HEATING VENTILATING AIR CONDITIONING GUIDE 1944 Table 6. Tabulated Data for Example 3 Circuit No. S. Available ph 1226 milinches Section 0-4 4-5. 5-6 6-3 3-7 7-8 8-9 9-0 Total Load Mbh 45 35 20 20 20 20 35 45 Pipe Length Ft 3.5 10.0 12.0 6.5 9.5 12.8 13.8 2.3 70.4 Elbows No. 2.5 2.0 0.0 5.5 5.5 1.0 2.5 2.5 < 21.5 Pipe Size In. 1X ix 1 1 1 lX IX Equivalent Length, Ft Unit Friction Total Milinches Friction, per Ft Milinches 11.3 15.2 12.0 17.5 6.3 9.2 3.4 13 71 140 41 228 20.5 14.9 20.3 10.1 13 267 13 194 9.2 187 6.3 64 121.8 1192 0-4 4-5 5-2 2-8 8-9 9-0 Total 45 35 15 15 35 45 Circuit No. 2. Available ph 1226 milinches 6.2 6 9.5 7 1 18.7 X 20.4 7.5 24.0 71 140 140 490 187 64 1092 0-4 4-10 10-1 1-11 11-9 9-0 Total 45 10 10 10 10 45 Circuit No. 1. Available ph 1226.milinches 9.0 1.5 % 5.0 5.5 X 9.5 11.5 5.5 2.5 X X 11.3 10.7 18.1 15.4 11 46 11 11 71 124 434 199 169 64 1067 Data recorded in Table 6 show that Circuit 3 consists of 70.4 ft of pipe and 21.5 elbow equivalents. Assuming that the average size of the pipe will be IK in., the 21.5 elbow equivalents may be replaced by 21.5 x 2.6 (%x 1.25x1.0), or 56 ft of pipe, which would make the total equivalent length of the circuit 70.4 plus 56 or 126.4 ft of pipe, and the average fh, 1225/126.4, or about 10 milinches per foot. For this unit fh and a temperature difference of 40 F (see Fig. 3), a 1 in. pipe will convey 18 Mbh, a IK in. pipe, 37 Mbh, and a 1)4 in. pipe, 56 Mbh. The pipe sizes for the several sections of Circuit 3 may be selected as indicated in Table 6. Having selected the pipe sizes, the unit friction heads may be found from Fig. 3 and the total friction head calculated and recorded as shown in Table 6. If the grand total, in the present case 1192 milinches, differs materially from the available ph, 1225 milinches, one or more of the pipe sizes must be changed and the calculation repeated until the total fh is practically equal to the available ph of 1225 milinches. It is not necessary, in the design of hot water heating systems, to be extremely careful to have the fh exactly equal to the available ph, because a hot water heating system has the ability to adjust itself to varying conditions of considerable magnitude. For example, in the present case, the calculated fh is 1192 milinches, or about 3 per cent less than the calculated available ph; the water would, therefore, circulate a little faster than con templated and the return temperature would be a little higher than 160 F. This would CHAPTER 16. HOT WATER HEATINC SYSTEMS AND PIPINC immediately lower the available ph and the ph and fh would come into balance at a value higher than 1192 and lower than 1225. Since it is generally not necessary to make extremely refined calculations, Table 1 may often be used instead of the chart of Fig. 3 to determine pipe sizes. For example, in the present case, Table 1 shows that for an fh of 10 milinches a IK in. pipe would convey 28 Mbh with a temperature difference of 20 F or 56 Mbh with a temperature difference of 40 F. Since the IK in. pipe in Fig. 10 is to convey only 45 Mbh with a temperature difference of 40 F, or only 22.5 with a temperature difference of 20 F, it is evident from the table that the fh will be between 6 and 8 milinches. For 6 milinches the heat con veyed is 21.2 and for 8 milinches, it is 24.8; for 22.5 Mbh, thefh would be estimated to be about 6.5, which would be sufficiently accurate for the present calculation. Having completed the design of Circuit 3, it is simple to design Circuit 2 because it has four sections in common with Circuit 3 and it is only necessary to design Sections 5-2 and 2-8, as shown in Table 6, so that the total fh of Circuit 2 will be practically equal to the total fh of Circuit 3. Having completed the design of Circuit 2, it is necessary to design Circuit 1, as shown in Table 6, so that its total fh will be approximately equal to the totalfh of the other two circuits since all three circuits have equal pressure heads. Two-Pipe Forced Circulation System Example 4. In the design of a system for Fig. 11, as in the design of Example 2, there are three unknowns--pressure head, pipe size, and flow-return temperature difference, any two of which may be assumed and the third found. In the design of a system for Fig. 8, the pressure head and the temperature difference were assumed and the pipe sizesfound. In this case, the pressure head is to be found. Solution. In selecting the temperature difference and the pipe sizes, it should be borne in mind that the first cost of the pipe system and of the radiation is reduced by reducing Fig. 11. Two-Pife Forced Circulation System . 317