Document 1Qmkz0oKgDQnxQBqE7qX5q6wX
Heating Systems st^f
Cyclotherm Division
United States Radiator Corporation
Sales and Executive Offices
Oswego, New York
Factory Distributors throughout the United States
CYCLOTHERM STEAM AND HOT WATER GENERATORS
Operate on Cyclonic Combustion prin ciple. Completely automatic with full safety controls. Oil, gas or interchange able gas and oil firing. Only four con nections required.
The Cyclonic Combustion operating principle causes the fuel to be burned while spiraling at high velocity around the inside wall of the combustion chamber, forming virtually a tube of flame. This provides uniform and highly efficient heat transfer over the entire furnace wall without hot spots. Com plete utilization of heat transfer areas provides quick heat as well as greater than 80 per cent efficiency with the re duced maintenance of a two-pass design.
15 to 80 hp models are equipped with "on-off" control; 100 to 500 hp models have modulated control. 80 hp units with modulating controls furnished at customers request. Automatic combus tion safeguard, low water and other safety controls are included.
Sizes from 18 to BOO hp
Pressure Range
Available in standard low pressure units or high pressures up to 200 psi. Hot water generators are also available in all sizes.
Standard Burner Arrangements
Fuel
Cyclotherm Model No.
Light Oil, 1 to 3 C-600 thru C-17,500
Heavy Oil, 5, 6 and
Bunker C
C-2800 thru C-17,500
Gas, mfd., mixed
and natural
C-600 thru C-17,500
Comb. It. oil and gas C-600 thru C-l-7,500
Comb. hy. oil and gas C-2800 thru C-17,500
Model No.
0600 CM000 CM 400 C-2100 C-2800 C-3500 C-4400 C-5200 C-7000 . C-8700 C-10500 C-l2000 C-13800 C-17500
Max. HP Rating
18 30 40 60 80 100 125 150 200 250 300 350 400 500
STANDARD RATINGS AND DIMENSIONS,
Output BTU Per hr
600.000 1.005.000 1.340.000 2,010,000 2.680.000 3.350.000 4.187,500 5,025.000 6.700.000 8,375.000 10.050.000 11,725.000 13.400.000 16.750,000
Steam Units
Steam Per Hr. (Pounds)
600 1,035 1.380 2.070 2.760 3.450 4.315 5.175 6.900 8.625 10,350 12.075 13.800 17.250
Equiva lent Di rect Ra diation (Sq Ft)
2.500 4.185 5.580
8,375 11.165
13.955 17.445
20.935 27,915
34.882 41,875
48.850 55.850 69.764
Hot Water Units
Equiva Gallons lent Di Per Hr rect Ra
(100*Rise) diation . (Sq Ft)
743 1.240
1.655 2,480
3.305 4,135
5.170 6,205 8.270
10,337
12.405 14.475
16,540 20.674
4.005 6.700 8,930 13.400
17.865 22.330
27.915 33,500
44,665 55,782
66,900 78,115
89,330 111.564
Overall Dimensioni (Inches)
Length Height Width
71 44 27|
80) 54
41
110) 54
41
124 63! 45)
152 66) 55
162 73) 64
173) 84) 68)
197) 91) 75
224) 98) 81
251) 98) 81
252 102) S8
252 102) 88
252 102) 88
264 102) 88
1470
Heating Systems iSf8'
The Dewey-Shepard Boiler Co.
Sales Office: 1311 N. Capitol Avenue, Indianapolis, Ind.
STEEL FIRE TUBE BOILERS & HEATERS GAS & OIL FIRED
VERTICAL FIRE TUBE UNITS capacities 96,000 to 1,000,000 Btu ASME CODE CONSTRUCTED
All Dewey-Shepard boilers and water heaters (oil and gas fired) are built on the pat ented "Tube within a Tube" principle. All units are jacketed with fiber-glass insula tion ready for instant hook-up.
Oil Burners Underwriters Approved. Gas Burners A.G.A. Listed. Boilers Automatically Welded. Built-in Coils Optional.
Model
NET RATING Water, Sq Ft
' Steam, Sq Ft
B 560 C 756 D 840 E 1120 F 1400 G 1540 H 1960 I 2120 J 2750 K 3000 L 4480 M 5960
350 470 520 700 875 965 1230 1330 1720 1895 2800 3730
Boiler ratings do not include allowance for Built-in CTofls.
* If piping and pick-up loss exceeds 20 percent of installed radiation, allow for such added loss.
OIL and GAS BOILERS and WATER HEATERS
Dewey-Shepard's patented "Tube within a Tube" principle gives you 80 per cent or
more heat absorption, resulting in pre-heating the incoming cold water before it
comes in contact with the metal surfaces to which radiant heat is being applied.
There is one square foot of heating surface for every gallon of. water, transferring
every possible unit of heat to the water, resulting in EFFICIENT, ECONOMICAL
OPERATION . . . plus many other advantages for your customers, such as:
LESS FUEL USED*LOWER INSTALLATION COST NO LIME--NO SCALE*
20 PER CENT LESS HEAT LOSS THROUGH THE STACK*NO EXPANSION,
CONTRACTION OR CONDENSATION* CLEANEST HEAT POSSIBLE* SUFFI
CIENT HOT WATER AT ALL TIMES
DEWEY-SHEPARD'S NEW OIL and GAS FIRED "COUNTER FLOW" BOILER
Designed for use with Baseboard Radiation, Copper Convectors, and Radiant Panel
with forced circulation and small pipe sizes.
SPECIFICATIONS
Output
Net Btu 95,200
Net Rating 540 EDR
Heating Surface 19 sq ft
Site 31 in. x 19 in. x 19 in.
Shipping Weight
300 Boiler 55 Burner
1471