STEAM HEATING
Selection of Radiation
It is usually necessary to select the type and location of radiation to conform to the conditions and space available in the room. In general it is usually most convenient and practical to locate the radiation on the exposed side of the room.
The size of the radiator to take care of any particular heat loss can be best selected from the data sheets compiled by the Society's Research Laboratory in cooperation with the U. S. Bureau of Mines Experiment station, which are based on experiments by the late Director, John R. Allen and F. B. Rowley. As the heat emitted per square foot of radiation varies in radiators of different heights, widths and lengths, and also with the steam pressure and the temperature of the room, errors will occur if the same factor is used for all radiators.
Examples for the use of tables: Assume the heat loss in the room in the problem above, cited, which was estimated at 15,497 B. t. u. per hour, to heat the room to 70 deg. fahr. Two-column 38 in. radiators have been selected using steam at 1 lb. gage or approximately 215 deg. fahr.
Solution : In Table 2 for two-column radiators, under 38 in., it will be
found that a 17-section radiator will emit 15,960 B. t. u. Therefore a
17-section--2 column 38 in. radiator will be required with a rated surface
of 85 sq. ft.
< ;
If in the same example steam at 5 lb. pressure or approximately 227 deg. fahr. was used and the room was heated to only 60 deg. fahr. requiring 13,300 B. t. u. and three column 26 in. radiators are selected the radiation would be estimated as follows:
Solution: In Table 8 following down the first column to 5 lb. gage pressure and then following over horizontally to 60 deg. fahr. room temperature the conversion factor 0.864 will be found. The heat loss 13,300 X 0.864 (the equivalent heat loss) = 11,480 B. t: u. In Table 3 for 3 column radiators under the heading 26 in. it will be found that a 13 section radiator will supply 11,242 B. t. u., under standard conditions which is the closest to the amount required. Therefore a 13 section 3 column 26 in. radiator will be required.