340 CHAPTER-13 1 1958 Guide For the fan motor, use Equation 16 with a load factor of unity, and omit term Motor Efficiency because the motor is not within the apace. qan = 7.5 X 2544 = 19,100 Btu per hr. Moisture Permeation, Miscellaneous Allowance, and the Load-Lag Estimate: Moisture permeation will be negligible, since this is a comfort job with a good building construction. There would besome heat gain in the ductwork, but this would not be great be cause of the short run involved. Practical judgment for this job would suggest that no adjustment for load-lag need be made to the load as computed. (Refer to Fig. 4). While it is true that inside radiation forms an important part of the total heat gain, it is advisable to be conservative in recognizing the effect of the large, flat, hot roof on the comfort sensations of the occupants. Radiation from the relatively low ceiling, augmented by heat absorption from the lighting fixtures, would produce a sensation of warmth in excess of the nominal effective temperature (see Chapter 6) estab lished by the wet-bulb and dry-bulb temperatures. Hence, it is not desirable to take advantage of every small decrease possible in the peak design load, especially since the peak occurs in mid-afternoon when everything would be rather well warmed. Total Loads and Required'Air Quantity through Conditioning Equipment: The total loads are summarized in the following table: Summary of Total Loads--Example 11 Load Component Sensible Btu/hr Latent Btu/hr All walls, roof and doors................................. Glass areas........................................................ Infiltration 67 cfm............................................ Ventilation Air (1275 cfm X 0.15)................. Occupants.......................................................... Lighting............ ............................................... Motor, fan......................................................... 78,500 5,970 1,085 3,100 17,000 62,700 19,100 Space Load........................................................ 187,455 Ventilation 1275 cfm X (1-0.15)..................... Totals................................................................. 17,600205,055 Grand Total Sensible and Latent............... .................................. 2,270 6,480 21,250 30,000 36,715 . 66,715 271,770 Compute the enthalpy difference ratio from Equation 18. h, -- h, (187,455 + 30,120) X 1076 = 7770. Wi-W. 30,120 From the A.S.H.A.E. psychrometric chart Chapter 3, determine that the appa ratus dew-point is 53.9 F. Compute the effective air quantity (Equation 19). Then, Qr, 187,455 = 7830 cfm. 1.08 (80 - 53.9) X 0.85 (Refer to Chapter 35 for coil selection.) From note under Equation 19 the dry-bulb range will be (80 -- 53.9) X 0.85 = 223 deg, and the dry-bulb temperature of air leaving the coil will be 80 -- 22.2 = 57.8! * The dry-bulb temperature leaving the fan (including the heat supplied by the Jan motor), or delivered into the room, will be (from Equation 21): 187,455 - 19,100 ,, ,,,, , _ l = 80 - --1------------ --- = 80 - 19.9 = 60.1 F. 1.08 X 7830 With good distribution and diffusion, this temperature should not produce objec tionable drafts. .1 Cooling Load 341 The various calculations for the sensible, latent, and total heat loads for Example 11 may be summarized as follows: Example 11: Summary Outdoor Conditions.........................95 DB Space Conditions............................. 80 DB 78 WB 65 WB 0.0168 Humidity Ratio 0.0098 Humidity Ratio Difference........................... 15 0.0070 Sensible Load Transmission Roof 4000 sq ft X 53 X 0.34 =........................ S. Wall 405 sq ft X 6 X 0.41 =....................... E. Wall 765 sq ft X 11 X 0.52 =..................... N. Wall Ex. 170 sq ft X 3 X 0.52 =............... N. & W. Party Wall 1065 sq ft X 2 X 0.26 = Floor None Door 35 sq ft X 15 X 0.59 =..........X............... All Glass and Rest of Doors =......................... Solar Radiation S. Glass 60 sq ft X 13 =.......................... ....... S. Glass (Doors) 35 sq ft X 42 =..;.......... ....... E. Glass (Doors) 18 sq ft X 14 =..................... N. Glass 30 sq ft X 15 =................................... Internal Load Infiltration 67 cfm X 1.08 X 15 =............ Ventilation 1275 cfm X 1.08 X 15 X 0.15......... Lights (12,000 X 1.20 + 4000) 3.41 =............. People 85 X 200=............................................ Motor, Fan 7.5 hp X 2544 =............................ Btu/Hr 72,000 995 4,380 265 550 310 3,020 780 1,470 250 450 1,085 3,100 62,700 17,000 19,100 Total Sensible Space Load.........................................-................... Latent Load Infiltration 67 cfm X 4840 X 0.0071 =........... ............................. 2 270 Ventilation 1275 cfm X 4840 X 0.0071 X 0.15................ ............. 6,480 People 85 X 250 =...... 21 250 187,455 Total Latent Space Load Ventilation Am Which Does Not Become Part of Space. Load sensible 1275 cfm X 1.08 X 15 X (1-0.15) =................ tatent 1275 cfm X 4840 X 0.0071 X (1-0.15) =..................................... _____Grand Total Load..................................... ........................................ 30,000 17,600 36,715 271,770 LETTER SYMBOLS USED IN CHAPTER 13 fraction of incident solar radiation absorbed, dimensionless; subscripts D, d, and t refer to direct, diffuse and total, respectively, 0 solar altitude, degrees, y wall solar azimuth, degrees, c emissivity, dimensionless, S incident angle, degrees. X --= amplitude decrement factor, dimensionless. raction of incident solar radiation transmitted, dimensionless. <j> = ^ J^hiscr-ipts D, d and t refer to direct, diffuse and total, respectively. ifc - ,7 azimuth> degrees. ^ _ w"* azimuth, degrees. b = fFea ,across which heat is being transferred, square feet. faction of air passing through coil which does not contact surfaces, coil by-pass factor.