Compliance Evaluation Inspection Report Utter Stop June 2023
Submitted to: U.S. ENVIRONMENTAL PROTECTION AGENCY
REGION 8 1595 Wynkoop St. Denver, CO 80202
Submitted by: Eastern Research Group. 14555 Avion Parkway, Suite 200
Chantilly, VA 20151 EPA Contract No. 68HERC21D0007
Task Order 68HERC22F0492 COMPLIANCE EVALUATION INSPECTION REPORT
Date of Report:
June 28, 2023
Date and Time of Inspection: May 16, 2023 at 08:00 am CDT
Weather:
Overcast, 58 Fahrenheit
Facility Contact/Owner:
Owner Address:
201 Main Ave East Rolla, ND 58367
Facility Address:
Facility Phone: Facility ID Number:
1 Utter Stop Road
Belcourt, ND 58316
3050002
Reason for Inspection:
Compliance Inspection
Inspector(s):
, ERG
Utter Stop CEI Report
ii
June 2023
TABLE OF CONTENTS
1. NARRATIVE ..................................................................................................................... 1
2. SUMMARY ........................................................................................................................ 4
ATTACHMENTS
ATTACHMENT A: EPA REGION 8 UST COMPLIANCE CHECKLIST ATTACHMENT B: PHOTOGRAPH LOG ATTACHMENT C: TANK LEAK DETECTION RECORDS ATTACHMENT D: RELEASE DETECTION EQUIPMENT CERTIFICATION ATTACHMENT E: PIPING TESTING RECORDS ATTACHMENT F: OVERFILL AND SPILL PREVENTION RECORDS ATTACHMENT G: OPERATOR TRAINING RECORDS ATTACHMENT H: WALKTHROUGH INSPECTION RECORDS ATTACHMENT I: CERTIFICATE OF REGISTRATION ATTACHMENT J: NOTICE OF INSPECTION
Utter Stop CEI Report
iii
June 2023
Financial Assurance
Ms.
provided a Certificate of Registration that expires on 06/30/2023 showing it is part
of the petroleum tank release compensation fund which is included in Attachment I. No
documentation was provided on the coverage of the deductible.
Physical Inspection
During the site visit, Mr.
reviewed documents on site and observed the fill ports, STPs,
and one dispenser sump, and the ATG monitoring interface for the two USTs on site. Photograph
#1 in Attachment B shows the interface for the Tank Sentinel TS 750 monitoring system.
Attachment C includes an inventory report for the USTs. Mr.
also observed the spill
bucket and fill pipe for the two USTs. An audible external overfill alarm was observed in close
proximity to the tank field. The spill bucket for Tank 1 contained about inch of fuel. The spill
bucket for Tank 2 appeared to be clean and in good condition. Mr.
also observed the
STP for both USTs. Mechanical ALLDs were observed on the STPs. The junction boxes
associated with the STPs were in good condition. The ATG probes were also present in the STP
sump for each of the tanks, and no issues were noted for these during the inspection.
There were four pump dispensers on site and one of these were opened as part of the inspection.
Dispenser piping was entering the secondary containment as shown in Photograph #7 in
Attachment B. Mr.
did not observe signs of leaks at the time of the inspection.
No monitoring wells were observed at the tank field during the inspection. Vent lines are located in the tank field and no obstructions or concerns were noted for the vent lines at the time of the inspection.
Utter Stop CEI Report
3
June 2023
2. SUMMARY
Tank 1 has a 15,000-gallon capacity and stores regular unleaded gasoline. Tank 2 has a 12,000-
gallon capacity and stores premium unleaded gasoline. Tank 1 and Tank 2 are FRP constructed
tanks and were installed in 1994. Passing leak detection results were provided for both tanks for
the previous 12 months. An annual certification for the ATG system was provided during the
inspection. There are four dispensers on site that operate with pressurized flexible plastic piping
so cathodic protection is not required. Passing testing records for the ALLD functionality tests
and the annual line tightness tests were provided. STPs for the tanks have mechanical ALLDs.
No visible signs of a leak were observed. An audible external overfill alarm was observed in
close proximity to the tank field. The spill bucket for Tank 1 contained about inch of fuel. The
spill bucket for Tank 2 appeared to be clean and in good condition. No hydrostatic testing results
for the spill buckets was provided. Tank 1 and Tank 2 are single-walled FRP tanks with double-
walled flexible plastic piping. Cathodic protection is not required. Ms.
is a Class A and
Class B operator. There were no designated Class C operators. Monthly walkthrough inspection
records were provided for the past 12 months but only involved checking the ALLD. The facility
provided a Certificate of Registration that expires on 06/30/2023 showing it is part of the
petroleum tank release compensation fund. No documentation was provided concerning the
deductible. Attachment J contains the Notice of Inspection signed by Ms.
. Mr.
provided a copy to Ms.
and left the premises.
Joseph Watson Date: 2023.06.28 22:34:26 -04'00' Digitally signed by Joseph Watson
Inspector Signature: _________________________________ Date:_06/28/2023________