Document 1vnb077V5LD96aKJKJQ1rnpd
TOWOLDMON0035656 WATER_PCB-00020125
Contents
PAGE 1 The Pydraul Air Compressor Fact Finder
1 How Compressor Fires and Explosions Occur
3 Pydraul Fire-Resistance
4 Pydraul AC-A Virtually Eliminates Valve Deposits
5 Converting To Pydraul Is Easy
6 Pydraul Provides Excellent Lubricating Qualities
7 Mixing Compatability
7 Pydraul Is Used As A Lubricant For Compressors Made By All Major Manufacturers
8 Safe Handling
0510470
TOWOLDMON0035657 WATER PCB-00020126
The Pydraul
Air Compressor
Fact Finder
. . . is designed to make the many facts about Pydraul fire resistant lubricants for air compres sors--Pydraul AC-A, Pydraul AC-A Winter Grade 28 and Pydraul 625A--easy to find. These safety lubricants for air compressors were specially developed to offer you:
Safety from Fire and Explosion Pydraul eliminates combustible mists and mini mizes carbonaceous residues -- greatly reducing the threat of compressor fires and explosions.
Lower Maintenance Costs Pydraul eliminates deposits on exhaust valves, in coolers and in piping. You save the costs of com pressor downtime and cleaning. Many compressor users find these savings alone justify using Py draul lubricants.
How Compressor Fires &
Explosions Occur
Every theory about the mechanisms of compres sor fires and explosions hold one idea in common: petroleum oils are directly involved.
Petroleum Oil Mists & Films Mist and accumulated films from petroleum oil in compressor systems can, under a variety of con ditions, break down into combustible gases and carbonaceous residues that can ignite and pro duce an explosion, a receiver fire--or both. The U. $. Bureau of Mines' found that carbon deposits in air compressors lubricated with petroleum oil form a "carbon-oxygen complex." Oxidation forms this complex, and accelerated by heat, this oxida tion process can lead to an explosion.
The Shortcomings of Safety Devices Safety devices do not completely eliminate fire and explosion possibilities. A study on "The Mecha nism of Explosions In Starling Air Lines,"2 based on an exhaustive survey of compressor operations at 53 companies, reports that a stuck or leaking air check valve permits the engine being started to pack the section of line between the check and air timing valve with an explosive "oil residue-air" mixture. A pressure wave will force this mixture upstream into the main air line--and coupling this with good flame propagation in the power cylinder, the condition is laid for explosion in the pipe sys tem,
Air line explosions and fires may even occur with out the engine being started or before the ignition is turned on. Carbon and rust particles in a "hot" air line, due to operating an overheated compres sor too long--hardly an improbable condition-- can become saturated with oil, and with the flow of starting air, can cause these oil-saturated par ticles to flame.
Explosion Tests at 1300 PSI The Walter Kidde Company, makers of fire extin guishing equipment, warns in a study3 that users of high pressure air should guard against intro ducing a shock wave into high pressure lines by suddenly opening a plug cock in air compressor systems using petroleum oil. This report showed that in a 1-inch diameter tube, the inside walls filmed with oil, a sudden admission of air at pres sures above 1300 psi caused combustion.
How can you eliminate the conditions that cause fires and explosions in air compressors? Eliminate the source of carbon deposits, the basic cause of most air compressor disasters--petroleum oil.
Substitute fire- and explosion-resistant Pydraul.
1. "The Carbon-Oxygen Complex as a Possible Initiator of Explosions and Formation of Carbon Monoxide in Com pressed Air Systems," by Busch, Berger, and Schrenk, Bureau of Mines paper H.1.4465, June 1949.
2. "The Mechanism of Explosions in Starting Air Lines," by Ridgway, Robert S., Petroleum Refiner, June 1958.
3. "Oil Combustion Phenomena in High Pressure Air Sys tems," M. W. Weibel, Walter Kidde & Co.. Inc., Report R-831, copyright 1952.
U510471
TOWOLDMON0035658
WATER_PCB-00020127
TABLE 1
COMPATIBILITY WITH METALS
Pydraul air compressor lubricants are compatible with all construction metals including aluminum. In most operations, aluminum bearing surfaces will wear as long as any other metal surfaces lubri cated with Pydraul if they have been anodized.
TABLE 2--VAPOR PRESSURE
Temperature
Vapor Pressure mm Hg
C. F. PYDRAUL AC-A
PYDRAUL 625A
PYDRAUL AC-A WINTER GRADE
28
0 32 3.5 x 10-S
10 50 11.0 x 10-s
20 68 3.3 x 10-5
40 104 2.4 x 10-
60 140 11.5 x 10-4
80 176
5.0 x 10-3
100 212
1.7 x 10-2
150 302
0.26
200 392
2.2
0.30 x 10-6 1.1 x 10-6 4.0 x 10-6 3.8 x 10-5 2.3 x 10-4 1.2 x 10-3 0.55 x 10-2 0.13 1.4
5.5 x 10-617.5 x 10-6 50 x 10-6
3.5 x 10-4 1.6 x 10-3 6.6 x 10-3 2.2 x 10.2 0.31 2.3
Vapor Denslty=11.2 compared to value for air of one (1).
l PYDRAUL AC-A ' WINTER GRADE 28
| .,
i I
;
Char Blue Liquid 1.235-1.255 0.15
0.15%
ir>;. Mssu fete. 45 SSU
|p`> * '"-tw
pT~, wf. pia.lt.jMWI.
If- -
; i > ! ;
;
\
>
It4 krvtr > >> . --m.p...e.
26 to 30 3.8 to 4.2
132.8SSU 39.3 SSU 165 SSU 45 SSU --25F.
2.63
350F.
610"F. 0.00041
033 0.068
380,000
41.0 Negligible
FIGURE 1--TYPICAL VISCOSITIES
. PYDRAUL625 A . PYDRAUL AC-A
TEMPERATURE, DEGREES FAHRENHEIT
TOWOLDMON0035659 WATER PCB-00020128
Pydraul Fire-Resistance
Pydraul fire-resistant fluids and lubricants have worked in industry since 1951, providing many
millions of machine hours of fire-free operation. Never during these hours of machine operation has a Pydraul fluid contributed to a fire--and never since their introduction in 1954 has any
Pydraul fire-resistant compressor lubricant caused a compressor fire or explosion.
FIRE-RESISTANCE TESTS OF PYDRAUL AC-A,
PYDRAUL AC-A WINTER GRADE AND PYDRAUL 625A
TEST
High Pressure Spray Test AMS3150C and Federal Test Method Std. 791. Test fluid sprayed at 1000 psi through orifice, passing through flame of oxyacetylene torch, 6000F.
RESULTS
Does not flash or ig nite up to 3Vi feet from orifice.
Atomized Spray Test (procedure used by Factory Mutual Engineer ing Division). Test fluid heated to 140F. sprayed at 1000 psi from atomized cone type nozzle. A torch is passed through this spray 2 feet and 2 to 6 inches from the orifice.
Local burning by torch at 6 inches and 2 feet from orifice. Flames self-extinguishe imme diately when torch re moved.
Hot Manifold Test (Federal Test Method Std. 791). Test fluid drip ped on tube at 1300F.
Does not flash or burn.
Molten Metal Ignition Test. Test fluid exposed to the surface of aluminum alloy at 120(TF., to test for spontaneous ignition.
Does not ignite.
0510473
TOWOLDMON0035660 WATER_PCB-00020129
500 hours on premium petroleum oil
Pydraul AC-A Virtually Eliminates
Valve Deposits
Compressor Data: 142 CFM, 6" LP Bore, 5" HP Bore, 5" Stroke, 870 RPM, 100 psi air
The photos compare exhaust valve deposits formed during individual 500-hour operations on two lubricants: a premium grade petroleum oil . . . and Pydraul AC-A*. A glance at the photo of the valve lubricated with petroleum oil shows considerable carbon deposit build-up after 500 hours operation. The improve ment in the valve condition in the photo on the right is obvious--virtually no carbon deposits after 500 hours operation with Pydraul AC-A. In the par ticular case, the compressor operator expects to get 7500 to 10,000 hours of service from Pydraul AC-A without shutting down--a 15- to 20-fold in crease in operating time without a shutdown. Re sult: substantial maintenance savings in time and money--and virtual elimination of the fuel source of most air compressor fires and explosions.
*No photographs available of Pydraul 625A and Pydraul AC-A Winter Grade 28, but results are at least identical.
0510474 4
TOWOLDMON0035661 WATER_PCB-00020130
Converting lo Pydraul Is Easy
First, simply drain the petroleum oil and wipe the crankcase or lubricator.
Thoroughly clean the exhaust valves and inter stage equipment before filling the crankcase or lubricator with Pydraul. Pydraul will loosen car bonaceous deposits, varnishes and sludge. Unless these loosened deposits are cleaned from the sys tem, they could clog pipelines and components, requiring additional downtime and production loss. Once the valves have been thoroughly cleaned of potentially dangerous carbon deposits, Pydraul lubricants will keep them clean--and let compres sors run longer between maintenance shutdowns.
STANDARD CHECK FOR COMPRESSORS--Plas tic separator bowls. Not all plastic separator bowls are suitable for Pydraul service. Certain plastics are "crazed" or softened when exposed to Pydraul. Bowls made of glass, brass, steel, and these plastics--polycar bonate, polyethylene, or nylon--are recommended for use with Pydraul. If you have a question re garding the resistance of a particular plastic, Monsanto will be happy to advise you.
Diaphragm valves. Pydraul lubricants have a sof tening effect on neoprene and buna N rubber diaphragms normally used for petroleum oil serv ice. These diaphragms should be replaced with butyl rubber, EPR (ethylene propylene rubber), fluoroelastomer, silicone or other compatible elas tomer materials resistant to Pydraul fluids. Dia phragm sheeting is available from normal sources of supply.
All diaphragms in unloading valves or downstream control valves should be replaced at the time of changeover, Diaphragms in valving downstream from separator systems or drying systems need not be replaced at changeover time, but should be changed on a preventative maintenance schedule as soon as practicable after operation on Pydraul is begun.
For air compressors supplying air for instrumenta tion functions, mist eliminator systems are recom mended to remove lubricant mists and moisture from air streams. A Monsanto development, a Brink mist eliminator is a particularly effective system, available from Monsanto in a series of lowcost mist eliminator systems to operate at all ca
pacities. For information on a Brink series suitable for your compressor system, write to:
Monsanto Enviro-Chem Systems, Inc. 800 North Lindbergh Blvd. St. Louis, Mo. 63166 Telephone: (314) 694-2286
(Joseph A. Brink)
SPECIAL CHECK FOR SPLASH-LUBRICATED COMPRESSORS
Crankcase paint. Pydraul air compressor lubri cants will soften and loosen some paints from crankcase interiors. These paint particles could block the lubricant passages, For this reason, it is a good practice to remove paint from crankcase interiors before Pydraul is added to the system. Standard paint removers are adequate tor remov ing this paint.
SPECIAL CHECK FOR FORCE-FEED LUBRICATORS Sight-glass fluid. If a separate force-feed lubri cator of the type normally filled with water and glycerine is used, one of two changes is neces sary: either replace the sight-glass fluid with one heavier than Pydraul or insert a metal bobber in the sight-glass. Pydraul fluids are heavier than water or glycerine and will not rise through these standard sight-glass liquids. Fluorochemical 101, a clear liquid supplied by the Minnesota Mining and Manufacturing Company, has a higher density than Pydraul and is a completely satisfactory re placement.
Metal bobbers. The alternate to using Fluoro chemical 101 is to modify the sight-glass lubricator by inserting a simple metal bobber. The bobber is installed by draining the sight-glass liquid, remov ing the guide wire and inserting the bobber. Operation of the lubricator is then indicated by movement of the bobber with each stroke of the pump plunger instead of counting the drops as with guide wires. Bobbers are available for either McCord, Manzell, or Lincoln Engineering lubri cators. Modification of the Madison-Kipp lubricator requires replacement of the entire sight-glass.
Vacuum-sight lubricators. Vacuum-sight lubrica tors require no modification for Pydraul usage.
0510*7*
U
TOWOLDMON0035662 WATER_PCB-00020131
Pydraul Provides Excellent
Lubricating Qualities
TABLE 3 FALEX LOAD TEST
PASSING LOAD
Pydraul 625A
Pydraul AC-A
Pydraul AC-A Winter Grade 28
4250 4025
4175
TABLE 4 FALEX WEAR TEST
WT. LOSS, PIN (mg.)
WT. LOSS, BLOCKS (mg.)
Pydraul 625A
1.1 5.8
Pydraul AC-A
0 0.5
Pydraul AC-A Winter Grade 28 0.6 0.9
DROP SIZE
Drop size of a lubricant is important to determine an adequate lubricant injection rate to insure proper compressor lubrication. The rate of lubri cation is controlled by noting the drops per unit of time.
The drop size for the fluids tabulated below were determined by noting the number of drops formed at room temperature (75F.) on a 1 mm I.D. by Vh mm O.D. glass tip. (Larger or smaller drops will result if different sized tips are used.)
Fluid
Medium weight petroleum oil Pydraul AC-A
Drop* per cubic centimeter
33 39
When installing new equipment, it is best to start with an increased lubricant feed rate and reduce this rate by successive increments. Inspection of
cylinder walls and valves will indicate the proper
degree of wetting.
TABLE 5 TIMKEN
OK LOAD (lbs.) FILM STRENGTH (Pf)
Pydraul 625A
Pydraul AC-A
Pydraul AC-A Winter Grade 28
30 11,700 45 15,100
24 8,600
TABLE 6
SHELL FOUR-BALL WEAR
(167F,, 1 hour, 630 rpm., mm scar diameter)
STEEL ON STEEL
PYDRAUL 625A
PYDRAUL AC-A
PYDRAUL AC-A
WINTER GRADE 28
10 kg 40 kg
STEEL ON BRONZE
10 kg
0.23 0.60
0.46
0.33 0.67
0.48
0.42 0.66
0.43
6 0510476
TOWOLDMON0035663 WATER_PCB-00020132
Mixing Compatibility
Pydraul AC-A, Pydraul AC-A Winter Grade 28 and Pydraul 625A are completely miscible in all pro portions with competitive synthetic phosphate ester lubricants.
Pydraul Is Used As A Lubricant For
Air Compressors Made By All Major Manufacturers
New air compressors of most types and sizes pro* duced by major compressor manufacturers can be manufactured for lubrication with Pydraul. The manufacturers listed (below) have manufactured compressors equipped for Pydraul, upon specifi cation of the buyer, for over ten years. Many com pressors have operated on Pydraul lubricants con tinually with exhaust air temperatures of 350F. Pydraul is also used to lubricate cylinders in com pressors operating at pressures over 4500 psig.
American Messer Corporation Atlas Copco Bury Compressor Company Carrier Corporation Chicago Pneumatic Tool Company Clark Brothers Company,
division of Dresser Industries Cooper-Bessemer Corporation DeLaval Steam Turbine Company Gardner-Denver Company Ingersoll-Rand Company Joy Manufacturing Company Kinney Manufacturing,
division of The New York Air Brake Company Norwalk Company, Incorporated Schramm, Incorporated Worthington Corporation
TOWOLDMON0035664 WATER_PCB-00020133
MM
..-tiZi*-....
Safe
Handling
There has been no reported case in many years of service to indicate any special health hazard with Pydraul air compressor lubricants. However, as with all specialized industrial fluids and lubricants, certain precautions are advisable. Animal toxicity screening studies indicate Pydraul AC-A, Pydraul AC-A Winter Grade 28 and Pydraul 625A may be considered only slightly toxic from the standpoint of accidental ingestion or skin ab sorption. It does not appear to have any signifi cant potential for skin or eye irritation. Because these fluids have excellent solvent properties, re peated or prolonged skin contact could lead to de fatting and drying of the skin; thus reasonable personal hygiene practices are recommended to avoid prolonged and repeated skin exposure. If Pydraul fluids are splashed or sprayed into the eyes, moderately severe pain and irritation may
result. There is no evidence to show Pydraul causes permanent eye tissue damage. Eyes should be thoroughly flushed with water and the workman referred to a physician. To relieve irritation, physi cians have used 1% pontocaine solution, as well as the ophthalmic cortisone acetate solution.
Vapor inhalation. At room temperatures, there is no vapor inhalation hazard from Pydraul fluids. Although there has been no problem with high concentration of vapors, inhalation of vapors at high temperatures should be prevented.
If the compressed air is to be used for air line masks, respirators and other inhalation equipment, it is always recommended that a commercial filter cartridge for air-supplied masks be incorporated in the compressor air line to remove any foreign matter. This is good industrial practice for any compressor fluid or lubricant.
UblOWd
^
TOWOLDMON0035665 WATER_PCB-00020134
DISTRICT SALES OFFICES ALL DIVISIONS
AKRON, OHIO 44313 260 Springside Drive Montrose Development Park Tel. (216) 666-4111
ATLANTA, GEORGIA 30326 Lenox Towers East 3400 Peachtree Rd. N. E. -- Suite 1711 Tel. (404) 577-2260
BOSTON, MASSACHUSETTS 02149 Everett Station Tel. (617) 387-5010
CHICAGO, ILLINOIS 3158 Des Plaines Ave. Des Plaines, Illinois 60018 Tel. (312) 296-6688
CINCINNATI, OHIO 45206 1501 Madison Road Tel. (513) 751-6707
DETROIT. MICHIGAN 48235 500 Northland Towers East Tel. (313) 357-0910
HONOLULU, HAWAII 96812 205 Pacific International Bldg. 677 Ala Moana Blvd.. P. 0. Box 3824 Tel (808) 531-2744
HOUSTON, TEXAS 77027 1301 Post Oak Tower 5051 Westheimer Road Tel. (713) 621-9550
LOS ANGELES, CALIFORNIA 90022 6670 . Flotilla St. Tel. (213) 723-2492
NEW ENGLAND AREA Hydrocarbons & Polymers Div. 730 Worcester St.. Indian Orchard, Mass. 01051 Tel. (413) 788-6911 Plastic Products & Resins Div. P. O. Box 2130. Springfield, Mass. 01101 Tel (413) 788-6911
NEW YORK, NEW YORK 10017 277 Park Avenue Tel (212) 922-4111
ST. LOUIS, MISSOURI 63166 800 N. Lindbergh Blvd. Tel (314) 694-1000
SAN FRANCISCO BAY AREA 2710 Lafayette, Santa Clara. Calif. 95052 Tel. (408) 243-0414
SEATTLE, WASHINGTON 98121 2112 Third Avenue Tel (206) 622-4203
WILMINGTON. DELAWARE 19803 2005 Concord Pike, Fairfax Tel. (302) 658-6531
Additional District Offices are maintained by:
Agricultural Division
ALLENTOWN. PENNSYLVANIA 18104 Park Professional Building 2200 Hamilton Street Tel. (215) 437-5471
DECATUR, ILLINOIS 62523 207 Decatur Professional Building 363 South Mein Street Tel (217) 423-6031
DES MOINES. IOWA 50310 312 Merle Hay Tower Tel. (515) 276-8503
FREMONT, NEBRASKA 58025 150 South Main Street Tel. (402) 727-1230
INDIANAPOLIS. INDIANA 46205 Suite 218. 4000 Meadows Drive Building Tel. (317) 547-9148
KANSAS CITY, MISSOURI 64133 701 Blue Ridge Tower 4240 Blue Ridge Boulevard Tel. (816) 353-8060
LULING, LOUISIANA 70070 P. O. Box 174 Tel. (504) 784-6263
MANKATO, MINNESOTA 56001 111 Madison East Tel. (507) 387-3406
MEMPHIS, TENNESSEE 38104 303 Union Plaza Building 1635 Union Avenue Tel. (901) 278-7811
MUSCATINE, IOWA 52761 P. 0. Box 473 Tel. (319) 263-1331
Hydrocarbons & Polymers Division-Lion Oil
EL DORADO, ARKANSAS 71730 Lion Oil Building Tel. (501) 863-3111
JACKSON, MISSISSIPPI 39209 P. 0. Box 10937. Westland Siation Tel. (601) 352-3646
N. LITTLE ROCK, ARKANSAS 72119 410 West 8th Street. P. O. Box 5821 Tel. (5011 376-2437
MEMPHIS. TENNESSEE 38113 1023 Riverside Drive, P 0. Box 13248 Tel. (901) 948-4451
Organic Division (Rubber Instruments)
AKRON. OHIO 44311 920 Brown Street. P. 0. Box 2307 Tel. (216) 434-1962
Plastic Products & Resins Division
EUGENE, OREGON 97401 P. O. Box 1819 855 Seneca Road Tel. (503) 342-7201
KENILWORTH, NEW JERSEY 07033 Noith Seventh Si. & Monroe Ave. Tel. (201) 276-2900
Textiles Division
ATLANTA. GEORGIA 30303 Atlanta Merchandise Mart 240 Peachtree St,, N. W. Tel. (404) 577-2260
CHARLOTTE, NORTH CAROLINA 28210 6230 Feirview Road. Suite 400 Tel. (704) 364 0110
GRFENVILLE. SOUTH CAROLINA 29606 McAlister Plaza P. 0. Bo* 5564, Station B Tel (803) 239-9171
NEW YORK. NEW YORK lOOOt 350 Fifth Ave. Tel (212) 556-5100
051047V
TOWOLDMON0035666 WATER_PCB-00020135
0510^80
Monsanto
"Nothing contained heiein is to be construed as a recommendation to use any product in conflict with any patent MONSANTO MAKES NO WARRANTIES AS TO THE FITNESS OR Mf RCH ANT ABU IT Y 0 ANY PRODUCTS REFERRED TO. no guarantee ol satislictciy results from reliance upon contained mlormation or recommendations, and disclaims all liability tor any resulting loss 01 damage "
Monsanto Company / Functional Fluids / 800 North Lindbergh Blvd. / St. Louis, Missouri 63166
0770 161IRA
Litho in U. S. A.