Heating Ventilating Air Conditioning Guide 1939
water temperature, or furnace bonnet temperature to shut off the burner when the pressure or temperature becomes excessive, a device on the boiler to shut off the burner if the water level falls below safe limits or one which automatically feeds additional water to the boiler, and a device for controlling the gas pressure within desired limits. The main gas valve may be either of the snap action or throttling type.
Sizing Gas-Fired Heating Plants
While gas-burning equipment can be and usually is so installed as to be completely automatic, maintaining the temperature of rooms at a pre determined and set figure, there are in use installations which are manually controlled. Experience has shown that, in order to effectively overcome the starting load and losses in piping, a manually-controlled gas boiler should have an output as much as 100 per cent greater than the equiva lent standard cast-iron column radiation which it is expected to serve. '
Boilers under thermostatic control, however, are not subject to such severe pick-up or starting loads. Consequently, it is possible to use a much lower selection, or safety factor. A gas-fired boiler under thermo static control is sensitive to variations in room temperatures so that in most cases a factor of 20 per cent is sufficient for pick-up load.
The factor to be allowed for loss of heat from piping, however, must vary somewhat, the proportionate amount of piping installed being con siderably greater for small installations than for large ones. Consequently a selection factor for thermostatically controlled boilers must be variable. Liberal selection factors to be added to the installed steam radiation under thermostatic control are given in Fig. 3 of Chapter 13.
Appliances used for heating with gas should bear the approval seal of the American Gas Association Testing Laboratory. Installations should be made in accordance with the recommendations shown in the publi cations of that association.
Ratings for Gas Appliances
Since a gas appliance has a heat-generating capacity that can be pre dicted accurately to within 1 or 2 per cent, and since this capacity is not affected by such things as condition of fuel bed and soot accumulation, makers of these appliances have an opportunity to rate their product in exact terms. Consequently all makers give their product an hourly Btu output rating. This is the amount of heat that is available at the outlet of a boiler in the form of steam or hot water, or at the bonnet of the furnace in the form of warm air. The output rating is in turn based upon the Btu input rating which has been' approved by the American Gas Asso ciation Testing Laboratory and upon an average efficiency which has been assigned by that association.
In the case of boilers, the rating can be put in terms of square feet of equivalent direct radiation by dividing it by 240 for steam, and 150 for water. This gives what is called the American Gas Association rating, and is the manner in which all appliances approved by the American Gas Association Laboratory are rated. To use these ratings it is only necessary to increase the calculated heat loss or the equivalent direct radiation load by an appropriate amount for starting and piping, and to select the boiler or furnace with the proper rating.
230
Automatic Fuel Burning Equipment ;
eiven by the American Gas Association Laboratory is not
The raU" ^,ative rating when considered from the standpoint of only a con efficiencyi but ;s aiso a safe rating when considered from the
capacity a physical safety to the owner or caretaker. The rating that standpo`n ^an appjiance ;s limited by the amount of gas that can be
;s placed up"
production of harmful amounts of carbon monoxide.
u-ne!me limitation applies to all classes of gas-consuming heating
*i- S rps that are tested and approved by the Laboratory. Gas boilers
appliances
ratings up to 14,000 sq ft of steam, while furnaces with
aItings up to about 500,000 Btu per hour are available. (See Chapter 20.)
REFERENCES
. Stoker Information, Bulletin No. 5, Committee of Teh, 307 N. Michigan Ave.,
^Domestic Burners for Pennsylvania Anthracite, Commercial Standard CS48-34
ti c of Comnicrcfi* o' r Lnrp Exoectancy of Domestic Underfeed Stokers for Anthracite, by Allen J
i^Tmnscn?A.I.M.E., Coal Division, Vol. 119, 1936).
Relation of the Size of Bituminous Coals to Their Performance on Small Under. i "cLkers--The Relation of the Size in the Hopper to That Burned in the Retort, hR A Sherman and E. R. Kaiser, Technical Report No. 1, Bituminous Coal Research,
Inc (December, 1935) Pt. I.
c ,, IT ,
Xke Relation of the Size of Bituminous Coals to Their Performance on Small Under-
, i ctnkers--Burning Tests on Four Typical Coals, by R. A. Sherman, E R. Kaiser and
H^R Limbacher, Technical Report No. 1, Bituminous Coal Research, Inc. (July, 1937)
Pt S1t1oker Coals, Anonymous, Bulletin of Chesapeake and Ohio Railway Co., 1935.
A S H.V.E. Research Report No. 907--Study of Performance Characteristics of Oil Burners and Low Pressure Heating Boilers, by L. E. Seeley and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol. 37, 1931, p. 517).
A S H V E Research Report No. 925--A Study of Intermittent Operation of Oil Burners, by L. Ei Seeley and J. H. Powers (A.S.H.V.E. Transactions, Vol. 38, 1932,
** Air Supply and Its Effect on Performance of Oil Burners and Heating Boilers, by
L. E. Seeley, J. H. Powers and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol. 39, 1933,
p. 75). Study of Fuel Burning Rates and Power Requirements of Oil Burners in Relation to
Excess Air, by L. E. Seeley and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol. 40,
1934, p. 319). Oil Burning in Residences, by D. W. Nelson (A.S.H.V.E. Transactions, Vol. 41,
1935, p. 355). Domestic Oil Burners, by A. H. Senner (Mechanical Engineering, November, 1936).
A Study of Oil-Fired Heating Boilers, by R. C. Cross and W. R. Lyman (Heating and Ventilating, October, 1931).
Value of Oil Burner Installation Surveys, by R. C. Cross and W. R. Lyman (Heating
and Ventilating, January, 1931).
Comfort Heating, American Gas Association.
Approval Requirements of Central House Heating Gas Appliances, American Gas Association.
A Method for Determining Fuel Burning Rates in Heating Boilers Fired by Auto matic Devices, by R. C. Cross (Heating and Ventilating, January, 1932).
Heat Losses1 and Efficiencies of Fuels in Residential Heating, by R. A. Sherman and
R. C. Cross (A.S.H.V.E. Journal Section, Heating, Piping and Air Conditioning,
January, 1937, p. 53).
.
Efficiencies and Costs of Various Fuels in Domestic Heating, by R. A. Sherman and R. C. Cross, Technical Report No. 3, Bituminous Coal Research, Inc., (December, 1936).
^Automatic Heating Equipment, American Architect 'Reference Data, No. 7, September,