Document 2JOvDrxjDQoZe98LO2nNV5p7L
CC
ST0000704
Harold Eosscher, Manager Midland Division 47 Building
SUMMARY ON ASBESTOS IN THE MIDLAND DIVISION
Since the recognition of health hazards associated with the use of asbestos, the following steps have been taken.
Environmental Health conducted ?. study of pipe covcrers
on the job and determined the exposure to dusts from
insulating materials in use. By determining how long
and hovr often the various activities wore performed a
time-weighted exposure was established. From this
information, the' minimal respiratory protection was
established for each type of insulating material anc each
activity in the pipe eoverers job.
During August, 1969 the results of this study were presented to the pip covcrers, maintenance supervisors and production representatives. Additionally, the Medical Department explained the health hazards involved and the effects
of smoking as a habit which enhances the chances of developing cancer of the lung. The maintenance group explained what would be required for respiratory protection
and when it was to be worn. The use of fiberglass as a replacement for aircell was discussed.
Since August, 19&9* the use of aircell has been discontinued and replaced with fiberglass (100``? - 350CF), Carey temp 1500 has been introduced as the replacement for calcium silicate type .insulations up to lbOCf'F. Purchasing v.'ill not buy an insulation containing asbestos without notifying the Maintenance Technology Center and insuring, that there is no other material that will do the job. Careytemp is more difficult to work with and install than some of the calcium silicate insulations. Because of this, there is probably a 9 to 10;' extra cost in using Carey temp. As the" covcrcrs become more experienced with Careytemp, this should drop. Work is underway with the manufacturer to improve the 'product.
Present technology docs not give us a :a;b:vki tute for
asbestos at high temperatures
). Ceramic foam "
may effor a possibility for high temperature use.
Insulating cements are also a problem urea. Until substitutes
can be dove loped, careful handling procedures must be
followed during the mixing.
The introduction of additional ashes to:; containing insulation into the Division has boon vastly reduced. In the coming years, the prime .source of asbestos exposure will be the removal, transportation and disposal of old asbestos insulation. Procedures for-handling and sending
old insulation to disposal must be developed.
The other major use of asbestos is
the chlorine cell
maintenance area in the manufacture ' dUreh rarms for
chlorine colls. The asbestos is re* ved in 50 lb bags
and dumped into a mix tank. About 1150s lbs3 is rnoul red
for a diaphragm, for the present cells and '-50 - 500 lbs
will be required par dianh rages In the new plant. The
new plant will use about 50,000 3bs/yr' of asbestos for
this purpose.
ST0000705
The operation has been studied by Environmental Health and the proper respiratory equipment ha been specified for the mixing operation. In the old cell maintenance
a__r_e_s only full bags of asbestos .....r..c.....h..a..nd.led and use of partial bags is avoided which reduces expeosurc. The mixing is an intermittent operation which also reduces personnel exposure. The new plant will h:xve a comp]etc ventilation system above the mix tank v:hi e h will go to a filter unit and then to a scrubber or beag filter.
In the cell buildings asbestos is handled in small amounts by the operators. It is dumped directly into the cell to plug holes in the diaphragm. This operation requires respiratory protection, for the long tom solution, a new material of construction for diaphragms is being Considered but a likely successor has not yet been found.
In the cell maintenance area as the old diaphragms arc
washed with high pressure viator,
of the asbestos is
recovered on a set of vibrating screens and is; cent to
land fill. The remainder is recovered at the treatment
plant on the centrifuges.
Environmental Health is making a complete inventory of uses of asbestos and recommended disposal techniques. The Maintenance Technology Center will viork with Waste Disposal and Environmental Health to develop procedures for handling and disposal of covering,.
, /I n<y.-ijA--
Vf. A. Snodgrass Maintcnancc Technology Center Oj^l Building
rwh