznsxn 5.5 FB/100 FL RnlisMn QussXiUtim Umtt when spplkabfe. Fibsm/oc sm btadc corrected whsm sppixmbte. Atmlysts porfonnsd by IkN Centrist Microscopy ta scootdsnen with NIOSH MatfaotMoc 7400. Muim Homes is mind proScictt by ths NIOSH Profidsnoy Ansiyticsi Test (PAT) Prognm, Lshornttny i.O. No. 7724M0I: Toils Deptettnont of Hoslth Uosnss No. 304)011, Effective Collection Amn fECA) is oqtml to 3*5.
Analyst:
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0 j 410 3
ittlroti i it lifts
MAXIM TECHNOLOGIES, INC.
222 Cavalcade Street 77009 * P.O. Box 8768 * Houston, Texas 77249 * (713) 692-9151
Client: Rebecca Perderson Soutwestem Bell Telephone One Bell Plaza, Room 910 Dallas, TX 75265
Client No.: Report No.: 95-10-178 Report Date: 10/17/95
Project: Airborne asbestos samples recieved on 10/17/95. Analyzed on 10/17/95. 1616 GUADALUPE, AUSTIN, TX
Samnie Tvoe/Location 01101195; Fan Room #1 02101195; Fan Room #2 03101195; Mech. Room #2 04101195; Mech. Room #3 05101195; Mech. Room #1 09101195; 3rf Floor, Return Air
RESULTS
Sample No. 95-10-178-1 95-10-178-2 95-10-178-3 95-10-178-4 95-10-178-5 95-10-178-6
Volume 937 1212 1204 1085 1142 1432
AC* Fibers/c 0.003 <0.002 <0.002 <0.003 <0.003 0.0015
* AC dcterzsaad usbg a
$.5 F&/100 FL Reliabi# Quaefcitatkxa Limit whom applicable. Ftban/oc are blank oometed whom applicable, Analysis performed by Phase Cociraat Microscopy m accordance with
NIOSH Methodotocy 7400, Maxim Houston is rated proficient by U NIOSH Proficiency Analytical Teat (PAT) Program, Labocuny i.D. No. 7724<MX)l; Texas Departure of Health License No. 30-0)18. Effective
Cofiectkm Area lECA) is equal to 3*5.
Analyst:
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0b4104
SOUTHWESTERN LABORATORIES
Materials, environmental ami geotechnical engineering, noniestructive, metallurgical ami analytical services
2S7S Looa Star Oriva R O. Box 22^227 Dalla. Taxaa 75222 21.4/263-1 133
Report of test on: - As bastes A-'V
10 Date tested:
15
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY WO GRANOC VALLEY ALEXANOWA
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2573 Lons Scar Oriva R O. Box 224227 Dallaa. Taxaa 75222 214/263-1133
Report of test on:
tes Air
/Ol,, Date tested: I 1 (
Type of Activity:
Decontamination
Background
Abatement
Remarks:
004106
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANOE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SwL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.Q. Box 173668 Austin, Texas 78760
Client:
SwL Dallas Attns Robert Garrison
Client No. Report No. Report Date
505092-121
December 20, 1991
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 12/17/91. Analyzed on 12/20/92.
Site: Southwestern Bell Telephone, 201 Cumberland Drive, Austin, Texas
Filter I.D.
1st floor, switch room, west side
1st floor, lounge
2nd floor, switch room
Basement power room
Blank
RESULTS
Swt lab No,
Time (min)
FR (I/ml
C-1 120 10.0
Volumes (liters)
1200
fb/fl 4.0/100
MPA 0.00787
AC* Fiba-s/cm
<0.004
C-2
120 10.0
1200
5.5/100
0.00787 <0.004
C-3
120 10.0
1200
3.0/100
0.00787 <0.004
C-4
120 11.0
1320
1.0/100
0.00787 <0.004
,C-5
,, -2.0/100
0.00787
Remarks:
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dalton Asbestos Coordinator
Our tetters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of testing laboratory. The us* of our name must receive our prior written approval.
fn: ASBDALLAS
00-1107
Su>L
SOUTHWEBTERIM LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
DAILY LOG
Reoort Date:
12/17 /91
To- SwL - Dallas, Attn: Robert Garrison
Project Name: southwestern Bell
Proiact No: 201 Cumberland - Austin, Texas
SwL Time Start:
9:00 a.m.
Stem:
1:00 D.m.
PAGE 1 OF 1
Samole Date:
12/17/91
No. of Samples Taken:
5
Method of Test: NIOSH 7400-A
Suoenntendent:
SwL Technician: Kenneth Williamson
Foreman:
Sample Location
1st floor, switch room, west side
1st floor, lounge
2nd floor, switch room
Basement, power room
Blank
ID C-1
C2 C-3 C-4
C5
Time Start
9:53 am
Time Stop
Total Time fmin)
11:53 am 120
Flow Rate (I/m)
10.0
Volume (liters)
1200
Fibers/ Field
4.0/100
MFA 0.00787
F/'cc <0.004
9:56 am
11:56 am 120
10:03 am 12:03 pm 120
10.0 1200 10.0 1200
5.5/100 3,0/100
0.00787 0.00787
<0.004 <0.004
10:06 am 12:06 pm 120
11.0 1320
,.
..
1.0/100
0.00787 <0.004
2.0/100
0.00787
Remarks:
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dalton Asbestos Coordinator
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of testing laboratory. The use of our name must receive our pnor written approval.
fn: AS8DALLAS
004108
SOUTHWESTERN! LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 173668 Austin , Texas 78760
Client:
SwL Dallas Attn: Robert Garrison
Report No. Report Date Page
505092-656 June 1, 1992 1 of 1
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 5/28/92 Analyzed on 5/29/92.
Site: Southwestern Bell Telephone 201 Cumberland Street, Austin, Texas
Filter I D. .
2nd floor, switch room
Basement, power room
1st floor, break area
1st floorr switch room
Blank
RESULTS
SwL Lab No.
Time (mini
Hic-1
120
FR SM
11.5
Volumes (liters)
1380
FB/FL 8.0/100
XP
MFA 0,00787
AC*
Fibers/cm3
<0.004
Hic-2 Hic-3
120 11.5 120 12.0
1380 1440
0/100 2.0/100
0.00787 0.00787
<0.004 <0.003
Hic-4
120 12.0
1440
5.5/100
0.00787 <0.003
Hic-5
.
0/100
0.00787
-
AC determined using a minimum 10 FB/100 FL Reliable Quantitation Unit where applicable. Bbers/cc are blank corrected where applicable. Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Methodology 7400.
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of testing laboratory. The use of our name must receive our prior written approval.
C'j4109
S&L
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 224227 2575 lone Star Drive Oallat, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Report Date: Date Received: Report Number:
April 19, 993 April 16, 993 9304159
, Vn
9 2,0
'
Identification:
817 North Loop, Austin, TX
SAMPLE NO. 01041393 02041393 03041393 04041393
05041393
06041393 07041393 08041393
LOCATION Switch Room, 1st floor, 5 E area
Switch Room, 1st floor, ESS area Switch Room, 1st floor. Frame area Basement, Mechanical Room, Air Handler Room i Basement, work area outside Mechanical Room 2 2nd floor, A/H Room Field blank Field blank
VOLUME fLl 1080 1080 1080 1080
FIBERS PER CC <0.005 <0.005 <0.005 <0.005
1080
<0.005
1080
<0.005 0.0/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
at*
Our letters and reports ate for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
G j 41 j 0
C00aDbd
iba/ns
sz-.zi
rts-
S&L
SOUTHWESTERN LABORATORIES
MmtMt, mmkmmtuM mi gtmtduied mgumrkt, maiutrmlm m&tallmrtlad mat mtslfticei itmm
9.0. Vox mm zsn tone star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bel Telephone Attention: Gladys Haeckef 7159 Sen Pedro, Room 108 Sen Antonio, TX 78216
Report Date
DateKaceived: Report Nwnbar:
April 19, 1893
April 16,1993 9304189
i
Identification:
817 North loop, Austin, IX
SAMEUm 01041393 02041393 03041393 04041393
05041393
06041393 07041393 08041393
MCATTO Switch Reoes, in Boor, 3 S am
Switch Room, lit floor, ESS am Switch Room, 1st floor, Frame am
Baseeml. MechankalRoooi, Air Hasdkr Roots i
lutncot, work am outside Medunial Room 2 2nd floor, A/H Rots Field Mack
Field Made
Ii 1080
QSBW <0.005
1080 <0.005
1080 <0.005
1010 <0.005
1080 <0.005
1080 <0.005 0.0/100 fids. 1,0/100 fids.
AimJygiparf:<fsrf%, Cw&mit
rUMt iws&sta by A* HIOCH Fwniy AntSPlMTett (PAT)
Matted 7409. Swi.DUhte
UUmmf I.D. Ne. 13213401.
Analyst!
20d 80tt
ISBl 036 PIS :0N HI
SOUTHWESTERN LABORATORIES, INC.
Services
Tht kmc* < wpasw 6tl not N Tte ntfwianiMi^awr4Mtef^iiv4
"wa/ms
CjIUI
ai vz'.zx mi 6-9@-Atw
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Drive P . Box 224227 Dallas. Texas 75222 214/263-1 133
Report of test on:
Date tested:
Project: X P -3 ' 3
Lab Number:
Type of Activity:
Decontamination /^Background
Remarks< 11ft
'1
'}Y
l.kb.&________ If //cUi
Abatement
C
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANGE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2573 Lone Star Drive R . Box 22-4227 Dallas. Texas 75222 21-4/263-1 133
Report of test on: -
Date tested: /--/$
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 173668 Austin, Texas 78760
Client:
SwL Dallas Attn: Robert Garrison
Report No. Report Date Page
505092-656 June 1, 1992 1 of 1
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 5/27/92 Analyzed on 5/29/92.
Site: Southwestern Bell Telephone, 817 North Loop, Austin, Texas
XP3b 10
RESULTS
Filter 1.0.
1st floor, switch room
SwL Lab No.
Time (min)
NL-1 120
FR (I/m)
12.0
Volumes (liters)
1440
EML
5.0/100
MFA 0.00787
AC* Fibers/cm'
<0.003
Basement, old work area, east side of bldg.
NL-2
120 11.5
1380
3.5/100
0.00787 <0.004
Basement, power room 2nd floor, work area
NL-3 NL-4
120 11.5 120 12.0
1380 1440
1.0/100 8.0/100
0.00787 0.00787
<0.004 <0.003
Blank
NL-5
,,
0/100
0.00787
,
u
*AC determined using a minimum 10 FB/10Q FL Reliable Quantitation Unit where applicable. Flbers/cc are blank corrected where applicable. Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Methodology 7400.
!>
Our letters and repons are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of testing laboratory. The use of our name must receive our prior written approval.
Cj4114
S&L
SOUTHWESTERN LABORATORIES
Client:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 173668 # Austin, Texas 78760
,/
7 2L
SwL Dallas Attn: Robert Garrison
Client No. Report No. Report Date
505092-121
December 20, 1991
3 <L
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 12/19/91. Analyzed on 12/20/92.
Site: Southwestern Bell Telephone, 817 North Loop Drive, Austin, Texas
Filter I.D.
Basement, work area
Basement, power room
2nd floor at mechanical room #4
1st floor, switch room
Blank
RESULTS
SwL Lab No.
Time (mini
FR (I/m)
NL-1 127 10.0
NL-2
126 10.0
NL-3 120 10.0
Volumes (liters)
1270
1260
1200
FB/FL 9.5/100 2.0/100 4.0/100
MFA 0.00787 0.00787 0.00787
AC* Fibers/cm'
<0,004
<0.004
<0.004
NL-4
121 11.0
1331
5.0/100
0,00787 <0.004
NL-5
,,
,,
0/100
0.00787
Remarks:
SOUTHWESTERN LABORATORIES, INC.
Robert N. Datton Asbestos Coordinator
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of testing laboratory. The use of our name must receive our prior written approval.
fn: ASBDALLAS
004115
><vL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
DAILY LOG .
Reoort Data:
12/19/91
To: suL - Dallas. Attn: Robert Garrison
Protect Name: Southwestern Bell
Protect No: 817 N. Lood - Austin. Texas
SwL Time Start:
8:00 a.m.
StoD:
12:00 D.m.
PAGE 1 OF 1
SamDle Date:
12/19/91
No. of Samples Taken:
5
Method of Test: MIOSH 7400-A
Superintendent:
SwL Technician: Kenneth Williamson
Foreman:
Sample Location
Basement, work area
Basement, power room
2nd floor at mechanical room #4
1st floor, switch room
Blank
- IP-
NL-1 NL-2 NL-3
NL4
NL-5
Time Start
9:53 am
9:55 am
10.05 am
Time Stop
Total Time (min)
12:00 pm 127
12:01 pm 126
12:05 pm 120
Row Rate (l/m)
10.0
10.0
10.0
Volume (liters)
1270
1260
1200
Fibers/
9.5/100 2.0/100 4.0/100
MFA 0.00787 0.00787 0.00787
F/cc <0.004 <0.004 <0.004
10:07 am 12:08 pm 121
11.0 1331
5.0/100 0/100
0,00787 <0,004
0.00787
.
Remarks:
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dalton Asbestos Coordinator
Hilary D. Johns Senior Programs^Marjager,
Our letters and reports are for ths exclusive use of the client to whom they are addressed. The letters and reports shall not Be reproduced except in full without the approval of testing laboratory. The use of our name must receive our prior written approval.
fn: ASBOALLAS
C u 4116
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2S75 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 2, 1992 June 29, 1992 9206274
Identification:
11258 Pellicano, Ei Paso, Texas
On June 25, 1992 a representative from Southwestern Laboratories Inc., ISwL) was at the Southwestern Beil facility located at 11258 Pellicano in El Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
062592 SBPW-01 Field blank
2.0/100 fids.
062592 SBPW-02 Field blank
2.0/100 fids.
062592 SBPW-03 Conference Room
1307 <0.004
062592 SBPW-04 Office/Copy Room
1328
<0.004
062592 SBPW-05 Telephone/Storage. Room
1297 0.005
062592 SBPW-06 Public Services
1307 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst
Bob Garrett, Manager :kz Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shill not be reproduced except in hill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Gu4117
SOUTHWESTERfy LABORATORIES /"
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 2, 1992 June 29, 1992 9206272
Identification:
520 Ivey, Ei Paso, Texas
On June 23, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 520 Ivey in El Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMELEMQa 062392 SBI-01
LOCATION Field blank
VOLiaiEILl
FIBERS PER CC 1.0/100 fids.
062392 SBI-02
Field blank
3.0/100 fids.
062392 SBI-03
Switch Room, E.S.S., south end
1359 <0.004
062392 SBI-04
Switch Room, E.S.S., north end
1359 <0.004
062392 SBI-05
Equipment Area, south end
1370
<0.003
062392 SBI-06
Equipment Area, north end
1359 <0.004
062392 SBI-07
Emergency Engine Room
1390
<0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst
fhdt..
Bob Garrett, Manager :kz Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
G 1)4118
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 e 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Identification:
510 Texas, Ei Paso, Texas
Report Date: Date Received: Report Number:
July 3, 1992 June 29, 1992 9206277
ftft 0
On June 26, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 510 Texas in El Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
sample NO,
LOCATION
VOLUME (L) FIBERS PER CC
062692 SBT-01
Field blank
0.0/100 fids.
062692 SBT-02
Field blank
0.0/100 fids.
062692 SBT-03
Basement, Mechanical Room B27
1308 <0.004
062692 SBT-04
Basement, Mechanical Room B28
1308 <0.004
062692 SBT-05
Basement, Mechanical Room B12
1308 <0.004
062692 SBT-06
Basement, Mechanical Room L87
1277 <0.004
062692 SBT-07
Basement, Mechanical Room L54
1297 <0.004
062692 SBT-08
3rd floor. Mechanical Room 349 '
1443 <0.003
062692 SBT-09
3rd floor, Mechanical Room 351
1412
<0.003
062692 SBT-10
1st floor, Mechanical Room 110A *
1412
<0.003
062692 SBT-11
1st floor. Mechanical Room 113B ^
1391 <0.003
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program. Laboratory i.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager Environmental and Analytical Services
Our letters and reporti are for the exclusive use of the client whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing loratory. The use of our name must receive our prior written approval.
Co4119
S<v
J' SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 224227 2575 Lone Star Drive Dallas, lexas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Identification:
510 Texas, El Paso, Texas
Report Date: Date Received: Report Number:
November 10, 1992 November 9, 1992 9211075
AAoo$o
On November 5, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 510 Texas in El Paso, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMFLENa
LOCATION
VOLUME (LI FIBERS PER CC
110592 SWB-01
Field blank
2.0/100 fids.
110592 SWB-02
Field blank
0.0/100 fids.
110592 SWB-03 110592 SWB-04
1st floor. Mechanical Room 110A
1st floor, Room 105
1222 <0.004 1073 <0.004
110592 SWB-05
1st floor, Room 111A
1272
<0.004
110592 SWB-06
1st floor. Room 137, Residential ,, Billing
1201 <0.004
110592 SWB-07
1st floor. Room 146, near Room 146A
1128
0.005
110592 SWB-08
1st floor. Room 146, opposite end of room from SBT-G7
1015 0.005
110592 SWB-09
3rd floor, Room 314
1032
<0.005
110592 SWB-10
3rd floor, Room 331
1014
0.005
110592 SWB-11
3rd floor. Auditorium
1006 <0.005
110592 SWB-12
3rd floor, Room 328
1110 <0.004
110592 SWB-13
3rd floor, Room 310
1014 <0.005
110592 SWB-14
3rd floor, Room 300
996 <0.004
110592 SWB-15
5th floor, Emergency Generator Room
1112
<0.004
Gj4120
SOUTHWESTERN LABORATORIES, INC
Report No: Report of: Reported to: PAGE 2 of 2
9211075 Air Monitoring Southwestern Beil Telephone
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
110592 SWB-16 110592 SWB-17 110592 SWB-18
5th floor, AHU Room near Control Panel 5th floor, AHU Room near fan 5th floor. Room 504
1112 1023 1147
<0.004 <0.005 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Kyle Burroughs
:kz
Environmental and
Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in hill without the approval of the testing laboratory. The uae of our name muit receive our prior written approval.
004121
\
!
c
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services 2573 Lone Star Drive P . Box 224227 Dallas, Texas 75222 214/263-1 1 33
XAdd^o
Report of test on: y
C Project: 06; C
<?(
n
J_uLc2i>
Date tested;/- ~r\3~Lf ] Lab Number:
Sample Number / ID
d>
ts} 0
Location
fb XI
L
/Yj i L
I Y\ I.-VV
"VS
Vo
DV
ft v
ft X?
fV
Ay ^ ^ i\ f vn~K
nl L_
/h i rt^r K D
XX. .
iV
l| *1
X
L-V 7
JaLtk.XT
(7
<0
0^ t c 0
A tf-4
\l
Technician
H tS
Pump
Number Time
Flow
and Det. Volume Limit
\ Off | jo
r% On ^
L/Min
> Elapsed !0
0 1j ' L
off ii f.6
On ^ J L/Hin
A'
w
f
aV
Elapsed ii
0ff /
On q >0
Elapsed
", n
L
f0 L/Min /^
L
0ff/ vr
On a \ l)
V
}!L
Elapsed nof
Off ^ V_^*
l H { >
A1 EUpsed
v
<4-V
L/Min
/X L
L/Min l U%0
L
Fibers Fibers per per Field cc
Analyst:
Chain of Custody:
CIH/IH:
_________ *
________
Manager:
Type of Activity:
Decontamination____ Background
Remarks vWJti
-YxL iLJJ
^ x L.
---------- ,,,lfflir....lnnf:...............I-.
/J *'
fA'
A"f\-
Abatement
Gj4122
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV Rio GRANDE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MIOUANO MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lane Star Drive P O. Box 224227 Dallas. Texas 75222 214/263-1 133
nReport of test on: ^
03 6
Project:
i !f
u < A.t _
pf P
L-<' /ht oD
Date tested: Lab Number:
Sample Number / ID
"V4 ho
Location ^ (/
\
. <)t)'
h i l-/iw C-A- yLx*--J-
X V. A '<Ua^ P U&J?
\ "7
,ip r>'
,rP / fc ..Q'V
fa
\,
A\) /.
,jfV ^L(. ^>1 gS^c-V-.
.o ft
'Piir'
fa Ml
1 O.i IdJeauVi?
Pump Number Time
Flow and Volume
Det.
Limit
u 0ff/;5S u
On^
L/Min
'll H
4 vgr\
y
. V'
Elapsed
J~7
Of^
On .
- \
Elapsed 7 * u
Oft. ./*
i-"*
On, <- \ Elapsed
ft) fa L
W0
L/Min
L
>-/, J
L/Min
/6) fa L
On?-7,;
fa Elapsed
Off ^
fa a-.-'3 0n O) 0\ JJ
, -7 ' Elapsed 3 7,
(/ 0
L/Min
A>?> L
L/Min /#)
L
Fibers per Field
Fibers per
cc
'.JuldcLp Technician
Analyst:
Chain of Custody:
CIH/IH:
v_________________________ Manager:
Type of Activity: _____Decontamination___ Background Abatement Remarks :fafa" hClttP P/TlP fa/-fa? /' fa 6-
JPt-
j
,>P7v-
C04123
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANOE VALLEV ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
3 < I
SOUTHWESTERN LABORATORIES
iil
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2375 Lone Star Drive P , Sox 224227 Dallas, Texas 75222 21 4/2S3-1 133
AReport of test on: -)( Q 0_____ _________
Date tested: (j> X / ,6
Project: "ST-?
{ilf
Lab Number:
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY WO GRANGE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services Lone Star Drive P O Box 22^22"7 Dallas, Texas 75222 214/263-1 133
Report of test on: -
Date tested: j - ^ T 5
Project: d0
Pcis^o
Lab Number:
Sample Number / ID
Location
Pump Number Time
Flow and Volume
Det. Limit
Fibers per Field
Fibers per cc
X&
A0 \KJ
A
v^
I9"
t ii4 c
-b'
H1?
v1)'
X. , A
,1
!\, a }> 6- </ ^4^
\A .0
*;>
a
13 f
X(LflLflidac;
IX'kX
6
&
Jf / -/Technici1 a-i C.Uf A4' -=uc t v.
Ip 0ff *
On . .
Si 60
Elapsed
i-lo
L/Min
10.8*
L
Off
If.o
?
(Y
On _ . _
Elapsed jL?a
L/Min
J09> 1L
k
i
$
Off 7.^
On avp
Elapsed
9-1&
Y- o
L/Min
/ol* L
Off
<7,
0n S
S'7 Elapsed
CLJd
L/Mi n
Md
L
0ff7:3-> f o
0n'!,> L/Mi n
Elapsed f 6 fo
i
7-16
L
Analyst:
Chain of Custody:
CIH/IH:
Manager:
Type of Activity^ ____ Decontamination Background
Remarksrrr^ nJl-Lif
/" --
AL-l'h
t/
ffjy #
... limAldwil^.lllll.
X'
*
~ Xi- X"7'/ / )7
c
-/A rf f- C
/A A
. \ *3 >v 1
Abatement
& /Ir,
Cj4125
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANOE VAI.I.EV ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Drive P . Box 224227 Dallas. Texas 75222 214/263-1 133
Report of test on: - "){ A do}> d
Date tested: 4? J 1- 1)
Project:
S> & p
c0 0
.tr !
Lab Number: ;
Type cof Activity:
., h-wr-,C"c/?f
- .. ,
Remarks: / > ,
__Decontamination
J z.*
"iy 1 r
>IH_ X'u j
-.4/
<
cV 6r..
_Background_
/cf .
Abatement
Gj4126
HOUSTON PALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. Sox 224227
SOUTHWESTERN LABORA TORIES
2575 lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Report Date: Date Received: Report Number:
July 27, 1993 July 01, 1993 9307010
YA j ; ; o
Identification: 500 Texas, El Paso, Texas
SAMPLE.NO, 01062393. 02062393 03062393 04062393 05062393 06062393
07062393 08062393 09062393 10062393 11062393 12062393 13062393 14062393 15062393 16062393 17062393 18062393
LOCATION
VQLJUMEJL1
Basement, Main Mechanical Room
1080
Basement, Main Mechanical Room
1080
Basement Headquarters, A/H Room
1080
Basement, Headquarters, A/H Room
1080
Basement Headquarters, A/H Room
1080
Basement Headquarters, Mechanical Room, A/H
1080
Basement, Main, Em. Engine Exhaust pipe
1080
Basement, Main, Em. Engine Exhaust pipe
1080
Basement Chiller Room, Basement Main
1080
A/H Room
1080
Pipe Room, 3rd floor
1080
Room 110, pipe chase, 1st floor
1080
Room 137A, Revenue Mgt. Center
1080
Room 137B, Billing Inquiry Center
1080
Room 111, Federal Gov't Marketing
1080
Room 146, center
1080
Room 146, near Room 149
1080
Room 328, Conference Room
1080
FIBERS PER CC <0.005 <0.005 <0.005 <0.005 <0.005 <0.005
<0.005 <0.005 <0.005 <0.005 <0.005 <0.005 <0.005 <0.005 <0.005
0.005 <0.005 <0.005
SOUTHWESTERN LABORATORIES, INC
Report No: Report of: Reported to: PAGE 2 of 2
9307010 Air Monitoring Southwestern Beil Telephone
SAMPLE NO. 19062393 20062393 21062393 22062393 23062393 24062393 25062393
LOCATION Room 331, Forecasting Room 400 Penthouse Roof Room 504 Frank Alanz Office Field Blank Field Blank
VOLUME fL) 1080 1080 1080 1080 1080
FIBERS PER CC <0.005 <0.005 <0.005 <0.005 <0.005 2.0/100 fids. 2.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program. Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
:kz
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
C04128
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
SS7S Lone Star Dnve R O. Box 33A337 Dallas. Texas 75222 214/2S3-1 133
Report of test on: - /kbdS h s
f Moni fry.
lCJ
Date tested: 5/23/T4-
Project: SOO
&( fhso
Adm' ^thtaca Ped&rson
Lab Number:
Sample Number /ID
Location
Pump Number Time
Flow and Det. Volume Limit
Fibers per Field
Fibers per cc
Q/n 5/^
Off fas S2.t ^On <?. (5 L/Mi n
0703*3lif
0/W 52?
27Dom
(33/
Elapsed IW 7
a7 3
L
Off f.S^
7/75 On <7,50 L/Min
Elapsed
3.+0
L
Off
(1/73 On?. 53
Elapsed
> / r'
Off
L/Min
/%0<f
L
4-5Z
C$03^<t
I Do 3*3^
aw
fA
3/8
Technician: __
17/7*
On % S'/ Elapsed
L/Min /<>&
L
Off /(,7'k On/tf.,:^
Elapsed
-ftYTT
4.4/
L/Min
/** L
Analyst:
Chain of Custody:
CIH/IH:
__
Manager:
Type of Activi ty:
Decontamination
Background_____Abatement
Remarks:
HA17W
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANOe VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2573 Lone Scar Drive R Q. Box 224227 Dallam, Texas 75222 214/263-1 133
Report of test on : 4sbeshs klf Mvn,kn/iq
Date tested: ?Jl2
Project: `oOOT^dS ' *L-L Pq^SQ
ft tin Rebecca federsnn
Lab Number:
Sample Number / ID
Location
pom
L S.
02C32^<I t)^0323CW 04032-39^
oo/n
UO.
13oo m
,LMl
Z ^
Pump Number Time
Flow and Det. Volume Limit
Off 4<f7
I457 On ^ 2-3 L/Mi n
Elapsed Off
tol3 L
>4-2.1a
5^ On<f. $ Elapsed
9-'10
Off
L/Min
H50
L
HW
On <?;*>/ Elapsed
<2-7 o
Off
L/Min
/20<f
L
H 27
<yX(of On <? V-o L/Mi n Elapsed /7?
Fibers Fibers per per Field cc
a<?0/W
/2-
Off
132.55
On <-/,
Elapsed
'3-'7o
ti-45
L/Mi n
//% L
Technician: CIH/IH: Type of Activity: Remarks:
Analyst: Manager: Decontamination_____Background
Abatement
Chain of Custody:
Cj4130
HOUSTON OAU-AS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Drive P O. Box 224227 Dallas. Texas 75222 a a 1^/263-1133
Report of test on: - /{S' LeS
4// /Hm /
Date tested:
Project:
0 t-j fdSo ...QjJn: .Rebecca M*?on
Lab Number:
Sample Number /ID
Location
Pump Number Time
Flow and Det. Volume Limit
Fibers Fibers per per Field cc
itawf /M3Z3<7'I !3o3^
Ioom
6^s
--p-----------Atom-
Som $-3o
n/%
NiSt>
M3b
Off
On id-oj Elapsed
Zifa
Off
On /J.jS
Elapsed
i'7 r
Off
On f<):/3 Elapsed
a 60
+*3 L/Mi n
to $7
L
444
L/Min
M3
L
4,4<
L/Min
ffO 2L
fCi)0/n
0^
,55
i 13 7
Mil
On/d)2A L/Min
Elapsed /0f2L
Off H-L3 On /d-2/ L/Min
Elapsed
3no
L
Technician:
________ _
Analyst:
CIH/IH:
_________
Manager:
Type of Activity:
Decontamination Background____ Abatement
Remarks:
Chain of Custody:
G04131
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lon Scar Orive R O. Box 224227 Dalle. Taxes 75222 214/2B3-1 133
Report of test on : -fishesk? fij( Mon i hn\
Date tested: ^^94
Project: SpQ I
, h( P^<>o
________ AMn : fie btdee, Pedtrrm
Lab Number:
Sample Number / ID
Location
Pump Number Time
Flow and Det. Volume Limit
Fibers Fibers per per Field cc
fa 63251if
Off
/7/7 7
On
Elapsed Qlo
Off
<*% L/Min
/AOf l
iic^m
n On /o; JJ L/Min
Elapsed /A3
?; io L
Off A* 37
/cm On /d'.( L/Min
Elapsed in
Slo
L
Off
a**'.
field
On L/Mi n
Elapsed
Off On
L
L/Min
Elapsed
L
Technician:
Analyst:
Chain of Custody:
CIH/IH:
Manager:
Type of Activity:
DecontaminationBackground Abatement
Remarks:
0^4132
HOUSTON * DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY # RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. Sox 224227
SOUTHWESTERN LABORA TORIES
2575 Loot Stir Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
April 11, 1994 March 28, 1994 9403241
Identification:
500 Texas, El Paso, TX
SAMPLE MD. 01032394 02032394 03032394 04032394 05032394 06032394 07032394 08032394 09032394 10032394 11032394 12032394 13032394 14032394 15032394 16032394 17032394
LOCATION Room L54 Room L87 Room L86 Room L86 Room B12 Room B12 Room B28 Room B31 Room B29 Room B18 Room B25 Room B28A Room B30 Room 137 Room 131 Room 339 Room 349
VOLUME (L) 1073 1150 1204 1789 1196 1147 1085 1204 1085 1394 1087 1643 U02 1092 1142 1204 1193
FIBERS PER CC <0.004 <0.004 <0.004 <0.002 <0.004 <0.004 <0.004 <0.004 <0.004 <0.003 <0.004 <0.002 <0.004 <0.004 <0.004 <0.004 <0.004
0'j4133
SOUTHWESTERN LABORATORIES, INC.
Report No: Report of: Reported to: PAGE 2 of 2
9403241 Air Monitoring Southwestern Bell Telephone
SAMPLE NO.
18032394 21032394 22032394
LOCATION
Room 507 Field blank Field blank
VOLUME (L) FIBERS PER CC
1180
<0.004 1.0/100 fids. 0.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400, SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 752124X11.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
Kyle Burroughs'
:kz Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in fitll without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Cj4134
SA &1
SOUTHWESTERN LABORATORIES
6^
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 2, 1992 June 29, 1992 9206270
y Ao$ %i
Identification:
5845 Sean Haggerty, El Paso, Texas
On June 23, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 5845 Sean Haggerty in El Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NCL
LOCATION
VOLUME (L) FIBERS PER CC
062392 SBSH-01
Field blank
1.5/100 fids.
062392 SBSH-02
Field blank
0.0/100 fids.
062392 SBSH-03
Switch Room, north end
1266 <0.004
062392 SBSH-04
Switch Room, south end
1245 <0.004
062392 SBSH-05
Administration Area
1266 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
Environmental and Analytical Services
alCoUei 135 Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
S&L
f\ y
i ,-
P SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
November 10, 1992 November 9, 1992 9211076
Y A oo Ao
Identification:
6045 Griems, El Paso, TX
On November 6, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at
the Southwestern Bell facility located at 6045 Griems in El Paso, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMRCENQ.
LOCATION
VOLUME (L) FIBERS PER CC
110692 SVVB-01
Field blank
0.5/100 fids.
110692 SWB-02
Field blank
1.5/100 fids.
110692 SWB-03
1st floor, Computer Room
1278 <0.004
110692 SWB-04
1st floor, SCC Room at Control desk
1107
<0.004
110692 SWB-05
1st floor, SCC Room at north end
1068 <0.004
110692 SWB-06
1st floor, SCC Room, south end
1050
<0.005
110692 SWB-07
1st floor, SCC File/Library Room
1050 <0.005
110692 SWB-08
1st floor, SCC Storage Room
1050 <0.005
110692 SWB-09
1st floor. Switch Room, north end
931 <0.005
110692 SWB-10
1st floor. Switch Room, south end
1054
<0.005
Analysis performed by Phase Contract Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
004136
Report of: Report to:
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 13, 1992 June 29, 1992 9206273
Identification:
6045 Griems Ct., El Paso, TX
On June 24, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 6045 Griems Ct. in El Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.,
LOCATION
VOLUME (L) FIBERS PI
062492 SBG-01
Field Blank
1.0/100
062492 SBG-02
Field Blank
1.0/100
062492 SBG-03
Basement, Mechanical Room 1-3
1422 0.007
062492 SBG-04
Basement, Printer Room
1432
0.005
062492 SBG-05
Basement, Office
1432
<0.003
062492 SBG-06
Basement, Power Room
1422
<0.003
062492 SBG-07
Basement, Boiler Room
L380 <0.003
062492 SBG-08
3rd floor, Switch Room, north end
1411 <0.003
062492 SBG-09
2nd floor, Switch Room, south end
1463
<0.003
062492 SBG-10
1st floor, Switch Room, north end
1422
0.005
062492 SBG-11
1st floor. Switch Room
1432 <0.003
Analyaia performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Gu4137
S*L
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Loo* Star Drive
P.0. Box 224227, Dallas, Texas 75222
214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Mr. Joey Grubbs One Bell Plaza, Room 910 Dallas, Texas 75202
Report Date: Date Received: Report Number:
December 18, 1991 December 11, 1991 9112129
o 04
Identification:
6045 Griems Ct. , El Paso, Texas
On December 9, 1991 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 6045 Griems Gt. in El Paso, Texas to provide
prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO,
LOCATION
VOLUME fU
FIBERS PER CC
120991 S8G-01 120991 SBG-02 120991 SBG-03 120991 SBG-04 120991 S8G-05 120991 SBG-06 120991 SBG-07
Field blank Field blank Mechanical Room #111, Basement level Mechanical Room #1-2, Basement level Boiler Room, Basement level Mechanical Room #1-3, Basement level Mechanical Room #1-3, Main water cut-offvalve area
1264 1264 1254 1274 1303
0.0/100 fids. 1.0/100 fids. <0.004 <0.004 <0.004 <0.004 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NI0SH Method 7400. SwL Dallas is rated proficient by the N10SH Proficiency Analytical Test (PAT) Program, Laboratory I.D. Mo. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analvs t
///// -A''- /
J
/ -- - rlfrg. -/
V :kz
Bob Garrett, Manager Environmental and Analytical Services
Our letters end reports sre lor the exclusive use of ttie client to whom they are addressed. The letters end reports shall not be reproduced except In full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0j4138
SWL ' P.O. Box 224227
SOUTHWESTERN LABORATORIES
2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Identification:
6045 Griems, El Paso, TX
Report Date: Date Received: Report Number:
July 12, 1993 July 1, 1993 9307005
L(
SAMPLEm 09062493 , 10062493 11062493 12062493 13062493 14062493 15062493 16062493 17062493
LflCAIIQH
Basement, Chiller Room Basement, Air Intake Room Basement, Emergency Engine Room 2nd floor. Switch Room, center 1st floor. Switch Room, center 1st floor, SCC 2nd floor. Lounge Field blank Field blank
vQUIMEjX)
1080 1080 1080 1080 1080 1080 1080
FIBERS PER CC <0.005 <0.005 <0.005 <0.005 <0.005 <0.005 0.007 0.0/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. 3wL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program. Laboratory I.D. No. 75212-001.
i '' 0
SOUTHWESTERN LABORATORIES, INC.
Analyst
._^z
&
Kyi^Byrrou
En^ironmenta^and 'Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
G J 4139
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Scar Drive P O. Box 224227 Dallas. Texas 75222 214/263-1 133
Report of test on
Project:
/-- \
<-c -0 V.
u/
n
L ^2 **
Date tested: Lab Number:
Sample Number / ID
Location
Pump Number Time
Flow and Det. Volume Limit
Fibers Fibers per per Field cc
a i. V
&
fA Off,
lj '^
ruiliv. Kx'Jyk
On , ;J L/Mi n
O. Elapsed / <>jo
O ") )
V
y->
n a u-. * i
mil
=4 S
r
I* HIM IMII
l
ILfr/M
-
Or*
\I
>/
!!,
J I, t,
A
II
"...... 7/i
T*.*
f(-
<;
'i i "S
Off
Vj>->
On. _
Elapsed
1K
fy
CV
\\
Off , 3>
On | j <?
Elapsed
7 . L/Min /7
L
L/Min
L
*> V'
\\9
\ A>A
ofL,? ij j
On ,M
^f
L/Min n
Elapsed /j'S*
OffT, 7, } '/ > On L/Mi n
A Elapsed ,
\
J 1
L
Technician; j d ;>^v ^CULotk' ^ Analyst:
Chain of Custody:
CIH/IH:
v__________ Manager:
Type of Activity: ____ Decontamination
TfV SL&JJ '->,.''7"/
Remarks:
A/
Jt C. { j,0 -- /
Background____ Abatement :3-_AjUuJu-
na-v-
^y>~~lb
HOUSTON DALLAS AUSTIN BEAUMONT CONBOE GALVESTON COUNTY BIO GBANOE VALLEY ALEXANOBIA SAN ANTONIO FORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
Gj4140
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
53^*755 Lnm Star Dnv/ m
ra__ `3*3^537
Report of test on:
00 ^ -;
Date tested: ^ - w
/ i/ <A
Project: Lr L' * i
t'jt
^ / /.U--ri-c-z-
Lab Number: __________
Sample Number / ID
L.
Location
^ J ur-
9$
-V ; -*Lj.
A
n
v
,^7 /"
Pump Number Time
Flow and Det. Volume Limit
Off
on /
Elapsed
I Ac
S
Off . .
K. > '
\' On
LX
Elapsed
Off
/
On
o -- s' lapsed
ij ,, L/Mi n
1 J' L/Min
L
L/Min
Fibers Fibers per per
Field cc
*n> V
A
Off On L/Min 2 Elapsed
Off On L/Min
Elapsed
L
Techniciciaiann:://^/^ / 0!.Ui
/'/VAm 1 yst:
Chain of Custody:
CIH/IH:
________ __ Manager:
Type of Activity:
Decontamination , Background Abatement
Remarks: ,4 4 S>('
xir,^
' -V '
A\,
Si-
L
/
i ..
/ U kJ'
iA A i.O-/t
Go 4141
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANOE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORA TORIES
Report of: Report to:
P.O. Sox 224227 2575 Lon* Star Drive Dallas, Texas 75222 # 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
April 11, 1994 March 28, 1994 9403243
Identification:
6045 Griems, El Paso, TX
SAMPLE NO. 01032494 02032494 03032494 04032494 10032494 11032494
location
Mechanical Room Mechanical Room at main water 2nd floor, Equipment Boiler Room Field blank Field blank
VOLUME (L) 1204 1085 310 1196
FIBERS PER CC <0.004 0.010 <0.015 <0.004 5.0/100 fids. 2.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordsnee with NIOSH Method 7400. SwL Dailss is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:.
:kz Environmental and Analytical Services
Our lettera and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in hill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
GG4142
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical entinetring, nondestructive, metallurgical and analytical services
aS75 Lon Star Drive R , Box 224227 Dallas. Texas 75222 a 214/2B3-1 133
Technician: ___________ __________ Analyst: _____ _________ ___
CIH/IH:
_Manager:
Type of Activity:
Decontamination___ Background Abatement
Remarks:
Chain of Custody: (774143
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GAUVESTON COUNTV RIO GRANDE VALUEV ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SwL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 9, 1992 June 29, 1992 9206276
Identification:
7945 Parral, El Paso, TX
On June 26, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 7945 Parral in El Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
sample nq.
LOCATION
VOLUME (L) FIBERS PER C_G
062692 SBH-01
Field blank
0.5/100 fids.
062692 SBH-02
Field blank
3.0/100 fids.
062692 SBH-03
1st floor. Switch Room
1432 <0.003
062692 SBH-04
Basement, old AHU Room
1391 <0.004
062692 SBH-05
Basement, Emergency Engine Room
1391 <0.004
062692 SBH-06
Basement
1381 <0.004
062692 SBH-07
2nd floor, Switch Room
1360
<0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 752124X31.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
Environmental and Analytical Services
GJ4144
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
/ tS' r U"
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 e 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
November 11, 1992 November 9, 1992 9211077
XX mV
Identification:
7945 Parral, El Paso, TX
On November 6, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 7945 Parral in El Paso, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
gAMPLENO,
LOCATION
VOLUME flL) FIBERS PER CC
110692 SWB-01 Field blank
0.0/100 fids.
110692 SWB-02 Field blank
3.5/100 fids.
110692 SWB-03
1st floor, E.M.S. Switch Room, north end
1128
<0.004
110692 SWB-04 1st floor, E.M.S. Switch Room, south end
1007
<0.005
110692 SWB-05 1st floor, E.M.S. Office
1068
<0.005
110692 SWB-06 1st floor, Spec. Svcs.
1050
<0.005
110692 SWB-07 2nd floor. Mechanical Room
1032
<0.005
110692 SWB-08 2nd floor, 1A-ESS, northeast area
1157 <0.004
110692 SWB-09 2nd floor, 1A-ESS, northwest area
1157 <0.004
110692 SWB-10 2nd floor, 1A-ESS, south end
1204
0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
ib
SOUTHWESTERN LABORATORIES, INC.
Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in fill! without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Gj4145
SWL
P.O. Box 224227
SOUTHWESTERN LABORA TORIES
2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Report Date: Date Receivi ed: Repoirrtjtjfflfcnmber
/V
July 16, 1993 July 1, 1993 9307007
Identification:
7945 Parrai, El Paso, TX
SAMPLE NO, 01062593 02062593 03062593 04062593 05062593 06062593 07062593 08062593 09062593 10062593 11062593
LOCATION Emergency Engine Room, Basement Air Handler Room, Basement Battery Area, Basement Air Chiller Room, Basement 1st floor. Switch Room 1st floor. Switch Room, Adm. Room 1st floor, DMS Area 2nd floor. Frame Room 2nd floor. Mechanical Room, A/H Field blank Field blank
VOLUME fL) 1080 1080 1080 1080 1080 1080 1080 1080 1080
FIBERS PER CC <0.005 <0.005 <0.005 <0.005 0.005 <0.005 <0.005 <0.005 <0.005 0.5/100 fids. 0.5/100 fids.
Analysis performed by Phsae Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
V-
O'
Analyst:
SOUTHWESTERN LABORATORIES, INC.
Our letters and reports are for the exclusive use of the client to whom they~te addressed. The letters and reports shill not be reproduced except in fitll without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Gj4146
}fh
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star drive P O. Box 22-4227 Dallas. Texas 75222 214/263-1 1 33
; Report of test on
QtJLto\d)
Payees
Date tested: U
Project: _______
Lab Number:
Type of Activity:
Decontamination Background____ Abatement
Remarks:
~2/
S.4a<.
/dA--,..S4_^,.
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES (/
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Drive P O Box 224227 Dallas. Texas 75222 214/263-1 133
Report of test on: Xnod)W Project:
e/> Ax-ctw)
Date tested: Lab Number:
Type of Activity:
Decontamination Background____ Abatement ------------------ -------
Remark----
__H1 Sa-r*- ftcLro- /&>
yfs4 ~tk n ^^(_L
C j4148
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANOE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Ks
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
PB75
Star Dnua P O Box 224227 Dallas.
Report of test on:
Date tested: ^ ^ ^
Project:
Lab Number:
Type of Activity:
DecontaminationBackground Abatement ----- ------------- --------
texdhj$<Jip yjfhj Af ficut Lu._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
~7'Sf
__________
004149
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY WO GRANOE VALUEV ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. 80* 224227
SOUTHWESTERN LABORA TORIES
2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
April 11, 1994 March 28, 1994 9403244
Identification:
7945 Parral, El Paso, TX
SAMPLE NO. 05032494 . 06032494 07032494 08032494 09032494 12032494 13032494
LOCATION Sump Room Mechanical Room Boiler Room Engine Room 2nd floor, Mechanical Room Field blank Field blank
VOLUME fL) 1324 1150 1102 1142 1072
FIBERS PER CC <0.003 <0.004 <0.004 <0.004 <0.004 2.0/100 fids. 2.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NTOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 73212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst
:kz Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in ilill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Gj4150
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
ZS7S Lone Scar Drive R O. Box 224227 Dalle. Texas 75222 214/253-1 133
Report of test on: ~A5hes ii /
Date tested: v 2^ rf
Project:
&rr&i 1 faso
Lab Number: ______
CIH/IH: Type of Activity: Remarks:
Manager: Decontamination Background____Abatement
G o -i 151
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2375 Lon Star Oriv IRQ. Box 22-4227 Dallas. Taxaa 75222 21-4/263-1 133
Report of test on :
Li oim, lzri a-A ' J
Project: "7^4 *5
foSSo
y^^nr\. iZu'h<~>c-a--' P^ers-cm
Date tested: 3jZ'fnf
" r
Lab Number:
Sample Number / ID
Location
Pump Number Time
Flow and Det. Volume Limit
Fibers Fibers per per Field cc
IZX/3W<i<l
Off
On L/Min
Elapsed
L
Off
13o37M^
On L/Min Elapsed
Off
On L/Min
Elapsed Off
L
On L/Min
Elapsed
Off On L/Min Elapsed
Technician: CIH/IH: Type of Activity: Remarks:
Analyst: Manager: _Decontamination___ Background_____Abatement
Chain of Custody:
-------------------------------------------------------------------------------------------------------- ---------------
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY RIO GRANOE VALLEY ALEXANDRIA
SAN ANTONIO FORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
StL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 257S Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of:
Air Monitoring
Report to:
Southwestern Bell Telephone Attention: Gladys Haecker
7159 San Pedro, Room 106 San Antonio, Texas 78216
Identification:
Ho
9506^McCombs, El Paso, Texas
Report Date: Date Received: Report Number:
July 2, 1992 June 29, 1992 9206271
/|7kT
On June 23, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 9300 McCombs in El Paso, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME fL) FIBERS PER CC
062392 SBMC-01 Field blank
1.5/100 fids.
062392 SBMC-02 Field blank
0.5/100 fids.
062392 SBMC-03 Lounge/Vending Room
1401 <0.003
062392 SBMC-04 Southwest corner Office
1276 <0.004
Analysis performed by Phase Commit Microscopy in accordance with NIOSH Method 7400. SwL Dallaa ia rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
:kz Environmental and Analytical Services C'j4153
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SwL
SOUTHWESTERN LABORATORIES \ V
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2575 Lone Star Drive Dallas, Texas 75222 e 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
October 30, 1992 October 29, 1992 9210313
/
Identification:
418 Gator, Gruver, TX
On October 28, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 418 Gator in Gruver, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
102892 SWG-01
Field blank
0.5/100 fids.
102892 SWG-02
Field blank
1.0/100 fids.
102892 SWG-03
Southeast area
965 <0.005
102892 SWG-04
West side (center)
1165 <0.004
102892 SWG-05
Center of Room
1157 <0.004
102892 SWG-06
Northeast area at Cell Area
1157 <0.004
102892 SWG-07
Mechanical Room
1148 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
:kz
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Gj4154
SWL
P.Q, Vox 224227
SOUTHWESTERN LABORATORIES
2575 too# Stir Drive DiIIm, Tow* 75222 214/651-2700
Report of; Report to:
Air Monitoring
Southwestern Ml Telephone Attention: Rebecca Pederson One Beil Plaza, Room 910 Dallas, TX 76202
Report Date: Belt Recrired:
Report Numbers
July 7, 1994
June 30, 1994
9406238
Identification:
125 W, Stevenson, Hale Canter
SAMPLE WO, 16062494 062494 062494 17062494
Mechanical Room Field blank #3 Field blank #4 By fmt door
VOLUMES
1193
1220
Qll.JDt IS PER CC <0.004
0.0/100 (Ids. 2.0/100 fids. <0.004
Amiyite performed by Kiw CoMttsS VEetemtpf m wmiaasc widt NIOSH Metkni 7400. SwL P*fe* k nacd prefkiear by rite NIOSH Pioft&maf AMlytfeari Ten (PAT) Program. tebeamty 1.0. No. 73212401.
SOUTHWESTERN LABORATORIES, INC.
Analyslii^^ Industrial Hygiene Technician
Oor team tad lepwm re ftw ifc# eiehiave ue of 4n cliea* la wbom 4wy u
The keen ted rcpwa rtull not be
fcippriiriilof (fee urig latanmy. Tie ost of oor eat owe receive mu prior wriota tppmvil.
PQd T9#
T68T 026 t?I2:0N 131
-wa/ms
:ai 0:1T 0371 trS.-lT-ETltl
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
3373 Lone Star Drive R . Box 33-4337 Dallas. TaxiM 75222 314/3B3-1 133
Report of test on: -
Air
Project: |2-5 Vj.'Sfc+llft'SCflj V~t Afg- Of htjOT'
Date tested: Lab Number:
Sample Number / ID
Location
Pump Number Time
Flow and Det.
Volume Limit
Off <0*1
Elapsed
Off
4*^2-
L/Min
tW3 L
'
^iiLv ..
..................
0*
--
door
On L/Min
Elapsed Off
L
On L/Min
Elapsed Off
L
+52L/Min
-
Elapsed -no
Off
On
t&-0 L
L/Min
Elapsed
L
Fibers Fibers per per Field cc
Technician: _______ ______________ Analyst: ______________ ____
CIH/IH:
______________ Manager:
Type of Activity: ____ Decontamination Background____ Abatement
Remarks:
Chain of Custody:
GJ4156
HOUSTON OALL&S AUSTIN BEAUMONT C0NR08 GALVESTON COUNTV RIO GRANDE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SwL
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 224227 2575 Lone Star Drive
Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 117 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
March 2, 1992 February 25, 1992 9202250
Identification:
324 N. Miles, Hereford, TX
On February 20, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 324 N. Miles in Hereford, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
location
VOLUME. fL) FIBERS PER CC
022092 SBH-01 022092 SBH-02 022092 SBH-03 022092 SBH-04 022092 SBH-05 022092 SBH-06
Field blank Field blank 1st floor. New Switch Room 1st floor, Old Switch Room Basement, near Air Dryer 2nd floor. Fan Room
1283 1395 1395 1385
2.0/100 fids. 3.0/100 fids. <0.004 <0.003 <0.003 <0.003
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program. Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
Environmental and Analytical,Ser
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Sw/
/
ri SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 224227 257b Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
September 30, 1992 August 31, 1992 9208279
Identification:
334 N. Mile, Hereford, TX
On August 27, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 334 N. Mile in Hereford, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME fLI FIBERS PER CC
082792 SBH-01
Field blank
0.0/100 fids.
082792 SBH-02
Field blank
0.5/100 fids.
082792 SBH-03
Basement, Fan Room
1438 <0.003
082792 SBH-04
Basement, Boiler Room
1538 <0.003
082792 SBH-05
Basement, Emergency Eng. Room
1379 <0.003
082792 SBH-06
1st floor. Old Switch Room
1290
<0.004
082792 SBH-07
1st floor, New Switch Room
1270
<0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Anatyst:/^^ K
:kz
KyiajBurtpugl
Environmental and Analytical Services
0 Li 4158
Our lettcn and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in hill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SOUTHWESTERN LABORATORIES
/ Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Identification:
215 E. Franklin, Hillsboro, Texas
Report Date: Date Received: Report Number:
June 11, 1992 June 8, 1992 9206081
Y
On June 8, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 215 E. Franklin in Hillsboro, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO,
LOCATION
yOLUMEJLi FIBERS PER CC
060892 SWBH-01 Field blank
2.0/100 fids.
060892 SWBH-02 Field blank
0.0/100 fids.
060892 SWBH-03 Diesel Fuel and Mechanical Room
1039 <0.005
060892 SWBH-04 Air Handling Room
1039 <0.005
060892 SWBH-05 Switch Room
1039 <0.005 ' \
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory i.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
Environmental and Analytical Services
0^4159
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of:
Air Monitoring
Report to: .
Southwestern Beil Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Identification:
2A
294 W. Campbell, Kermit, TX
Report Date: Date Received: Report Number:
Novembers, 1992 October 29, 1992 9210311
On October 26, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 291 W. Campbell in Kermit, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
vOLmffiiLl FIBERS PER CC
102692 SBK-01
Field blank
2.0/100 fids.
102692 SBK-02
Field blank
0.0/100 fids.
102692 SBK-03
Doorway at AHU Room and Emer. Gen. Room ! 148
<0.004
102692 SBK-04 102692 SBK-05 102692 SBK-06 102692 SBK-07
Southeast comer Switching Room East wall Switching Room North wall Switching Room Cell area near Switching Equipment
1148 1139 1139 957
<0.004 <0.004 <0.004 <0.005
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:!
:kz
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in lull without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SWL ' P.o. Box 224227
SOUTHWESTERN LABORATORIES
2575 lone Star Drive e Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Identification:
210 W. Campbell, Kermit, TX
Report Date: Date Received: Report Number:
, / ; y
/'
August 3, 1993
July 19, 1993 9307160
SAMPLE-NO, 01070793 02070793 03070793 04070793 05070793 06070793 07070793
LOCATION 1st floor. Mechanical Room (Freeland Street) NDS side, frame, back wall NDS side, frame, back wall NDS area (Campbell Street) Field blank Field blank
VOLUME fL> 1080 1080 1080 1080 1080
FIBERS PER CC <0.004 <0.004 <0.004 <0.004 <0.004 3.5/100 fids. 1.5/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
Analyst:
SOUTHWESTERN LABORATORIES, INC.
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in fiill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
GJ4161
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Drive P O. Box 224227 Dallas. Texas
)
Report of test on: "U-
i_^^
75222 214/2B3-1 133 Date tested: (Q7 ~"Q 1 '*7 J>
Project: / f W y,L
2. j L Lw
Lab Number:
/ Type of Activity:
Remarks: - '~Sv ' V X/
Decontamination Background Abatement
/~
^ !s
. '6.
n/ \ ?
//
iLdl2L
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANGE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lonnoe/./SSttar Drive P O Box 224227 Dallas, Texas 75222 214/253-1 133
Report of test on:/[- /_ ' : } ^ . /
Date tested
"'i
Project: V^/U
V
. Q* II' /
/ <.
Lab Number:
Sample Number /ID
C. j'/i'
Location
1 L:
i
.-/*
--r-rr^--
Pump Number Time
Flow
and Det. Volume Li mi t
Off
V L/Min Elapsed
Fibers Fibers per per Field cc
Off On L/Min Elapsed
Off On L/Min Elapsed
Off
On L/Min
Elapsed
L
Off On L/Min
Elapsed
Technician; CIH/IH:
/-- '' X/
"~7....
Analyst: Manager:
Chain of Custody:
Type of Activity:
Decontamination Background Abatement
Remark's?^'-'' .--1." *'
. _-7 , \
\ 7 >:
GJ4163
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANGE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. Sox 224227
SOUTHWESTERN LABORATORIES
2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Identification:
201 W. Campbell, Kermit, TX
SAMPLE NO. 05052494 05052494 #3 #4
LOCATION Switchroom, first floonby heater) Mechanical room, first floor Field blank Field blank
Report Date: Date Received: Report Number:
May 27, 1994 May 27, 1994 9405246
VOLUME (L) 1089 1084
FIBERS FER--CG <0.005 <0.005 0.0/100 flds 0.5/100 flds
Analysis performed by Phase Contrast Microscopy in accordance with NTOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory l.D. No. 75212-001.
TERN LABORATORIES, IN
jLu.
Analyst
iwk*
:bf
KyieiBunpugi
0o4164
Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and report* shall not be
reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2375 Lana Scar Drive IRQ. Box 224227 Dallas. Texas 75222 214/263-1133
Report,of test on:
Anf -lion.- to, ,,;
-)
Date tested:
Project: %?( Uu>
; KgYMi t~
--__________
Pt&rs KebaQ9e & <x tr t
Lab Number:
Sample
cpvo/ lAJ (A^WiP,,bci'i
i --L/
Number / ID Location
Pump Number Time
Flow and Det. Volume Limit
OHoS^^cj [/$ u 5~>21/ Cjtj
/ OtfW\
3*-t F \(Z(bl Itake')
M Urn
JlSi T /. ii.
V, Off On
if.sq
L/Hi n
lapsed 10?"?
mo
I
Off lASX'
1,
On
L/Min
J 1`. o a
t Elapsed
Z.^0
Off
O>
M/ll llr
F 7F-A
nigfyn
On L/Min
Elapsed Off
L
On L/Min
Elapsed
Fibers Fibers per per Field cc
Off On L/Mi n
Elapsed
L
Technician:
Analyst:
CIH/IH:
______ Manager:
Type of Activity: _____ Decontamination Background____ Abatement
Remarks:
Chain of Custody: IkTITSS
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRANOE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH # LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2573 Lana Star Drive P Q. Sox 224227 Dallas, Texas 75222 21 U/2B3-1 133
Report of test on: _________ ______ __
n e *1
Date tested: ' /'- - >
Type of Activity:
Decontamination Background___ _Abatement ------------
-
RewrksMPa. r(iytfwLc Jli~-.
-------------------------
/ tu .
/XoLa. A-
ib
CO4166
HOUSTON niai i Apt AUSTIN BEAUMONT CONROE "jA^EStON COUNTY WO GPANOE VALUEV ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MlOLANU `ONBOe SHREVEPORT TEXARKANA SHERMAN
S*L 6iv
X
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2575 lone Star Drive e Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
Novembers, 1992 October 29, 1992 9210314
Identification:
218 E. Second, Lefors, TX
On October 28, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 218 E. Second in Lefors, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
102892 SBLF-01
Field blank
0.0/100 fids.
102892 SBLF-02
Field blank
0.0/100 fids.
102892 SBLF-03
Northeast comer of room
890 <0.006
102892 SBLF-04
West wall (center)
742 <0.007
102892 SBLF-05
Southeast area of room
881 <0.006
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
Analyst:
SOUTHWESTERN LABORATORIES, INC.
Our letten and reporta are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be
reproduced except in lull without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Gj- 187
191
1 TSOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 17366 Austin, Texas 78760
Client:
SwL Dallas Attn: Tony Robertson
Client No. Report No. Report Date
505093-175 November 3, 1992
Project
Airborne asbestos samples taken by Kenneth Williamson with SwL on 10/27/92. Analyzed on 10/29/92.
Site:
Southwestern Bell Telephone, 909 Colorado St., Austin, Texas 1107 Water St., Bastrop, Texas 309 SW San Antonio St., Lockhard, Texas
RESULTS
FilterJJJL
SwL Lab No.
Time (mini
FR (l/mi
909 Colorado St., Austin, Texas
Old Bldg. Basement Hal <3* Rm. B-24
COL-1
150 11.5
Old Bldg. Basement Power Room
COL-2
150 11.5
Old Bldg. 3rd Floor Elev. Lobby @ Rm. 303
COL-3
147 11.5
Old Bldg. Rm. 301
COL-4
140 11.0
New Bldg. Basement Mech. Rm. #0-1
COL-5
135 11.0
New Bldg. Basement Power Room
COL-6
137 11.5
New Bldg. 1st Floor Rm. 122
COL-7
133 11.5
New Bldg. 1st Floor Beet Rm. 124 (Inside Rm. 122)
COL-6
132 11.5
New Bldg. 5th Floor Bev. Lobby @ Rm. 521
COL-9
132 11.0
New Bldg. 5th Floor Rm. 521
COL-10
135 11.0
New Bldg. 8th Floor Rm. 804
COL-11
135 11.5
Volumes (liters)
1725 1725 1690.5 1540 1485 1575.5 1529.5 1518
1452 1485 1552.5
ia
4.5/100 3.5/100 10.5/100 1.5/100
0/100
2.0/100 2.0/100 2.0/100
1.5/100 1.0/100 6.5/100
MFA
Ebers/gm:
0.00787 <0.003
0.00787 <0.003
0.00787
0.003
0.00787 0.00787
<0.003 <0.003
0.00787 <0.003
0.00787 <0.003
0.00787 <0.003
0.00787 <0.003 0.00787 <0.003 0.00787 <0.003
0j4168
- -P O'-
euLm
Time Swl lab No. (mini
fM-Obtomdo a. Austin.TgaaJCgoU
Nsw Bldg. 8th Floor Bov. Lobby < Rm. 80S
COL-12
137
FWd Blank
COL-13
.
RESULTS
FR Volumts SM (Stars)
11.5 1575.5
--
EML 5.0/100 0/100
11Q?-WtlarJt... 6aatroe-._Iffiai
Switch Boom
SAS-1
Mr Handler Boom
8AS-2
Field Blank
BAS-3
145 m 145 11.5 --
1667.5 1667.5
-
5.0/100 1.0/100 0/100
WLMMLMmLM* South and of Bldg. North and of Bldg. FMd Blank
LOC-1 IOC-2 LOC-3
145 11.5 145 11J
e>
1667.5 1667.5
1.5/100 3.0/100 0/100
AC* MFA E&%l223
0.00787 *0.003
0.00787
%*
MOT*? *0.003
0.00787
0.00787
A
0.00787 <0.003 "~ T
0.00787 p ^ <o.oo3y
-7 .5
r --
0.00787
I
I "K determined using a minimum 10 FB/100 Ft AeSable Quantitation Unit wnw* applicable. FKswitfcc art btanit eerreetad where appScabte.
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dalton Asbestos Coordinator
Hilary D. Johns Senior Programs Mi
Our letter* end reports ar* for the exclusive us* of the dent to whom they art addressed. The letters and reports aha* not be reproduced except In Ml wfthout the approval of testing laboratory. The use of our name must receive our prior written approval
\#
v.
004169
SOUTHWESTERN LABORATORIES
<
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 # 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 1, 1992 June 19, 1992 9206185
X? *'3 ?
Identification:
2010 Ave. R, Lubbock, Texas
On June 18, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 2010 Ave. R in Lubbock, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE.NO.
LOCATION
VOLUME (L) FIBERS PER CC
061892 SBLR-01
Field blank
3.0/100 fids.
061892 SBLR-02
Field blank
3.0/100 fids.
061892 SBLR-03
3rd floor, A/C duct shaft Room 327
1146 <0.004
061892 SBLR-04
3rd floor, pipe chase
1146 <0.004
061892 SBLR-05 061892 SBLR-06
1st floor, A/C duct shaft 1st floor, pipe chase
1795 <0.003 1088 <0.004
061892 SBLR-07
Basement, Mechanical Room No. 1
1231 <0.004
061892 SBLR-08
Basement, Large Mechanical Room, north end
1231 <0.004
061892 SBLR-09
Basement, Large Mechanical Room, south end
1241 <0.004
061892 SBLR-10
Basement, Boiler Room
1203 <0.004'
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
Environmental and Analytical Services
Gj4170
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in lull without the approval of the testing laboratory. The use of our name must receive our prior written approval.
S&L
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
,4 5
June 24, 1992 June 19,1992 9206184
Identification:
1405 Main, Lubbock, TX
On June 17, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 1405 Main in Lubbock, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME fL) FIBERS PER CC
061792 SBL-01
Field blank
0.0/100 fids.
061792 SBL-02
Field blank
1.0/100 fids.
v 061792 SBL-03
/ y 061792 SBL-04
Basement, Sherwood Bldg., Boiler Room 011
Basement, Sherwood Bldg., AHU Room SO 12
1327 1298
<0.004 0.005
061792 SBL-05
Basement, Porter Bldg., AHU Room 003
1346
<0.004
061792 SBL-06
Basement, Porter Bldg., Cell Area
1375 <0.003
061792 SBL-07
Basement, Porter Bldg., Pump Area, Room 001
1317 <0.004
061792 SBL-08
Basement, Porter Bldg., Large Pump Room 001
1298 <0.004
061792 SBL-09
Basement, Porter Bldg., Boiler Room
1279 <0.004
, 061792 SBL-10
1st floor, Sherwood Bldg., AHU Room 101
1442
0.004
v 061792 SBL-11
1st floor, Porter/Sherwood Bldg., west Mechanical Room 10S
1298 <0.004
C 061792 SBL-12
1st floor, Porter/Sherwood Bldg., [_Occt0
south Mechanical Room 125-B
1298
<0.004
C 061792 SBL-13
1st floor, Porter/Sherwood Bldg., abandoned Switching Room
, uCg
1403
<0.003
KJ 061792 SBL-14
3rd floor, Sherwood Bldg., area used
to be a AHU Room (
......----
1317
0.007
0^4171
SOUTHWESTERN LABORATORIES, INC
Report No: Report of: Reported to: PAGE 2 of 2
9206184 Air Monitoring Southwestern Bell Telephone
SAMPLE NO.
LOCATION
061792 SBL-15 061792 SBL-16 061792 SBL-17 061792 SBL-18 061792 SBL-19 061792 SBL-20 061792 SBL-21
3rd floor, Porter/Sherwood Bldg., west Mechanical Room 305
3rd floor, Porter/Sherwood Bldg., south Mechanical Room 325B
5th floor, Sherwood Bldg., area used to be a AHU Room S504
5th floor, Porter Bldg., Room P501
3rd floor. Porter Bldg., Emergency Engine Room
3rd floor. Porter Bldg., Mechanical Room 307
3rd floor, Porter Bldg., Fan Room Room 307
VOLUME (L) FIBERS PER CC
1327 <0.004
1317 <0.004
1270 <0.004
1241 1212
<0.004 <0.004
1231 <0.004
1241 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400, SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
:kz Environmental and Analytical Services
Cj4172
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0 i/
S&1 lb
IA>SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Sox 224227 2575 lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Identification:
1405 Main, Lubbock, TX
Report Date: Date Received: Report Number:
November 5, 1992 October 29, 1992 9210312
2J 7 S
On October 27, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 1405 Main in Lubbock, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO. 102792 SBL-01
LOCATION Field blank
VOLUME fL)
FIBERS PER CC 1.0/100 fids.
102792 SBL-02
Field blank
0.0/100 fids.
102792 SBL-03
Sherwood Bldg., 1st floor, AHU, Room 101
1095 <0.004
102792 SBL-04
Porter-Sherwood Bldg., 1st floor, AC Power Room
1086
<0.005
102792 SBL-05
Porter Bldg., 1st floor, old AT &T Long Distance Room
928 0.006
102792 SBL-06
Void
- 102792 SBL-07
Porter-Sherwood, 3rd floor. Break Room
1210
<0.004
102792 SBL-08
Porter-Sherwood, AHU Room 002, Basement
816
<0.006
* 102792 SBL-09
Porter-Sherwood, Supply Air Duct, Room 002, Basement
970 <0.005
` 102792 SBL-10
Sherwood Bldg., 2nd floor, AHU Room 216
1068
<0.005
102792 SBL-11 7 102792 SBL-12
Porter-Sherwood Bldg., Mechanical Room 325-B
Porter-Sherwood Bldg., Mechanical Room 304
961 <0.005 952 <0.005
' 102792 SBL-13
Porter Bldg., 5th floor, hallway
1121 <0.004
004173
SOUTHWESTERN LABORATORIES, INC
Report No: Report of: Reported to: PAGE 2 of 2
9210312 Air Monitoring Southwestern Bell Telephone
SAMPLE NO.
102792 SBL-14 102792 SBL-15 102792 SBL-16 102792 SBL-17
LOCATION
Porter Bldg., 5th floor. Room S501 Porter Bldg., 5th floor. Room S505 Sherwood Bldg., 5th floor, hallway Sherwood Bldg., 5th floor. Mechanical Room
VOLUME (L) FIBERS PER CC
905 1059 988 935
<0.005 <0.005 <0.005 <0.005
Analyst! performed by Phase Contrast Microscopy In accordance with MIOSH Method 7400. SwL Dallas is riled proficient by the NIOSH Proficiency Analytical Tert (PAT) Program, Laboratory I.D. No. 75212-001.
Analyst: GMJLfy,
:kz
Our leoen and report, arc for the exclusive urn of the elkat to whom they are tddmmd. The keen and repost* ahall not b
foil receive priorreproduced except in without the approval of the testing laboratory. The um ofournuna mum
our written approval.
/< r ^ S&L
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Loo* Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
April 12, 1993 April 7, 1993 9304060
Identification:
1405 Main, Lubbock, TX
SAMPLE NO, 01032993 02032993 03032993 04032993 05032993 06032993 07032993 08032993 09032993 10032993 11032993 12032993 13032993
LOCATION
VOLUME (L)
Basement, Sherwood Bldg., Boiler Room #011
1080
Basement, Sherwood Bldg., AHU Room #S012
1080
1st floor, Porter/Sherwood west Mechanical Room #105
1388
1st floor, Porter/Sherwood south Mechanical Room #125B
VOID
1st floor, Porter/Sherwood abandoned Switching Room
VOID
3rd floor, Porter/Sherwood west Mechanical Room #305
1080
3rd floor, Porter/Sherwood south Mechanical Room #325B
1304
1st floor, Sherwood Bldg., AHU Room 101
1080
3rd floor, Sherwood Bldg., area used to be AHU Room
1420
5th floor, Sherwood Bldg., area used to be AHU Room
1080
3rd floor. Porter Bldg., Emergency Engine Room
3rd floor. Porter Bldg., Mechanical Room 307
3rd floor, Porter Bldg., Fan Room 307
1080
FIBERS PER CC 0.006
<0.004 <0.003
<0.004 <0.004 <0.004
0.003 <0.004
1220 0.004 1080 <0.004 <0.004
17"
SOUTHWESTERN LABORATORIES, INC
Report No: Report of: Reported to:
PAGE 2 of 2
9304060 Air Monitoring Southwestern Bell Telephone
SAMPLE NO. 14032993 15032993 01033093 02033093 03033093 04033093
05033093
06033093
LOCATION
VOLUME (L)
Field blank
Field blank
Basement, Porter Bldg.
1080
Basement, Porter Bldg., Mechanical Room
1080
5th floor. Porter Bldg.
1040
Basement, Porter Bldg., Equipment Room Center
Basement, Porter Bldg., Equipment Room West
1000 1040
Basement, Porter Bldg., Boiler Room
1040
FIBERS PER CC 1.0/100 fids. 1.0/100 fids.
<0.004 <0.004 <0.004 <0.004
<0.004
<0.004
Analysis performed by Phaaa Cootnu* Microscopy in accordance with NIOSH Method 7400. SwL Dellas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analytical Services beOur Istten and reports am for the exclusive use of tbs client to whom they am addmsatd. The Setters and reports dull not
reproduced except in full without the approval of the Ming laboratory. The urn of our mam must receive our prior written approval.
GJ4176
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical tntinetring, nondestructive, metallurgical and analytical services
2573 Lorw Star Drive R D. Box 224227 Dallas. Taxas 75222 214/253-1133
Report of test on: -,A.sb^fcA f
Date tested: ^j
Project: 1406 frw^
Lab Number: ________
Sample Number / ID
ClCfcHW
Location
^kluLU.
T MMtm
Mjl\...
'Skuu,VJL>~tT~i
3<hi
B-LtL feto
t&bl'WH
1HA, "11 r $
Pump Number Time
Flow and Det.
Volume Limit
Off
Ortf.ao
Elapsed
snc
Off
W L/Min
/lof
L
M 0n<fA3 L/Min
Elapsed /2>
3lo
L
Off f.5b
Oi
13 m
lWc
L/Min
i%iS L
Off Hi
mi Oi^f -5 ^ L/Min Elapsed /AJ2Jinc L Off
lini otf/W7 L/Min
Elapsed
L
1
Fibers Fibers per per Field cc
k. *1+n,
Technician: __________ ____________ Analyst:
CIH/IH:
_____________ _________ Manager: _______________ ___
Type of Activity: ____Decontamination Background Abatement
Remarks:
Chain of Custody:
0^4177
HOUSTON CMUJkS AUSTIN BEAUMONT CONROE GALVESTON COUNTY WO GRAND* VALLEY ALEXANORLA SAN ANTONIO FORT WORTH LEESVILLE MIOUANO MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN' LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2573 Lon* Sear Drive R O. Box 224227 Dallas, Taxaa 75222 214/283-1 133
Report of test on:
Date tested:
CIH/IH:
Manager:
Type of Activity: ____ Decontamination^___ Background
Remarks:
Abatement
Gj3T7S
HOUSTON PALLAS AUSTIN SISAUMONT CONROE 8ALVSSTON COUNTV MO ORANGE VAULEV AlEXANOA SAN ANTONIO FORT WORTH LSESVIU-E MtOCANO MONPfOK SHREVEPORT TEXARKANA SHERMAN
/, 8SC- - 3 % -JL'3^ ^>oC ^ 7$
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2373 Lone Scar Drive IRQ Box 224227 Delta. Texas 75222 214/263-1133
Report of test on: -(,LliS ^XL-'b
\Nv
Date tested:
'C* ^
Project:
-:o6 ,
} Li
Lab Number:
Technician:
_____ _
Analyst: --
Chain of Custody:
CIH/IH:
__________________ _
Manager: ______ -------------------------------------
--
Type of Activity: ____ Decontamination^___ Background Abatement -------
--
Remarks:
........... q...
HOUSTON tMLUS AUSTIN # WEAUMQNT CONROS OALVSSTON COUNTY BO SBANOS VAULITY AtSXANQA SAN ANTONIO XOBT WOBTH LECSVIUUE MQLANO MONBOS SHBeVSPOBT TBXABKANA SMUMMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
23-73 Lone Sear Driva R O. Box 224227 Dallas. Taxas 75222 a 214/2B3-1 133
Report of test on:
Date tested:
Project:
Lab Number:
Sample Number / ID
Location
Pump Number Time
Plow and Det.
Volume Limit
Off
On Elapsed
Off
L/Min L
On L/Min
Elapsed Off
L
On L/Min Elapsed
Fibers Fibers per per
Field cc
Off
On L/Min
Elapsed
Off On
L L/Min
Elapsed
L
Technician: Analyst:
Chain of Custody:
CIH/IH:
Manager:
__________
Type of Activity: ____ Decontamination Background Abatement
Remarks:
G..,u 4J...8H
HOUSTON QAIAAS AUSTIN BKAUMONT CONROE GALVESTON COUNTV WO BRANDS VALLBY ALEXANDRIA SAN ANTONIO FORT WORTH LEESV1LLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
SWL
P.O. Box 224227
SOUTHWESTERN LABORATORIES
2575 tone Star Drive e Dallas, Texas 75222 e 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, IX 75202
Report Date: Date Received: Report Number:
July 7, 1994 June 30, 1994 9406237
Identification:
1405 M*ip, i lihh'vi', TX
SAMPLE NO. 01062494 02062494 03062494 04062494 05062494 06062494 07062494 08062494 09062494 10062494 11062494 12062494 13062494
14062494 15062494 062494
LOCATION Sherwood, Basement Fan Room Sherwood, Basement Boiler Room Sherwood, 1st floor, Fan Room Sherwood, 3rd floor, old Fan Room Porter, 5th floor, Fan Room Porter, 3rd floor. Mechanical Room Porter, 3rd floor, Fan Room Porter, 3rd floor, Emergency Engine Porter, Basement Boiler Room Porter, Basement Poner, Basement, Air Handler Porter, Basement, Equipment Room Porter Sherwood, 1st floor. Mechanical Room, Room 105 Porter Sherwood, Room 125 Porter Sherwood, 3rd floor Field blank #1
VQLLMEiL) 1204 1220 1215 1212 1226 1201 1218 1220 1226 1212 1290 1215 1210
FIBERS PER CC <0.004 <0.004 <0.004 0.007 <0.004 <0.004 <0.004 <0.004 <0.004 <0.004 <0.004 <0,004 <0.004
310 <0.006 1153 <0.004
1.0/100 fids.
Gj4181
SOUTHWESTERN LABORATORIES, INC.
Report No: Report of: Reported to: PAGE 2 of 2
9406237 Air Monitoring Southwestern Bell Telephone
SAMPLE, NQ,
LOCATION
VOLUME (L) FIBERS PER CC
062494
Field blank #2
i .0/100 flH,
Analyais performed by Phue Contra* Mkroecopy in accordance with NK5SH Method 7400. SwL Delia* is rated proficient by the N10SH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:,
:kz Industrial Hygiene Technician
Our letter* and reporfj an for the exclusive use of the client to whom they an addnaaad. Tit* lattan and report* dull not be reproduced except in fttll without the approval of the testing khoratoty. The un of our ratine mat receive our prior written approval.
Cj4182
SOUTHWESTERN LABORATORIES
Report of: Report to:
P.O. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Air Monitoring
SOUTHWESTERN BELL TELEPHONE Attn: REBECCA PEDERSON ONE BELL PLAZA, ROOM 910 DALLAS, TX 75202
Report Date: Date Received: Report Number:
May 27, 1994 May 27, 1994 9405242
Identification:
623 EMERSON, MCCAMEY, TX
SAMPLE NO.
LOCATION
VOLUME (LI
FIBERS PER CC
06052394 07052394 08052394 #5 #6
Mechanical room, first floor Switch room, first floor, north Switch room, first floor, south Field blank Field blank
1075 <0.005 1080 <0.005 1078 not received
1.0/100 fids 0.0/100 fids
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
059
Jonathan L. Garrison
:bf
Industrial Hygiene Technician
Analytical Services
Our iettera and reporta are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the tearing laboratory. The am of our name must receive our prior written approval.
C.4183
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical entineering, nondestructive, metallurgical and analytical services
2573 Lon* Scar Driv* p O. Box 224227 Dallam. Taxas 75222 214/263-1 133
Report of test on: - As
h if
Date tested: Tj 2 4* 0
CIH/IH:
______
Type of Activity:
Remarks:
Manager: Decontamination Background
Abatement
004184
HOUSTON! OAU-AS AUSTIN * BEAUMONT CONdOE GALVESTON COUNTV m3 QdANOE VALLEV ALEXANOdIA
SufL
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Sox 224227 2575 Lone Stir Orivo Dal tic, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Report Date: Date Received: Report Number:
April 20, 1993 April 7, 1993 9304065
Identification:
623 Emerson - McCamey, TX
SAMPLEm 01-03-25-93 02-03-25-93 03-03-25-93 04-03-25-93 05-03-25-93 06-03-25-93 07-03-25-93 08-03-25-93 09-03-25-93
LOCATION Mechanical Room Mechanical Room Switchroom near battery plant Switchroom near frame Storeroom Frame Area Switchman's office Field blank Field blank
VQLJJMEIL),
USERS PER CC
1080 <0.005
1080
( <0.005
1080
0.01*
1080
0.02*
1080
0.02*
1080
0.01*
1080
0.02*
0.0/100 fids.
0.5/100 fids.
This sample was found to be over the EPA recommended "clean air' target value of <0.01 f/cc Subsequently, the sample was submitted for Transmission Electron Microscropy (TEM) to determine i the fiber loading was due to asbestos. The TEM analysis revealed that no asbestos fibers wer present.
Anaiyui performed by Hues CootTM* Microscopy is accordance with NIOSH Method 7400. SwL Delias is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
:kz
reproduced except in fill! without the approval of the testing laboratory. The uae of our name smut receive our prior written approval.
Gj4185
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Sear Drive P O Box 224227 Dallas. Texas 75222 e 214/2B3-1 133
Report of test on:
Date tested:
Project: fr
v Hi7 y /j
Lab Number:
Type of Activity
Decontamination Background
Abatement
Stfrfo/ApCj \Rema rk
-
ilieinffiiuiiir .........
"7 /
f
I -fj lJuLLhs3x.
f-
Scu^
AaLj Jq~- _a^
0v4186
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV * O ORANOE VALLEV ALEXANDRIA
SAN ANTONIO PORT WORTH LEESVtLLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
- "J
(j
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
25-75 Lone Sear Drive R O Box 22422'7 Dalles, Texas 75222 214/263-1 133
Report of test on:
' <<k
Date tested: 3' z- r* ^ j
Project: ,,/ /1 C i
' * > ,V ^ /
Lab Number:
Type of Aglfjvity: ____ Decontamination^___ Background Abatement ---------- --
Remarksf A~tt,l'.'
JL *, NaJtL'b^ --------------
,,
7/ff Sa, P,rJ.,-/aL,
VdJk.___^187
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV WO GRANOE VALUEV ALEXANDRIA SAN ANTONIO FORT WORTH LESSVIU..E MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
Huntingdon
Report of: Air Monitoring
Report to:
Southwestern Bell Attention: Rebecca Pederson
One Bell Plaza, Room 910 Dallas, TX 75202
Identification: Midland Drive
SAMPLE ML MKAUOM
01011195
Mechanical Room
02011195
Boiler Room
03011195
Jan Room
#01 Field blank
#02 Field blank
Huntingdon Engineering & Environmental, Inc.
P.O. Box 224227 2575 Lon. Star Onv. T.xa* 75212
T.laphona: (214) 631-2700 FAX: (214) 920-1891
Report Date: Date Received: Report Nimben
February 2, 1995 January 17, 1995 9501121
VQLU&ffilLl 1662 853 1308
<0.003 <0.006 <0.004
1.0/100 fids. 0.5/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by die NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
HUNTINGDON ENGINEERING & ENVIRONMENTAL, INC.
Analyst:
Gregot/M^f
f
Industrial Hygiene Technician :kz
C^TkL
'A/Md
TomBBaammeeas Environmental and Analytical Services
OurImm tadreport*m tvthsaastaiwwsf faeSentto w&osbtSwy anaddmuMl Tit*!mmandreportsauUnotb reproducedtxcept ia M wMmma fa mppcavil of fa Urtnt MkMMoty. Ifaurerf oar Mas must ream* our pnorwriOsa approval.
Gj4188
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical entineering, nondestructive, metallurgical and analytical services
2575 Lean Scar Ortva R O. Box 224227 Delta. Taxaa 75222 si <4/283-1 133
Technician: --________ Analyst: _____
CIH/IH:
_________________
Manager:
Type of Activity:
Decontamination Background____ Abatement
Remarks:
Chain of Custody: Gj4i89
HOUSTON r>Ai i *e AUSTIN BEAUMONT CONROE SALVESTON COUNTV WO ORANOB VALLEV AUXANDBA SAN ANTONIO FORT WORTH LEESV1U.E MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
S&L
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P-0. Box 224227 2575 lone Star Drive * Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Beil Telephone Attention: Gladys Haecker 7159 San Pedro, Room 117 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
March 2, 1992 February 25, 1992 9202246
2.3&0
Identification:
410 W, Missouri, Midland, TX
On February 18, 1992 a representative from Southwestern Laboratories Inc., ISwL) was at the Southwestern Bell facility located at 410 W. Missouri in Midland, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
021892 SBM-01 021892 SBM-02 021892 SBM-03 021892 SBM-04 021892 SBM-05 021892 SBM-06 021892 SBM-07 021892 SBM-08 021892 SBM-09 021892 SBM-10 021892 SBM-ll
Field blank Field blank 1st floor, south side Air Handler Room 1st floor. Equipment Room 2nd floor, south side Air Handler Room 2nd floor. Equipment Room 2nd floor, east side Air Handler Room 5th floor, south side Air Handler Room 5th floor, AT&T Equipment Room 6th floor, south side Air Handler Room 6th floor, ESS/SCC Work area
1113 1227 1246 1236 1006 1116 1125 1125 1088
3.0/100 fids. 1.0/100 fids. <0.004 <0.004 <0.004 <0.004 <0.004 <0.004 <0.004 0.005 0.009
0 4190
SOUTHWESTERN LABORATORIES, INC
Report No: Report of: Reported to: PAGE 2 of 2
9202246 Air Monitoring Southwestern Bell Telephone
sample ml
LOCATION
VOLUME fL) FTBERSPEg_CC
021892 SBM-12
6th floor, east side Mechanical Room
1037
<0.005
`-julyjii performed by Phaac Contrail Microscopy in accordance with NIOSH Method 7400, SwL Dallas ii ated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bo& Garrett, Manager
Environmental and Analytical Services
Our lettera and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name mute receive our prior written approval.
004191
s^i
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. BOX 224227 2575 lone star Drive # Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
D
September 10, 1992 August 31, 1992 9208275
identification:
410 W. Missouri Ave., Midland, TX
On August 24, 1992 a representative from Southwestern Laboratories Inc., (Swl) was at the Southwestern Bell facility located at 410 W. Missouri Ave. in Midland, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
mSAMPLE
LOCATION
YPLUMEJL1 FIBERS,PER,C
082492 SBM-01
Field blank
l.G/TOO lids.
082492 SBM-02
Field blank
0.5/100 fids.
082492 SBM-03
9th floor. Elevator Room
1210 <0.004
082492 SBM-04
7th floor, Mechanical R<x>m, west side
1220 <0.004
082492 SBM-05
7th floor, Mechanical Room, east side
1210 <0.004
082492 SBM-06
7th floor. Boiler Room, southeast comer
1200 <0.004
082492 SBM-07
5th floor, Room 501, east side office area
1220 <0.004
082492 SBM-08
5th floor, Elevator Lobby
1200 <0.004
082492 SBM-09
5th floor, Mechanical Room, south
1220 <0.004
082492 SBM-10
3rd floor, Room 303, Back Office, Public Relations
1220 <0.004
082492 SBM-11
3rd floor, Mechanical Room, east side
1220 <0.004
082492 SBM-12
3rd floor. Foyer, outside 303 & 302 at NCOO door
1210 <0.004
082492 SBM-I3
3rd floor. Toil, east side at Power Cell area
1190 <0.004
0/4192
S*l
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 # 2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
September 10, 1992 August 31, 1992 9208275
Identification:
410 W. Missouri Ave., Midland, TX
On August 24, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 410 W. Missouri Ave. in Midland, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO,
LOCATION
VOLUME (L) FIBERS PER CC
082492 SBM-01
Field blank
1.0/100 fids.
082492 SBM-02
Field blank
0.5/100 fids.
082492 SBM-03
9th floor, Elevator Room
1210
<0.004
082492 SBM-04
7th floor, Mechanical Room, west side
1220
<0.004
082492 SBM-05
7th floor, Mechanical Room, east side
1210
<0.004
082492 SBM-06
7th floor, Boiler Room, southeast comer
1200 <0.004
082492 SBM-07
5th floor. Room 501, east side office area
1220 <0.004
082492 SBM-08
5th floor, Elevator Lobby
1200
<0.004
082492 SBM-09
Sth floor, Mechanical Room, south
1220 <0.004
082492 SBM-10
3rd floor, Room 303, Back Office, Public Relations
1220
<0.004
082492 SBM-11
3rd floor, Mechanical Room, east side
1220
<0.004
082492 SBM-12
3rd floor. Foyer, outside 303 & 302 at NCOO door
1210
<0.004
082492 SBM-13
3rd floor. Toil, east side at Power Cell area
1190
<0.004
0^4193
SOUTHWESTERN LABORATORIES, INC
Report No: Report of: Reported to: PAGE 2 of 2
9208275 Air Monitoring Southwestern Bell Telephone
SAMPLE NO. 082492 SBM-14 082492 SBM-15
082492 SBM-16 082492 SBM-17
LOCATION 3rd floor, Toll, west side 3rd floor, west corridor at water fountain 1st floor, Mail Room 1st floor, east corridor
VOLUME (L) 1280 1309
FIBERS. <0.004 <0.004
1250 1260
<0.004 <0.004
nalysis performed by Phase Contrast Microicopy in accordance with NIOSH Method 7400. SwL Dallas is ted proficient by the NIOSH Proficiency Analytical Test (PAT) Program. Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
nalyst:
:kz
:ytal and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
CJ4194
SOUTHWESTERN LABORATORIES
P.O. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Identification:
410 W. Missouri, Midland, TX
SAMPLE NO. 010052394 02052394 03052394 04052394 05052394 #1 Wl
LOCATION Power room, basement Mechanical room, basement Corridor, fuel storage area, basement First floor, air handler Six floor, air handler, south end Field blank Field blank
Report Date: Date Received: Report Number:
May 27, 1994 May 27, 1994 9405244
VOLUME fL) 1068 1277 1220 1072 1161
FIBERS PER CC <0.005 <0.004 <0.004 <0.005 <0.004 1.0/100 fids 0.0/100 fids
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400, SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, I?
Analyst:
:bf and Analytical Services
Our letters and reports are for the excluaivc use of the client to whom they areWresaed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prnior written appnroval.
X j4i9o
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
23-73 Lone Star Driva R O. Sox 224227 Dalian. Texas 75222 214/203-1 133
Report of test on: -/Wb^ ret, ( U f Mw
Date tested:
Uif
Project: ^ (Q\X)' M t
< l , MiJlct n X.
A&n Ktbrc. (V. P-f
Lab Number:
Sample Number / ID
V It (,' /*V> t -
: Location
f
Flow
Fibers Fibers
Pump
and Det. per per
Number Time Volume Limit Field cc
GU-'l, '< '* *f*
fc'- > A?Stf cr.v.-rf *7,
/ :
y
a
0 1C5J11U4 y
V t, i W;/ ~ Hat I
7'..-. <
jk
r
7,
7 s- f~ /" / >4.. *- /-t i" I'fa t-.j L '
/1
t' 7 * 7- 5 / 7,
"T*' f h ~
5
Off
. Y'O
Elapsed
2 *fO
Off
L/Mi n /0&^
L
On L/Min
h) H5-
Elapsed /?77
^-T
L
Off 7-77
On L/Min
/u 5%
Elapsed /Slxo
2-13
L
Off 7.77
On J J #- V Elapsed
2-HO
L/Min
1072. L
Off
On // /o Elapsed
7.5(7 L/Min
ll<*(
L
y'1 >r- /7
Technician:
L' I P-r\ K -
Analyst:
Chain of Custody:
CIH/IH:
Manager:
Type of Activity:
Decontamination Background____ Abatement
Remarks:
0.4196
HOUSTON DALLAS AUSTIN MAUMQNT CONROE SALVESTON COUNTY WO GRANOE VALLEY ALEXANDRIA. SAN ANTONIO PORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
u-
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Onve P O, Box 224227 Dallas. Texas 75222 21 4/263-1 133
Report of test on: Project: jp Jd
. Vt
Date tested: 3
~ 13
Lab Number: ____________
Type of Activity: Remarks: 7/61
<AAAtfAvA.\ : AMH'l*)>
Decontamination Background____ Abatement /LcL
Js'sLlh.
&J4197
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY WO ORANOE VALLEY ALEXANDRA SAN ANTONIO FORT WORTH LEESVIU.E MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
SS75 Lone Star Drive R O. Box 224227 Dallas. Texas 75222 ai 4/2B3-1 133
Report of test on: - y~/J U,
Project:
Vb 1 i ? A' 3 &
/h^oUa^c/
Date tested: Lab Humber:
Type of Activity:
Decontamination Background____ Abatement - 1 ---------
_________________
--cnj-4i9e
n,rii s-- AcAo-/jc r/7v 7/^.^_______ _________
HOUSTON I-1AI i JL AUSTIN BEAUMONT CONROE GALVESTON COUNTV WO GRANGE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LBESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
Huntingdon
Report of: Air Monitoring
Report to:
Southwestern Bell Attention: Rebecca Pederson One Bell Plata, Room 910 Dallas, TX 75202
Identification; Dawn Avenue -- OcieSScl
01011295 02011295 #05 #06
LOCATION
AC Room Boiler Room Field blank Field blank
Huntingdon Engineering & Environmental, Inc.
P.O. Box 224227 2S7S Lon* Stir Drive Ddlae, Texee 75212
Telephone: (214) 631-2700 FAX: (214) 920-1891
Report Date: Date Received: Report Nianber:
February 2, 1995 January 17, 1995 9501122
VOLUME(L) 1077 1212
FIBERS PER CC <0.005 <0.004
1.0/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
HUNTINGDON ENGINEERING & ENVIRONMENTAL, INC.
Analyst:
Industrial Hygiene Technician :kz
Environmental and Analytical Services
Our bum tad npotts an fcr the xefcwv ua of the cheat to whom they an ed4wa4. The Itmtt tad reporte #ia!l not be reproduced except
iafiiUwiihmiheiippiHr^oftiifttiMh^
Ike use of our name must receive our prior written approval.
G04199
SOUTHWESTERN LABORATORIES
Matenak, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2373 Lon Star Drive P. O. Box 224227 Dellas;. Texas 75222 214/2B3-1133
Technician:
______ __ Analyst: ____________
Chain of Custody:
CIH/IH:
_________________
Manager:
Type of Activity:
Decontamination___ Background Abatement
Remarks:
oo
HOUSTON DALLAS AUSTIN MAUMONT CONROE SALVESTON COUNTY WO ORANOE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH UEBSVIU.E MlOLAND MONROE # SHREVEPORT TEXARKANA RhPRMAm
SwL
p --i
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
September 1, 1992 August 31,1992 9208278
Identification:
601 N. Lincoln, Odessa, TX
On August 26, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 601 N. Lincoln St. in Odessa, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME CL) FIBERS PER CC
082692 SBO-01
Field blank
0.0/100 fids.
082692 SBO-02
Field blank
0.0/100 fids.
082692 SBO-03
3rd floor, work area, 6th St. side
1587
<0.003
082692 SB0-04
3rd floor, work area, 7th St. side
1577
<0.003
082692 SBO-05
3rd floor, work area, Sam Houston St. side
1548
<0.003
082692 SBO-06
3rd floor, work area, Lincoln St. side
1468
<0.003
082692 SBO-07
1st floor, Administration area
1290
<0.004
082692 SBO-08
1st floor, Frame Room, Sam Houston and 6th St. side
1290
<0.004
082692 SBO-09
1st floor, Frame Room, Sam Houston and 7th St. side
1280
<0.004
082692 SBO-10
1st floor. Frame Room
1280
<0.004
Analytis performed by Fhsse Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst :kz nmental and Analytical Services
Oir letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in hill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
G j 4201
f S<
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive # Dallas, Texas 75222 * 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 117 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
March 2, 1992 February 25, 1992 9202247
Identification:
601 Lincoln, Odessa, TX
On February 18, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 601 Lincoln in Odessa, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME fL) FIBERS PER CC
021892 SBO-Ol 021892 SBO-02 021892 SBO-03 021892 SBO-04 021892 SBO-05 021892 S BO-06 021892 SBO-07
Field blank Field blank 1st floor, Switch Room 1st floor, Switch Room 1st floor, Air Handler Room 3rd floor. Conference Room 3rd floor, Air Handler Room
1153 1162 1028 1097 1125
1.0/100 fids. 0.5/100 fids. <0.004 <0.004 <0.005 <0.004 <0.004
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
Environmental and Analytical Services
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letter* and reports dull not be reproduced except in fill! without the approval of the testing laboratory. The use'ofour name must receive our prior written approval.
Go4202
Report of: Report to:
I SOUTHWESTERN LABORATORIES
P.O. Box 224227 2573 Lone Star Drive Dallas, Texas 75222 e 214/631-2700
Air Monitoring
SOUTHWESTERN BELL TELEPHONE Attn: REBECCA PEDERSON ONE BELL PLAZA, ROOM 910 DALLAS, TX 75202
Report Date: Date Received: Report Number:
MAY 27, 1994 MAY 27, 1994 9405243
Identification:
601 N. LINCOLN; ODESSA, TX
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
06052394 07052394 #3 #4
Chiller room, basement Second floor, lounge Field blank Field blank
948 1085
<0.005 <0.005
0.0/100 fids 0.0/100 fids
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400, SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program. Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
0^4203
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical entineering, nondestructive, metallurgical and analytical services
2575 Lone Scar Drive P O. Box 22*1227 Dalles. Texas 75222 21*1/263-1133
Report of test on: - /I
tv-'', / + ' / ' ^ . ? r
Date tested: 12 3If-. f 1
Project: &Q/ N- Lmroj
\thn &. be a <*
Sample Number / ID
Location
(*' liJjlU L1 o.r
cricswi
|mplAAnsIlfb |S^fa|fi J"
yw*
a a 't^2.
& tic i li/ ?
Lab Number:
Pump Number Time
Flow and Det. Volume Limit
Fibers Fibers per per Field cc
/neT i -
Off q.qS Onii . L/Min
Elapsed 2-/ 3 Off 4. r 3-
On f.#> L/Min
Elapsed
J? 40
Off
Is?jS
L
On L/Min
Elapsed
Y~ f
Off
On L/Min
Elapsed
Off On
L L/Mi n
Elapsed
L
Technician:
______ Analyst:
CIH/IH:
________________________ Manager: ________________
Type of Activity:
Decontamination____ Background Abatement
Remarks:
Chain of Custody:
Gj4204
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV WO GRANT* VALLEY ALEXANOWA SAN ANTONIO FORT WORTH LEESVILLE MfOUWMO MONROE SHREVEPORT TEXARKANA SHERMAN
Sw
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 275 Lone Star Drive # Dallas, Texas 75222 e 2H/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Report Date: Date Received: Report Number:
April 20, 1993 April 7, 1993 9304064
5
Identification:
601 N. Lincoln - Odessa, TX
SAMELEm
06-03-24-93 07-03-24-93 08-03-24-93 09-03-24-93 10-03-24-93 11-03-24-93
LOCATION Basement Mechanical Room Basement Mechanical Room 2nd floor lounge/back wall 2nd floor iounge/vending area Field blank Field blank
VOLUME (L) 1080 1080 1080 1080
FIBERS PER CC 0.01* 0.01* <0.005 <0.005 0.0/100 fids. 1.0/100 fids.
This sample was found to be over the EPA recommended "dean air" target value of <0.01 f/cc.
Subsequently, the sample was submitted for Transmission Electron Microscropy (TEM) to determine it
the fiber loading was due to asbestos.
The TEM analysis revealed that no asbestos fibers were
present.
Analysis performed by Phsse Contrast Microscopy in seconUnce with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst;
dJAnalytical Services
ireOur letters and reports are for tb exclusive use of the client to whom they addressed. The letters end reports shall not be
reproduced except in dill without the approval of die testing laboratory. The use of our name must receive our prior written approval.
Gj4205
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2S75 Lone Scar Drive P Box 224227 Dallas, Texas 75222 21 4/2S3-1 133
Report of test on :(pd/ Ar Project:
7^
Date tested Lab Number:
^l
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2573 Lone Scar Drive R D Box 2H4227 Dallas, Texas 75222 214/263-1 133
MLReport of test on:
0 e S Of Project: X /-* X&i)
Date tested: 2,
^3
Lab Number: ________
Type of /Activity: ____Decontamination
Remary&Jj&tj/___7/S~5
Background__ ^Abatement
rib______________
------ ---------------______----
-W-
^ /
A*.,_____
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV WO GRANGE VALLEY ALEXANDRIA SAN ANTONIO TORT WORTH LEESVILLE MIOUANO MONROE SHREVEPORT TEXARKANA SHERMAN
siw
SOUTHWESTERN LABORATORIES
P.O. Box 224227 257S Lone Star Drive Dalles, Texas 75222 e 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
Identification:
307 S.W. 3rd, Seminole, TX
SAMPLE NO. 01052494 02052494 03052494 #1 Wl
LOCATION
Emergency engine, basement Boiler room, basement Air handler, basement Field blank Field blank
Report Date: Date Received: Report Number:
May 27, 1994 May 27, 1994 9405245
mnMiiLi
2373 5326 1075
HBEBSrgRCC
<0.002 0.001
<0.004 1.0/100 fids 2.0/100 fids
Analysis performed by Phase Contra* Microscopy in accordance with NTOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Te* (PAT) Program, Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC
Our letten and reports are for the exclusive use of the client to whom they a^ addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name mu* receive our prior written approval.
Go4208
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
237S Lon Star Oriv P O. Box 224227 Dalle. Txas 75222 214/263-1 133
Report of test on: - A-s
A./ Men , -for, ,ufj
: ~jx4*
Date tested
Project: d>o 7
AlW\
^ iSf /v* >J> cl cC-
Rc'ea- Vo.
f '<
Lab Number:
Sample Number / ID
S ^ Sgrr,-
Location
Pump Number Time
Flow
and Det. Volume Limit
Fibers Fibers per per Field cc
Gio52<H4
/ n- .i v- -
L~a vi
JL <A S r r er r i
02a5i- ~
U`
2 '-t J ~j
Off H-5 3
\*s L/Mi n
M
Elapsed 2573
, - -f
L
Off
On L/Min
Elapsed 552^
"7
Wk\
L
Off y.y?
On L/Min
Elapsed
Cf /0 75
-T-7 L
Off
A. f A
\J~" " 1 `
On L/Mi n
Elapsed
Off On
L L/Min
Elapsed
L
Technician: _______ Analyst: _
CIH/IH:
Manager: ______
Type of Activity: ____ Decontamination____ Background^___ Abatement
Remarks:
Chain of Custody:
Gv/4209
HOUSTON QALUAS AUSTIN SSAUMONT CONROS GALVESTON COUNTY WO GRANOE VALLfiY ALEXANDRIA SAN ANTONIO KQRT WORTH LEESV1LLE MIOUANO MONROE SHREVEPORT TEXARKANA SHERMAN
$WL
'
f P.o. Sox 224227
SOUTHWESTERN LABORATORIES
2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitorino
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, TX 78216
Report Date: Date Received: Report Number:
July 27, 1993 July 19, 1993 9307161
Identification:
307 West 3rd, Seminole, TX
p
SAMPLE NO.
01070893 02070893 03070893 04070893 05070893 06070893 07070893 08070893
LOCATION
Boiler Room, Basement A/H Room, Basement A/H Room, Basement Em/Eng Room, Basement Administrative area, 1st floor Field blank Field blank 1st floor. Frame area
VOLUME (L)
1080 1080 1080 1080 1080
1080
HBFRS PERJCC
<0.005 <0.005 <0.005 <0.005 <0.005 0.0/100 fids. 0.5/100 fids. <0.005
Analym performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:.
Kyle
Envirdnmdn
ytical Services
Our letters and reporta an for the exclusive use of the client to whom they arc *53resiei! Tha latters and reports ihail not be reproduced except in full without the approval of the testing laboratory. The use of our name muat receive our prior written approval.
0^4210
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, htetgllurgical and analytical services 2575 Lone Scar Drive P O Box 224227 Dallas. Texas 75222 214/263-1 133
HOUSTON ONJ-AS AUSTIN BEAUMONT CONROE GALVESTON COUNTV BIO GRANGE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH LEESVILLE MtOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
L/
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical.
2575 Lone Star Drive R 0. Box 224227 Dallas, Texas 75222 ft 2 1 >9
.
Report of test on:
zDate tested:
/- 9 j
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV A*0 GRANDE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MSOLANQ MONROE SHREVEPORT TEXARKANA SHERMAN
Swf
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Identification:
307 S.W. 3rd, Seminole, TX
Report Date: Date Received: Report Number:
September 29, 1992 August 31,1992 9208276
xf
On August 25, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 307 S.W. 3rd in Seminole, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME CL) FIBERS PER CC
082592 SBS-OI
Field blank
0.0/100 fids.
082592 SBS-02
Field blank
2.0/100 fids.
082592 SBS-03
Basement, Boiler Room
1190
<0.004
082592 SBS-04
Basement, Emergency Generator Area
1190
<0.004
082592 SBS-05
1st floor. Switch Room, south side
1210
<0.004
082592 SBS-06
1st floor. Switch Room, north side
1190
<0.004
082592 SBS-07
1st floor, hallway leading to Basement
1190
<0.004
Analysis performed by Phase Contraat Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Analyst:
-M-
7
:kz
Our letters and reports are for the exclusive use of the client to whom they ate addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SwL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 117 San Antonio, Texas 78216
Identification:
307 W. 3rd, Seminole, TX
Report Date: Date Received: Report Number:
March 3, 1992 February 25, 1992 9202248
/fP 9^
On February 19, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 307 W. 3rd in Seminole, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (LI FIBERS PER CC
021992 SBS-Ol 021992 SBS-02 021992 SBS-03 021992 SBS-04 021992 SBS-05 021992 SBS-06
021992 SBS-07
Field blank Field blank Break Room/Office area Switch Room Office Switch Room Basement between Boiler Room and A/C unit Basement, Emergency Generator area
1062 1153 1162 1134
1125
1.0/100 fids. 1.0/100 fids. <0.005 <0.004 <0.004 <0.004
<0.004
Aniivji* performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory l.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
Bob Garrett, Manager
Environmental and Analytical S^rvici^sr) ^ ^
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
Huntingdon
Engineering and Science for a Safer Environment
P.O. Box 224227 2575 Lone Star Drive e Dallas, Texas 75222 # 214/611-2700
Report of: Report to:
Air Monitoring
Southwestern Beil Telephone Attention: Elida Barfield One Bell Plaza, Room 910 Dallas, TX 75202
Report Date: Date Received: Report Number:
July 15, 1994 July 8, 1994 9407046
Identification:
209 E. 4th St., Sweetwater, TX
SAMPLE NO. 01070594 02070594 03070594 04070594 05070594 06070594
LQCATIM Basement, Equipment Room #2 Basement, Boiler Room Basement, Emergency Room #1 2nd floor, Fan Room Field blank Field blank
YQLUmfLl 601 1191 2208 1199
FIBERS PER CC <0.008 <0.004 <0.002 <0.004 0.0/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
HUNTINGDON ENGINEERING & ENVIRONMENTAL, INC
Analyst:
Industrial Hygiene Technician
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in foil without the approval of the leafing laboratory. The uas of our name must receive our prior written approval.
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2373 Lana Scar Drive R O. Box 22-4227 Delias. Texas 75222 21-4/2S3-1 133
Report of test on: - A
05
Date tested: ^PnH-
Project:
-S'-f, ^ ^
Lab Number:
_______________________________ ______ _
Sample Number /ID
Location
Pump Number Time
flow and Det. Volume Limit
Old^os^
\bc>.
030705^
m^--n'mv-,iv >/ T
/w/' c3 I t
/(_. fv\
^.cc 3. -
li
off <ruj; Lai. ox
I223S 0ns. !> L/Mi n Elapsed L
Off T- Hip
U7M8
Sd4 0H;ilT. L/Min
Elapsed
dqo
Off, %
4-m^
L
(L%~bL
On
3P 7
L/Min
Elapsed *3.337
sro^
L
dLhrjL.
6"o^t5f/ \
Off 7;# //7^.62
//<? On
L/Min
3:a5
Elapsed
opo
Off
On L/Min
Elapsed
l
Fibers Fibers per per Field cc
^UeU
kotu- 17
Technician:
^
Analyst:
Chain of Custody:
CIH/IH:
_Manager: __________________
------- ------------------
Type of Activity:
Decontamination Background Abatement ------
---
Remarks:
Ar\k*; L^*r
/ Ad 7>t?. a^<in> j
^t/dbrfQ ______ __
-- - ----------------0j4216
HOUSTON riA. 1 AUSTIN flCAUMONT CONROE GALVESTON COUNTY RK3 GRANOS VALLEY AUEXANORIA SAN ANTONIO FORT WORTH LEESVILLS MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
257S Lon Star Drive P. Q. Box 224227 Dalle. Texas 75222 214/2B3-1 133
Report of test on:
Project:
cUl 5, H ^ S+,
& ^e-i wojV
Date tested: Lab Number:
Technician: _____Analyst: _________
CIH/IH:
__________ _________ Manager:
______
Type of Activity:
Decontamination Background Abatement
Remarks:
Chain of Custody:
Gl/4217
HOUSTON DALLAS AUSTIN BEAUMONT CONPQE GALVESTON COUNTY Q GRANOE VALLEY ALEXANDRIA SAN ANTONIO FORT WORTH UEESV1LLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
y
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Drive P . Box 224227 Dallas. Texas 75222 214/263-1 133
Report of test on:
7/ //
Date tested:
-
Pro.iec^4==--:'`----7
-4 t , y -1'-
//
Lab Number:
Sample Number / ID /^Location
4
ri
V"
0
I
-L i
4> A UL
y?
% 'A.
HmK <ift
pd n ^
/3</yi 'f
A
o
\9^J^KClLtr\ t
Technicii
Pump Number Time
m Off
Flow and Det. Volume Limit
Fibers Fibers per per
Field cc
vO
L/Min
L
Off.
uV ^ On \ y Elapsed
^ ?)
yf is,
L/Min
/ ; fa L
0 Off ,>
o
0n //'5rt L/Min
Elapsed
n1
y" %
/
X.
S'
\.7 1
\V
Off
u;
0n II s' ' //A'i
Elapsed
<J 6>
L/Min
/y L
Ofy# . u
"IU L/Min
OElna.p',sed / d3>
Elnap->se> d
~ 1\
Analyst:
Chain of Custody:
CIH/IH:
Manager:
Type of Activity:
Decontamination x" Background Abatement
Remarks\ituhjP fMPh, jLu.-
.Mritj -/o7c^^4^ a nl+z,/<T
-- ----------------------------- __
G u 4 218
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY 0 GRANDE VALLEY ALEXANDRIA SAN ANTONIO TORT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
2575 Lone Star Drive R O. Box 224227 Dallas, Texas 75222 21 4/263-1 133
Report of test on:
Project:
f JT 4-{\
"I V /
5
Date tested: ' ^ -
/ Lab Number:
Sample Number / ID
Location
/I -An P'
Pump ''Number Time ~7 \V.
On a
f' Elapsed
Off
Flow and Volume
y.
L/Min
/ ^ ,,6
L
Det. Limit
On L/Min
E Wpsed Off
L
On L/Min Elapsed
Fibers Fibers per per
Field cc
Off On L/Mi n Elapsed
Off On L/Min
Elapsed
L
rMkTechnicia
/!
y Analyst:
Chain of Custody:
CIH/IH:
Manager:
Type of Activity: Remark%3Up,->0
-W
Decontamination background Abatement
PLP. iL^ar
_____________
?A/fa
-------------- _______________
G^4219
HOUSTON OALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTY HO GRANOE VALLEY ALEXANDRIA SAN ANTONIO PORT WORTH LEESVILLE MIOLANO MONROE SHREVEPORT TEXARKANA SHERMAN
S&IA
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.Q. Box 224227 2575 Lone Star Drive Dallas, Texas 75222
214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
October 5, 1992 October 5, 1992 9210033
Xht//
Identification:
211 E. 4th St., Sweetwater, TX
On October 2, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 211 E. 4th St. in Sweetwater, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
100292 SWBSW-01 Field blank
" 0.0/100 fids.
100292 SWBSW-02 Field blank
0.0/100 fids.
100292 SWBSW-03 1st floor, southeast comer of bldg.
1068
<0.005
100292 SWBSW-04 1st floor. Air Handler Room
1068
<0.005
100292 SWBSW-05 2nd floor, Fan Room
1068
<0.005
100292 SWBSW-06 2nd floor. Break Room
1068
<0.005
100292 SWBSW-07 Emergency Generator Room, basement
1068
0.005
Analyiii performed by Phaie Contra* Microscopy in accordance with NIOSH Method 7400. SwL Dallai ia rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
0j4220
Our letters tod reports ace for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in full without the approval of the testing laboratory. The use of our name must receive our prior written approval.
SwL
SOUTHWESTERN LABORATORIES
Report of: Report to:
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 224227 2575 lone Star Drive e Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
July 2, 1992 June 19, 1992 9206183
Identification:
209 E. Fourth St., Sweetwater, TX
On June 16, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 209 E. Fourth St. in Sweetwater, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO,
LOCATION
VOLUME (L) FIBERS PER CC
061692 SBSW-Q1
Field blank
0.5/100 fids.
061692 SBSW-02
Field blank
3.0/100 fids.
061892 SBSW-03
Basement, Boiler Room
1327
<0.004
061892 SBSW-04
Basement, Emergency Generator Room
1346
<0.004
061892 SBSW-05
Basement, A/C Room
1356
<0.004
061892 SBSW-06
Basement, Power Room at AHU Room
1461
<0.003
061892 SBSW-07
Basement, Power Room at Desk Area
1480
<0.003
061892 SBSW-08
2nd floor. Mechanical Room/Room 202
1604
<0.003
061892 SBSW-09
2nd floor
1613
<0.003
061892 SBSW-10
2nd floor. Fan Room/Room 210
1613
<0.003
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATORIES, INC.
AoL Bob Garrett, Manager
:kz Environmental and Analytical Services
0j4221
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in fiiU without the approval of the testing laboratory. The uae of our name must receive our prior written approval.
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Sox 173668 Austin, Texas 78760
Client:
SwL Dallas Attn: Robert Garrison
Report No. Report Date Page
505092-656
June l, 1992
1 of 1
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 5/28/92 Analyzed on 5/29/92.
Site: Southwestern Bell Telephone, 500 Talbot Street, Taylor, Texas
RESULTS
VP
S
Filter 1 D, Front office area Northwest comer of Bldg., computer area Switch room Basement, power room Blank
SwL Lab No Tay-1 Tay-2
Time (min)
120
120
FR i!Zml 11.5
12.0
Volumes (liters)
1380
1440
fb/fl 4.5/100 4.0/100
MPA 0.00787 0.00787
AG* Fibers/cm
<0.004
<0 003
Tay-3 Tay-4 Tay-5
121 11.5 120 12.0
-
1380 .40
0.5/100 3.0/100 0/100
0.00787 0.00787 0.00787
<0.004 <0.003
*AC determined using a minimum 10 F8/100 FL Reliable Quantitation Unit wnere applicable. Fibers/ce are blank corrected where applicable. Analysis performed by Phase Contrast Microscopy m accordance with NIOSH Methodology 7400.
/
.j
SOUTHWESTERN LABORATORIES, INC.
Martin J. Gibson Environmental Scientist
Our letters and reoorts are tor me exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except m Ml without the approval of testing laboratory. The use of our name must receive our prior written approval.
Gu4.222
,6 s'
S&1
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.0. Box 173668 # Austin, Texas 78760
Client:
SwL Dallas Attn: Robert Garrison
Client No. Report No. Report Date
505092-121 December 20, 1991
Project:
Airborne asbestos samples taken by Kenneth Williamson with SwL on 12/18/91. Analyzed on 12/20/92.
Site: Southwestern Bell Telephone, 500 Talbut Street, Taylor, Texas
Filter I D-
Basement, power room
1st floor, northwest comer
1st floor, switch room
1st floor, office area
Blank
RESULTS
SwL Lab No.
Time (min)
FR (I/m)
T-1 120 10.0
Volumes (liters)
1200
F8/FL 6.0/100
MFA 0.00787
AC* Fibers/cm
<0.004
T-2
120 11.0
1320
6.5/100
0.00787 <0.004
T-3
120 10.0
1200
7.0/100
0.00787 <0.004
T-4
120 10.0
1200
6.0/100
0.00787 <0,004
T-5
,,
0/100
0.00787
.
Remarks:
SOUTHWESTERN LABORATORIES, INC.
Robert N. Dettori Asbestos Coordinator
Our letters and reports are for tile exclusive use of the client to whom they are addressed. The letters and reports shall not be reproduced except in fun without the approval of testing laboratory. The use of our name must receive our prior written approval.
to: AS8DALLAS
Gj4223
S^l
!? o' 3
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
DAILY LOG
___________ ________________
Report Date:_______ 12/18/91
________
To: SwL - Dallas. Attn: Robert Garrison
Project Name: Southwestern Bell
_________
Project No: 500 Talbut - Tavlor, Texas
SwL Time Start:
1:00 p.m.________ ____________
Stop: _____________5:30 p.m. __________
________PAGE 1 OF 1
Sample Date: _____________ 12/18/91
No, of Samples Taken:
5 ____________ _
Method of Test:
NIOSH 7400-A
Supenntendent: ______________ _________________
SwL Technician: Kenneth Williamson
Foreman: __ ________________________________
Sample Location
Basement, power room
1st floor, northwest comer
1st floor, switch room
1st floor, office area
Blank
___ Ij2 T-1 T-2 T-3 T-4 T-5
Time Start
2:00 pm
Time Stop
4:00 pm
Total Time (min)
120
Flow Rate (I/m)
10,0
Volume (liters)
1200
Fibers/ Field
6,0/100
MFA 0.00787
F-cc <0 004
2:03 pm
4:03 pm
120
11.0 1320
6.5/100
0 00787
<0.004
2:05 pm
4:05 pm
120
10,0
1200
7,0/100
0.00787
<0 004
2:07 pm
4:07 pm
120
10.0 1200
6.0/100 '
0.00787
<0 004
0/100
0.00787
Remarks:
dfiy
Robert N. Dalton Asbestos Coordinator
ESTERN LABORATORIES, INC.
Hilary D. Johns
Senior Progrark^J^ahagi
Our letters and reports art for the exclusive usa of tha clitnt to whom trity art addrassad. The lattara and raoorts Shan not Be reproduced except in fuu without the Approval of testing Laboratory. The use of our name must receive our prior written approval.
fn: ASBOALLAS
Go4224
Huntingdon
Report of: Air Monitoring
Report to:
Southwestern Bell Attention: Rebecca Pederson One Bell Plaza, Room 910 Dallas, TX 75202
identification: Laforce Drive
SAMPLE NO, LOCATION
04011195
Boiler Room
0501195
Mechanical Room
m Field blank
#04 Field blank
Huntingdon Engineering & Environmental, Inc.
P.O. Box 224227 2575 Lon* Star Driva Dallas, Taxas 75212
Telephone: (214) 831-2700 FAX: (214) 920-1891
Report Date: Date Received: Report Number:
February 2, 1995 January 17, 1995 9501123
VOLUME(LI 1207 1595
fibers per cc <0.004 <0.003
i.5/100 fids. 1.0/100 fids.
Analysis performed by Phase Contrast Microscopy in accordance with MIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
HUNTINGDON ENGINEERING & ENVIRONMENTAL, INC.
Analyst: Gregory Industrial Hygiene Technician :kx
UdAu?
Environmental and Analytical Services
Our tontines and report* intxte axetaiws urn of the cBaet to whom they an addnmmd. Tbs toasts tad reports shall act h reproduced except ia fiiU without &* approval of the tasting laboratory. Tbs um of our anas must raewva our prior writtea approval.
Gj4225
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical entineering, nondestructive, metallurgical and analytical services
2375 Lone Scar Oriva IRQ, Box 224227 Dallas. Taxes 75222 214/263-1133
Report of test on:
Date tested:
Project: L-^LTbft- O
^
_____________ Mm Uehec t
-PscTTrLc,')
Lab Number:
Sample Number /ID
Location
Pump Number Time
Flow and Det. Volume Limit
Fibers Fibers per per Field cc
tiotlr't. HrT\ C^oii/%
in^S sUth, fc/r^
it
^03 /
led S> a^Jc
0ff5;w W On 11: ZS L/Hin
"V1 m-j Elapsed Mo Off M'l onf.i'3e L/Min
ni7L Wf /sp
Off
On L/Min
Elapsed Off
L
On L/Min
Elapsed
Off On
L L/Min
Elapsed
L
|
Technician: CIH/IH:
Analyst: Manager:
Chain of Custody:
Type of Activity:
Decontamination Background____ Abatement
Remarks:
0j4226
HOUSTON DALLAS AUSTIN BEAUMONT CONROE GALVESTON COUNTV RIO GRAND* VALLEY ALEXANDRIA SAN ANTONIO EQRT WORTH LEESVILLE MIDLAND MONROE SHREVEPORT TEXARKANA SHERMAN
ScuL V -
SOUTHWESTERN LABORATORIES
Report of: Report to:
Miltrials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services P.O. Box 22422/ 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
October 13, 1992 October 12, 1992 9210108
Identification:
925 Washington, Waco, TX
On October 12, 1992 a representative from Southwestern Laboratories Inc., (SwL) was at the Southwestern Bell facility located at 925 Washington in Waco, Texas to provide prevalent air monitoring. The results of the air samples collected are as follows:
SAMPLENO, 101292 SWB-01
location
Field blank
VOLUME (L)
FIBERS PER CC 0.0/100 fids.
101292 SWB-02
Field blank
0.0/100 fids.
101292 SWB-03
1st floor, Fan Room, east side
1068
<0.005
101292 SWB-04
Basement, Emergency Generator Room
1068
<0.005
101292 SWB-05
Basement, Fan Room
1068
<0.005
101292 SWB-06
2nd floor, Air Handler next to freight elevator
1068
<0.005
101292 SWB-07
3rd floor, Air Handler next to freight elevator
1007
<0.005 .
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Teat (PAT) Program, Laboratory I.D. No. 75212-001.
"7
SOUTHWESTERN LABORATORIES, INC.
Analyst:
Kyle|Burroujj
:kz Environmental and Analytical Services
f , <097
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters and reports shall net'b*'
"
reproduced except in Dill without the approval of the testing laboratory. The use of our name must receive our prior written approval.
^
SwL
SOUTHWESTERN LABORATORIES
Materials, environmental and geotechnical engineering, nondestructive, metallurgical and analytical services
P.0. Box 224227 2575 Lone Star Drive Dallas, Texas 75222 214/631-2700
Report of: Report to:
Air Monitoring
Southwestern Bell Telephone Attention: Gladys Haecker 7159 San Pedro, Room 106 San Antonio, Texas 78216
Report Date: Date Received: Report Number:
June It, 1992 June 8, 1992 9206082
X? 5-VII
Identification:
925 Washington, Waco, Texas
On June 8, 1992 a representative from Southwestern Laboratories Inc., !SwL) was at the Southwestern Bell facility located at 925 Washington in Waco, Texas to provide prevalent air monitoring during normal work activities. The results of the air samples collected are as follows:
SAMPLE NO.
LOCATION
VOLUME (L) FIBERS PER CC
060892 SWBW-01 Field blank
0.0/100 fids.
060892 SWBW-02 060892 SWBW-G3
Field blank Air Handler Room 110C, 1st floor
1039
0.0/100 fids. <0.005
060892 SWBW-04 Air Handler, northeast, 2nd floor
060892 SWBW-05
Air Handler, west of vertical pipe chase
060892 SWBW-06 Basement, next to Air Handler 0416
060892 SWBW-07 Basement, Boiler Room 006
1039 1039
935 935
<0.005 <0.005
<0.005 <0.005
Analysis performed by Phase Contrast Microscopy in accordance with NIOSH Method 7400. SwL Dallas is rated proficient by the NIOSH Proficiency Analytical Test (PAT) Program, Laboratory I.D. No. 75212-001.
SOUTHWESTERN LABORATO
Bob Garrett, Manager
:kz
Environmental and Analytical
^
Our letters and reports are for the exclusive use of the client to whom they are addressed. The letters end reports shall r ^ grovel,
ourreproduced except in full without the approval of the testing laboratory. The use of our name must receive prior