Document 1gea4j4p8LLk4q9BJGQ9Y8jXd
i: ' .
-'
$
.fr;
,, ?
. ' '! ?
.
'> V
V:. `
L\
{ f' I:
]
'
U
r% -
i\
DIRECTIONS FOR TEST NO.
c. m icrT-
FLASH ASP FLAME POINTS
/ y - v y - HS
METHOD:
The cup shall be supported bya metal plats i" (.635 cm) In thickness and
I 6 inches (15*24 cm) in width* The plats shall bo of brass, cast iron,
wrought iron, or steel* 3& the center of the plate there shall be a plane
depression 1/32* (,079 cm) In depth, and ef Just sufficient diameter to fit
cup* There shall be a circular opening 2 3/16" (5*50 cat) in diameter,
cut thpipthe plate, centering with the center ef the above mentioned do-
pression* The plate shall be covered with a sheet of hard aebestoa board
! 1/4" in thickness, and of the same shape as the metal plate* There shell
j be cut in the center of the asbestos board a circular hole Just fitting the
i cup* Heat may be supplied from any convenient source* The use of a gas
i burner, electric heater, or alcohol lamp is permitted, but under no circum-
| stances arc products of combustion or free flame allowed to come up around
i the cup* The source ef heat shall be centered under the opening in the plate
! and shall be of a type that will not produce local superheating. If drafts
' or excessive radiation by any suitabletypo of shield, that does not project
; above the upper surface ef the asbestos board* The thermometer shall con
; form to the requirements of thermometer Kq, 8* (See ASTIi table ef therao-
meters, $00.2 p* 2)
.
| / ;...
. ; ' PRQClDURij
_ .....
.........
: The thermometer shall be suspended or held in a vertical position by any
| suitable device, the bottom of the bulb shall be 1/4 in* v*635 cm) from | the bottom of the dup, and above a point half way between the center and | back of the cup* The cup shall be filled with oil to be tested in ouch a
! manner that the top of the meniscus Is exactly at the filling line at room temperattre. The surface of tho oil shall be free from bubbles. There
i shall be no ell above the filling lino or outside of apparatus* The test
| flame shall be approximately 5/32* (*397 cm) in diameter*
j The test flame shall be applied as the temperature road on the vheraometfer
; reaches each successive $0F mark* The flame shall pass in a straight line,
(or on tho ciroumferenco of a circle having a radius of at least 6 inches.) across the center of tho cup and at right angles to the diameter passing thru the thermometer. The test flame shall, while passing across tho cnar! face of the oil, bo in th# piano of the upper edge of the cup* The time for the passage of tho tost flame across the cup shall be approximately 1", /
i The oil shall bo heated at a rate not exceeding yflt per minute temperature
; rise till a point la reached approximately 100*7 below the probable flash
point of tho oil* Thereafter the irate of heating shall be decreased and for
: at leaet the last $0F before the flash point ie reached the rate shall be
net less than 9F or more than 11F par minute*
-
: The flaeh point shall be taken as the temperature read on the thermometer
when a flash appears at any point on the surface of the oil* The true flash
must not be confused with a bluish halo which sometimes surrounds the test
I flame*
'
-
i
DSW 330801
STLCOPCB4077445
':
X
DIRECTIONS FOR TEST NO.__________
giiR.igr.T-
FLASH AND FLAME POINTS - Page 2
v - _ - : ,
METHOD:.
After determining the flash point, the hosting ehall bo continued at tha
specified rate of 9F to Xl*t par minute, and application of tho toot flame
i
ahall be made to fura for a
at the perold
specified Intervale until of at least five seconds*
the oil ignites and continues The method of application
of tha flame ehall be the ease as for flash point* The temperature read
at the tine of iheflaae application, which Causes burning for a period of
five seconds or more, ehall be recorded as the fire point*
The flash point and fire point tests shall be made In a room or compartment ft from air drafts* The operator shall avoid breathing over the surface of the i oil* H is desirable that the room or compartment may be darkened sufficient}
so that the flash may bo readily discernible.
FAB:cm 1-26-45
f
0S>N **0802 STLCOPCB4077446