CHAPTER 13
1953 Guide , '
siderable reduction in heat gain, if all factors except solar intensity remain
the same. Reference 22 gives heat gain values for four orientations at 40
deg north latitude on August 1 for several types of .flat glass and glass block,' and solar intensities typical of humid industrial atmospheres. These data show that the following approximate reductions, based on total gain for the day, can be expected: 20 percent for all types of glass and glass block in east or west facing walls; 10 percent for south facing flat glass; 5 percent for south facing glass block walls.
Shading of Glass Areas--Design Tables
The effects and possibilities of shading should be carefully investigated whenever the heat gain from glass is a largo portion of the cooling load.
Vertical glass, which is not mounted in the plane of the building surface, is partially shaded by the setback. If a vertical window of height l and width w be set back from the plane of the building a distance s, the fraction of the total area of the window which receives direct solar radiation is:
where
rt tan 0 cos y
r, tan y + TiTt tan 0 tan y cos y
(5)
Ti = s/l, rt = s/to, 0 = solar altitude, and y is the wall solar azimuth (see Fig. 1):
Values of /? and y for various latitudes and August 1 are given in Table 6. Special cases not covered by the tabulated data may be solved analy tically;24 however, the design conditions chosen will yield a satisfactory approximation if used without correction for any time during the summer period.
Example 11: Estimate the total instantaneous rate of heat gain for a west win dow 3 ft wide by 5 ft high, with a setback of 6 in., for August 1 and 40 deg north latitude at 3:00 pm (sun time).
Solution: From Table 13, the instaneous rate of heat gain, due to transmitted direct and diffuse solar radiation, is 180 Btu per hr. From Table 6,0 is 45.5 deg and y is 16 deg. From Equation 5, the fraction of the total window area that is receiving direct solar radiation is:
(#i = l, -- O--.-lc-o-ta-s-nr1%46--5.5 -- 0.167 tan lo. + -0--.0--1-6--7--t-a-c-on--s-4-15--6.-5--t-a--n---1-6
= 1 - 0.106 - 0.048 + 0.005 = 0.851
In this instance the convection and radiation heat gain is due principally to temperature difference, so that shading has but a small effect on that portion of the absorbed radiation. Hence, the factor <1851 is applied only to the Table 13 value. Note also a small error results from the fact
that the diffuse radiation is not shaded to the same extent as the direct radiation. The total instantaneous heat gain therefore is:
9 = 3 X 5 (0.851 X 180 + 26) = 2690 Btu per (hr)(sq ft)
A window such as the one used in Example 11 would customarily be pro vided with an additional shading means for use particularly when directly sunlit. Conventional shading devices include awnings, shades, and screens of various types.
Experimental work conducted at the A.S.H.V.E. Research Labora tory,24'25 and other research26 to determine the effectiveness of various types of window shades, have been used as the basis for the recommended ratios
Cooling Load
~ 297
in column 3 of Table 24. A study of absorptivity of the shade to , solar radiation and heat transfer from the shade to the outdoors and indoors,
was used to determine these ratios. There are a number of variables affecting these ratios, such as color, fit,
solar altitude, and angle of incidence of the solar radiation. These values, therefore, must be considered, as approximate, only, and will have to beused with considerable judgment. An inside shade is effective to the ex tent of its reflectivity, since the portion of the solar radiation directly transmitted by the glass that is absorbed by the shade is transferred by convection to the room air, and by radiation to the solid room surfaces.
Table 24. Effect of Shading upon Instantaneous Solar Heat Gain Through Single Thickness of Common Window Glass
Type op Shading
Finish on Side Exposed to Sun
Fbaction op Gain Through Un
shaded Window
oooo
g S ftij!
Canvas Awning Inside Roller Shade, Fully Drawn* Inside Roller Shade, Fully Drawn*
Inside Roller Shade, Fully Drawn*
Inside Roller Shade, Half Drawn*
Inside Roller Shade, Half Drawn*
Inside Roller Shade, Half Drawn*
.
Inside Venetian Blind, Slats set at 45 deg
Inside Venetian Blind, Slate set at 45 degb
Inside Venetian Blind, Slate set at 45 deg|* Inside Venetian'Blind, Slats set at 45 degD Outside Venetian Blind, Slats set at 45 deg .
Outside Venetian Blind, Slats set at 45 deg, extended as an awning0 Outside Shading Screen,d solar altitude 0-20 deg Outside Shading Screen,d solar altitude 20-40 deg Outside Shading Screen,d solar altitude, above 40 deg
Dark White Medium color Dark color
White Medium color Dark color White
Medium Aluminum ' Dark color Cream
Any color Dark color Dark color Dark color
0.72 0.81 0.90 0.62
0.74 ' 0.70
0.86 0.30
0.40 0.75-0.43 0.43-0.22 0.22
* Roller shades are assumed to be opaque. Some white shades may transmit considerable solar radia tion. For white translucent shades fully drawn use 0.55, and for half drawn use 0.77.
b Venetian blinds are fully drawn and cover window. It i9 assumed that the occupant will adjust slats
to prevent direct rays from passing between slats.
0 Commercial shade with wide slats. d Metal slats 0.05 in. wide, spaced 0.063 in. apart, and set at 17 deg angle with horizontal. At solar alti tudes below 38 deg some direct solar rays are allowed to pass between slats, and this amount becomes progres sively greater at low solar altitudes.
INSTANTANEOUS HEAT GAINS VS. INSTANTANEOUS COOLING LOADS
The difference between instantaneous heat gain and instantaneous cool ing load has been mentioned previously; its practical importance is suffi
cient to warrant further consideration.
Fig. 4 offers a simplified schematic illustration showing how the radia tive part of the instantaneous heat gain is first absorbed by solid objects, and is not encountered by the conditioning equipment as a cooling load until some later time, when it finally appears in the air stream entering the equipment. While it is true that some lag also is inherent in convective heat transfer and the time required to change the air in the conditioned space, this is usually of the order of a few minutes to perhaps half an hour: Heat storage in the interior furnishings and structure increases according to the proportion of the instantaneous heat gain which is in the form of